Incite Fire Sigma-XT Installation And Operation Manual

Fire alarm and extinguishant system warning signs
Hide thumbs Also See for Sigma-XT:

Advertisement

Quick Links

Sigma-XT
Fire Alarm and
Extinguishant System
Warning Signs
Installation and
Operations Manual
Serial Communications Type
Australia Version 1 – October 2011

Advertisement

Table of Contents
loading

Summary of Contents for Incite Fire Sigma-XT

  • Page 1 Sigma-XT Fire Alarm and Extinguishant System Warning Signs Installation and Operations Manual Serial Communications Type Australia Version 1 – October 2011...
  • Page 2: Table Of Contents

    Index Page Table of Contents Overview ..............................3 Installation ..............................3 Cabling ............................... 4 Configuration ............................. 5 485 Serial Connected ......................... 5 4.1.1 Functions ........................... 5 4.1.2 Addressing ..........................5 All Signs .............................. 5 Connections ............................... 6 485 Serial Connected ......................... 6 NON 485 Serial Connected ........................
  • Page 3: Overview

    1 Overview The illuminated warning signs provide a clear, visual and audible warning for a variety of applications. Standard units are available to provide warning of a fire alarm or extinguishant release but the display may be customised to show any text on several coloured backgrounds. Warning signs have two levels of operation in which the top and bottom halves of the sign may be split to show an initial warning and then additional text for a reinforced warning, or if required both halves can be activated at once.
  • Page 4: Cabling

    3 Cabling The back box has two 20mm knockouts in the top, bottom and back and one 20mm knockout tin each side. Knockouts can be removed by sharply tapping them and when loose, pushing them back and forth until they break off.
  • Page 5: Configuration

    4 Configuration The warning sign can be configured to illuminate in a variety of signals from the serial bus by setting the DIP switch. Separate DIP switches are provided for the top and bottom sections of the warning sign. 4.1 485 Serial Connected 4.1.1 Functions FIRE The sign will illuminate on a fire signal.
  • Page 6: Connections

    5 Connections 5.1 485 Serial Connected Note: Only 3 warning signs are to be permitted to be connected to the 24V “Status Power” output on the Sigma XT panel. Should more than 3 signs be required, they must be powered from the 24V supply protected via a separate inline fuse.
  • Page 7: Non 485 Serial Connected

    5.2 NON 485 Serial Connected When 485 communications is not used, wiring must be terminated to 24V Trigger terminals. Note: This connection is not suitable for the System Inoperative sign which will illuminate on loss of 485 communications. +24V LVL2 CONTACT LVL1 CONTACT TRIGGER WARNING SIGN...
  • Page 8: Technical Specification

    #2 input operated #1 input operated #1 and #2 inputs operated 6 Technical specification Size 300mm X 195mm X 50mm Construction 1.2mm filly welded sheet steel IP Rating IP40 Finish Epoxy powder coated Colour (lid and box) BS00 A 05 grey fine texture Operating voltage 15V to 30V DC Current consumption...
  • Page 9 Sydney Block Y, Unit 1, 391 Park Road, REGENTS PARK NSW 2143 Mail: PO Box 508 GYMEA NSW 2227 Phone: 1300 INCITE (1300 462 483) | 02 9644 7144 Fax: 02 9644 7255 Email: sales@incitefire.com.au Technical support: support@incitefire.com.au Melbourne Address: Unit 120, 45 Gilby Road, MT WAVERLEY VIC 3149 Phone: 03 9544 2211 Fax: 03 9544 2212 Email: salesvic@incitefire.com.au...