Installation

Busbar
The Busbar Sections are secured to a framing system,
such as Unistrut®, using the Hanging Brackets as shown
below. The bar can be secured both on its fl at or on its
edge.
Before lifting a Busbar Section, ensure that a detailed
risk assessment is carried out for the lifting procedure
being performed in that specifi c area.
Powerbar recommend that the hanging brackets must be
mounted no more than 750mm / 30" from the center of the
joints. Care is to be taken not to damage ends of the busbar
during installation.
Powerbar recommends the hanging brackets be mounted
no more than 1.5 metres / 5' apart. Ensure that each section
of busbar has at least one set of fi xing brackets fi tted and that
the Busbar is level and plumb before fi nal tightening of all
joints. Either drop rod or unistrut style hanging brackets are
supplied depending on the client's request.
* Please note: Powerbar hanging bracket's must be used.
It is the responsibility of the support system supplier to ensure their
system can safely support the weight of our product.