*. Air delivery values are based on operating voltage of 230v, wet coil, without filter or electric heater. Deduct filter and electric heater pressure drops to obtain static pressure
available for ducting.
†. Standard Cubic Feet per Minute
‡. Factory-shipped cooling speed.
NOTES:
1. Do not operate the unit at a cooling airflow that is less than 350 CFM for each 12,000 Btuh of rated cooling capacity. Evaporator coil frosting may occur at airflows below this point.
FILTER SIZE
500
600
in. (mm)
20X20X1
0.05
0.07
(508X508X25)
20X24X1
—
—
(508X610x25)
24X30X1
—
—
(610X762x25)
24X36X1
—
—
(610X914X25)
HEATER kW
800
5-20
0.033
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
Table 5 – Wet Coil Air Delivery
AIR
†
DELIVERY
0.1
0.2
SCFM
905
695
SCFM
920
830
SCFM
1015
990
SCFM
1060
1030
SCFM
1165
1130
SCFM
995
875
SCFM
1055
1005
SCFM
1210
1175
SCFM
1225
1180
SCFM
1355
1335
SCFM
1195
1165
SCFM
1250
1210
SCFM
1410
1370
SCFM
1430
1380
SCFM
1535
1495
SCFM
1400
1360
SCFM
1455
1415
SCFM
1480
1425
SCFM
1535
1505
SCFM
1645
1600
SCFM
1580
1545
SCFM
1645
1610
SCFM
1750
1725
SCFM
1780
1755
SCFM
1905
1875
SCFM
1705
1675
SCFM
1755
1720
SCFM
1880
1850
SCFM
1900
1875
SCFM
2010
1985
Table 6 – Filter Pressure Drop (IN. W.C.)
700
800
900
1000
1100
0.08
0.10
0.12
0.13
0.14
—
0.08
0.09
0.10
0.11
—
0.04
0.05
0.06
0.07
—
—
—
—
—
Table 7 – Accessory Electric Heat Pressure Drop (IN. W.C.)