Installation Instructions V-Traq™ Field Installed Kit Precedent™ Packaged Rooftop HVAC Units Model Used with: BAYTRAQ001* Precedent BF Cabinet BAYTRAQ002* Precedent CDE Cabinet SAFETY WARNING Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training.
Page 2
Introduction Read this manual thoroughly before operating or servicing this unit. WARNING Proper Field Wiring and Grounding Warnings, Cautions, and Notices Required! Safety advisories appear throughout this manual as Failure to follow code could result in death or serious required. Your personal safety and the proper operation of injury.
Page 3
Introduction Trademarks WARNING All trademarks referenced in this document are the Follow EHS Policies! trademarks of their respective owners. Failure to follow instructions below could result in death or serious injury. • All Trane personnel must follow the company’s Environmental, Health and Safety (EHS) policies when performing work such as hot work, electrical, fall protection, lockout/tagout, refrigerant handling, etc.
General Information This document gives detailed instructions for installing a Traq Outdoor Air Monitoring assembly and controls in Precedent units equipped with the factory Low Leak Damper Economizer option. For startup notes, see “Verify System Operation,” p. The Traq field installation instructions are categorized by Precedent cabinet size.
Installation Precedent Cabinet with Low Leak from the top edge of the panel. Each hole from the top will be spread 3.50-inch between each other. Economizer (BAYTRAQ001A) Figure 3. Dimensions of hole locations The Traq airflow measurement system should be installed according to the following steps: 1.
Page 7
Installation 6. By this point, the assembly should be structurally 12. Connect the provided air tubing between the Traq sound enough to no longer require support from the assembly and the VCM control module. Be sure to second technician. match the high and low connections on the Traq assembly with the high and low connections on the 7.
Installation Precedent Cabinet with Low Leak Figure 10. Dimensions of hole locations Economizer (BAYTRAQ002A) The Traq airflow measurement system should be installed according to the following steps: 1. Remove the outdoor air hood of the unit to gain access to the section behind, once the panels are removed, the low leak economizer dampers should be visible.
Page 9
Installation 6. By this point, the assembly should be structurally routing as the factory wiring. Figure 13 shows the open sound enough to no longer require support from the RA section. second technician. 12. Connect the provided air tubing between the Traq 7.
Verify System Operation UC400 Application Notes cooling algorithm from opening the economizer dampers. A 10 VDC signal may be applied to the damper actuator to verify proper direction of • This unit is factory equipped with the Traq outside air operation.
Verify System Operation Object Data Points List (UC400) Table 2. Object data points Instance Object Name Point Reference Read/Write Description Analog Inputs Outdoor Air Velocity UI1.analogValue Read Reliatel Economizer Signal UI2.analogValue Read Analog Outputs Outdoor Air Damper AO1.analogValue Read 2-10 VDC Output Analog Values Default Setpoint: 0 cfm, Range: 0- Minimum Outdoor Air CFM Setpoint...
Page 12
Trane and American Standard create comfortable, energy efficient indoor environments for commercial and residential applications. For more information, please visit trane.com or americanstandardair.com. Trane and American Standard have a policy of continuous product and product data improvement and reserve the right to change design and specifications without notice.