elco ELM-4D1P Instruction Manual

elco ELM-4D1P Instruction Manual

Electrical multifunction meter

Advertisement

Quick Links

 
INSTRUCTION MANUAL
IM443-U v0.7
ELM-4D1P
GENERALITY
These digital multimeters allow to monitor all the electrical parameters
present on a distribution line. The local display of 30 electrical parameters
is carried out by 4 display with red LED guaranteeing a good and
contemporary reading of more measures. A simple front panel completes
the intuitive selection of several electrical parameters, with a great quantity
of information. These instruments, over of the instantaneous measures,
display the maximum peak of the main parameters (maximum peak and
maximum demand). The presence of the serial port communication
EIA485 (option) allows the connection in network of more instruments to
realize centralized measure networks.
These multimeters replace in a unique device, all the functions of
voltmeters,
ammeters,
varmeters, frequency meters permitting a great economic saving, a reduction of dimension and the wiring energy and
a simplification in the purchase and management of the instruments because this is a model usable at all of need of
local measure in the electrical panel, machine, etc.
AVAILABLE MODELS
It's available one model for DIN rail mounting.
-
ELM-4D1P-485A basic version in execution for DIN rail mounting 35
mm with serial output (RS485) and with analog output
OPTIONS
- Power Supply: 20÷60 Vac / 24÷72 Vcc (-C1)
- Power Supply: 85÷230 Vac / 90-250 Vcc (-C2)
- Insulated current inputs (-T)
MEASURED PARAMETERS
parameters
phase and three phase voltages
phase to phase and three phase system voltages
phase and three phase currents
neutral current
phase and three phase power factors
phase and three phase active powers
phase and three phase system reactive powers
phase and three-phase system apparent powers
frequency
temperature
three phase system active energy
three phase system reactive energy
three phase system apparent energy
hour counter
average and peak values (maximums):
maximum phase voltages
maximum phase currents
maximum neutral current
maximum three-phase powers
maximum average phase currents (maximum demand)
maximum average neutral current (maximum demand)
maximum average three-phase powers (maximum demand)
average phase currents
average neutral current
average three-phase powers
ELM-4D1P
ELECTRICAL MULTIFUNCTION METER
energy
meters,
cosphimeters,
instruction manual
wattmeters,
unit of measurement
[V-kV]
V
[V-kV]
V
[A-kA]
A
[A-kA]
A
PF
[W-kW-MW]
W
[VAr-kVAr-MVAr]
VAr
[VA-kVA-MVA]
VA
[Hz]
Hz
[°C]
T
[kWh]
Σ kWh
[kVArh]
Σ kVArh
Σ kVAh
[kVAh]
[hr]
h
[V-kV]
V
[A-kA]
A
[A-kA]
A
[W-VAr-VA (k-M)]
Σ W
[A-kA]
I
[A-kA]
A
Σ W
[W-VAr-VA (k-M)]
[A-kA]
A
[A-kA]
A
[W-VAr-VA (k-M)]
Σ W
IM443-U v0.7
initial identification
V
V
L1-N
L2-N
L3-N
V
V
L1-L2
L2-L3
L3-L1
A
A
L1
L2
L3
n
PF
PF
L1
L2
L3
W
W
L1
L2
L3
VAr
VAr
L1
L2
VA
VA
L1
L2
L3
L1
V
L1-N max
L2-N max
A
L1 m x
a
L2 max
n max
Σ VAr
max
max
I
L1 max (avg
)
L2 max (avg)
n max (avg)
Σ VAr
max (avg)
max (avg)
A
L1 a g
v
L2 avg
n avg
Σ VAr
avg
avg
Σ V
L-N
Σ V
L-L
Σ A
Σ PF
Σ W
Σ VAr
L3
Σ VA
V
L3-N m x
a
A
L3 max
Σ VA
max
I
L3 max (avg)
Σ VA
m x (avg)
a
A
L3 avg
Σ VA
avg
pag. 1

Advertisement

loading
Need help?

Need help?

Do you have a question about the ELM-4D1P and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for elco ELM-4D1P

  • Page 1 AVAILABLE MODELS It’s available one model for DIN rail mounting. ELM-4D1P-485A basic version in execution for DIN rail mounting 35 mm with serial output (RS485) and with analog output OPTIONS - Power Supply: 20÷60 Vac / 24÷72 Vcc (-C1) - Power Supply: 85÷230 Vac / 90-250 Vcc (-C2)
  • Page 2: Installation

    For safety reasons, place an external fuse protection at the input voltages, and use adequate cables for the working voltages and currents, with a cross sections from 0,5 to 2,5 mm ELM-4D1P instruction manual IM443-U v0.7...
  • Page 3: Wiring Diagrams

    WIRING DIAGRAMS ELM-4D1P instruction manual IM443-U v0.7 pag. 3...
  • Page 4 N.B. If the multimeters are used on single phase line, the measure are referred on the L1 phase. The others datadisplayed relatives at three phase system are not to consider. ELM-4D1P instruction manual IM443-U v0.7 pag. 4...
  • Page 5 SeTUp. Pressing the A key on the G display will appear the message SET that will remain always displayed during the set of each parameter to highlight the setup phase in running. The set values will be keep also in absence of auxiliary power supply. ELM-4D1P instruction manual IM443-U v0.7...
  • Page 6 8data 1stop-even parity 8.1 paR EVE (version with serial output) bit: 8data 1stop-odd parity 8.1 paR ODD SET PAS Increase Set Password OFF - 0002 ÷ 9999 Decrease Confirm and end of general settings ELM-4D1P instruction manual IM443-U v0.7 pag. 6...
  • Page 7 100 mS to 500 mS, with 100 ms steps by using B key (to increase the value) and C (to decrease the value). Confirm the value pressing the A key. This setting is used by all digital outputs. ELM-4D1P instruction manual IM443-U v0.7...
  • Page 8 To enable the chosen type, press the B key to change the indication on display G from NO to yes. Confirm enabling cancellation, by pressing the A key. The indication on display G change from yes to ---. ELM-4D1P instruction manual IM443-U v0.7...
  • Page 9 ALR HI Decrease (after 0 there is OFF) Set minimum alarm threshold Increase ALR LO Decrease (after 0 there is OFF) Set delay Increase ALR Dl Decrease Confirm and end of digital output settings. ELM-4D1P instruction manual IM443-U v0.7 pag. 9...
  • Page 10 F display will appear ALR DLY and the value expressed in seconds (range 1÷900). The modification of the value is done in the same way of the threshold set. With the confirmation (A key) the set is complete. The programming will be referred to the digital output indicated on G display (DO1 o DO2). ELM-4D1P instruction manual IM443-U v0.7...
  • Page 11 After the confirmation of the end scale on F display will be displayed the message AN with the limit values of the analog output: 0-20 or 4-20 selectable with the B and C keys. Confirm with A key. ELM-4D1P instruction manual IM443-U v0.7...
  • Page 12 R and the number of the instrument that is in communication while if the instrument transmits data, it displays the letter T. VARIABLE LIST three-phase voltage three-phase current neutral current three-phase power factor active power reactive power apparent power phase to phase voltage frequency T°C temperature ELM-4D1P instruction manual IM443-U v0.7 pag. 12...
  • Page 13: Measures Visualization

    L1 display will indicate the first 3 digits, the display L2 the seconds 3 digits and the L3 display the last 3. For example if: L1=000, L2=028, L3=53.2 the reading is 2853.2 kWh. m ax ELM-4D1P instruction manual IM443-U v0.7 pag. 13...
  • Page 14 In some application where the secondary is connected to other instruments apart from the ELM multimeter, some problems could happen concerning the typology of the amperometric inputs. If there are some problem call the assistance service. ELM-4D1P instruction manual IM443-U v0.7...
  • Page 15: Serial Line Connections

    32 instruments. The higher is the number of connected instruments on the same serial line, the lower will be their response speed. DIMENSIONS ELM-4D1P instruction manual IM443-U v0.7...
  • Page 16 (Article 8, 85/374/CEE).     Via Lago di Molveno, 20 – 36015 Schio (VI) Tel. +39 0445 661722 –Fax +39 0445 661792 http://www.elco-italy.com E-mail: info@elco-italy.com; support@elco-italy.com   ELM-4D1P instruction manual IM443-U v0.7...

This manual is also suitable for:

Elm-4d1p-485a