Short form engineers wiring diagram GUIDE and functional explanation Intelligas takes every care in ensuring these products reach you in perfect working order. Each system is tested on dispatch and site induced damage easily detectable. Ensure the operation of this unit is explained fully to the kitchen staff.
Page 2
5amps. KVM-SF ONLY if the panel is supplying the fans directly from the PCB then it should be supplied via a 16amp single phase isolator. If the panel is controlling Inverters and only the output signals are being used then, as above, the panel should be supplied by a 5amp fused spur.
5. OFF (supply sensed on spare input terminals) ON (supply fan sensed on board current sensors) ratings then contact our 6. OFF (temp sensor fitted in kitchen space) OFF (temp sensor fitted in canopy) technical support team. INTELLIGAS intelligas.co.uk Gas safety & control systems...
Page 4
Gas valve output & Mains supply to the panel. 1 x 16 amp Single phase fan speed control single phase for 230v fan output for fans up to 8 amps. or 3 amp if controlling invertors remotely. INTELLIGAS intelligas.co.uk Gas safety & control systems...
Page 5
Relay outputs for supply and Gas valve output & Mains extract fan invertors enable supply to the panel. 1 x 3 amp signal. 0-10v speed reference single phase 230v. for invertor speed control. INTELLIGAS intelligas.co.uk Gas safety & control systems...
Page 6
Link these terminals if not being used. Connect an extra estop button or buttons here, create a closed loop if more than one button is installed, link if not required. INTELLIGAS intelligas.co.uk Gas safety & control systems...
Page 7
The 0 -10v signal will the set point (adjustment on the fascia rise and fall with the selected speed on the front of control panel) has been reached. the panel. INTELLIGAS intelligas.co.uk Gas safety & control systems...
Page 8
Run the fans up and down stopping at each increment of speed to ensure that the current sensor light remains green. This will prevent nuisance tripping. 24 hour Technical Support 02381 290444 INTELLIGAS intelligas.co.uk Gas safety & control systems...
Page 9
Intelligas gas proving system mechanical layout Installation option 1 Dungs gas pressure Alternatively, the gas pressure switch can switch set to 15 bar be made into the test point on the gas valve. Ensure the downstream test point is used!