Technical Data - Schuch e864 12L Series Operating Instructions Manual

Explosion-proof led emergency light fitting
Table of Contents

Advertisement

2.5 Instructions for special versions with remote cutoff switch
Special versions of these lighting fixtures are equipped to be connected to a remote cutoff switch.
Through a remote cutoff switch (isolated switching contact) it is possible to remove the light fitting from
operation, e.g. during maintenance.
The remote cutoff switch must be closed during normal operation of the special light fitting.
If the remote switch is open, there will be no emergency lighting in the case of a power outage.
A change to the switch position of the remote cutoff switch is only indicated if the fixture is connected
to a power supply.
 If no power supply is present, when the remote switch is closed (resetting the
deactivation) the light fitting will not enter emergency lighting mode!
!
Functionality and operational life tests that are due to be carried out when the remote cutoff switch is
deactivated will be postponed until the deactivation is reset, and will be conducted when the necessary
requirements for the respective test are satisfied.
The interval of functionality and operational life tests are not affected by deactivating the light fitting.

3. Technical Data

Series:
Explosion protection:
Certification:
Rated voltage:
Isolation class:
Ingress protection:
Ambient temperatur:
Power consumption:
Cable entry:
(if supplied)
6
e864. 12L .. / . / .
│ │ └─ Capacity of emergency battery
│ └─ Nominal operating time in case of emergency
└─ Index of luminous flux
Explosion-proof LED Emergency Light Fitting for operating in hazardous
areas of zones 1 and 21.
o
II 2 G Ex db eb [ib] mb op is q IIC T4 Gb
o
II 2 D Ex op is tb IIIC T80 °C Db
IBExU 17 ATEX 1026
IECEx IBE17.0016
220...240 V AC; 50...60 Hz
Switching from mains to battery operation at approx. 180 V
Switching from battery to mains operation at approx. 195 V
I
IP66 (When using an Ex-breathing gland see Section 2)
-30 °C ... +55 °C (Standard versions)
0 °C ... +45 °C (Nominal range according to EN 60598-2-22)
-30 °C ... 0 °C (Emergency duration may be limited)
Versions for higher ambient temperatures see type plate
The power consumption of the LED is dependent on production fluctuations
as well as on the service temperature.
This is why just reference values can be given as follows:
e864. 12L42 / . / . : 35 W
e864. 12L60 / . / . : 49 W
Cable glands with thread size M25 x 1.5
Sealing range: 7 - 17 mm (for 10 - 17 mm remove the small sealing ring)
Torques: Connection thread 3 Nm; Pressing screw 2 Nm
Torque of locking screw: 5 Nm
See information label on the front page when having special versions!