Replacement Parts - A.O. Smith 650A, 740A Installation & Operation Manual

Commercial gas, glass-lined, tank-type low nox water heater
Hide thumbs Also See for 650A, 740A:
Table of Contents

Advertisement

• Do not proceed to Step 5 unless 24V is detected at "24V"
terminal of the Honeywell Module.
5. As soon as the pilot gas valve is energized, check for the
burner pilot flame through the burner peek-hole. If the pilot
flame is established inside the burner, then proceed to
Step 6.
• Turn the burner switch to "OFF" position for at least one minute
to reset the heater.
• Check for 24V between "PV" terminal and "MV/PV" terminal
after 45 seconds prepurge cycle (this 24V may only last
15 seconds starting after 45S prepurge). If there's no 24V at
the "PV" terminal ever, and there's 24V at "24V" terminal, the
Honeywell flame control module needs to be replaced.
• If 24V is detected for a period of 15 seconds, check for the
changes of gas supply line pressure when the pilot gas valve
is energized. If no visible pressure change during the pilot
ignition period, check for loose connection of the pilot valve or
a defective pilot gas valve.
• Adjust the pilot gas regulator setting during the pilot ignition
period (15 seconds window). Do not set too much or too little
pilot gas. This adjustment should only be performed during
the 15 seconds ignition period. A clockwise or counter-
clockwise 0.5 to 1 turn should be able to correct the problem.
Refer to burner manual for detailed pilot gas setting procedure.
• If still no pilot flame inside the burner, check for the spark
ignitor wiring, ignitor tip location and visually check the spark
(burner pilot assembly needs to be taken out for the visual
check). Refer to the burner manual for detailed spark ignition
troubleshooting procedures.
6. Pilot flame established but not detected by the flame control
module. Use Micro Amp meter to measure flame signal during
the pilot ignition period. Refer to burner manual for testing
procedures.
• If pilot flame is confirmed visually through the burner peek
hole, and the flame signal is zero, the thermal-cutoff safety
switch (mounted nearby the flame rod, inside the burner mixing
chamber) may be broken or check for loose wire connections
or low gas switch (mounted inside control panel) may be
broken. If the thermal cutoff switch or low gas switch is broken
(by checking the switch continuity), the switches must be
replaced before the heater can operate again.
• If it's confirmed that the thermal cutoff switch is damaged
(open), call the A.O. Smith Technical Center to analyze the
root cause (too lean combustion) and proper gas/air ratio
adjustment. Flashback will cause the thermal cutoff switch
broken (open).
• If the flame signal is not zero but below 1µA, relocate flame
rod or replace flame rod will be required. Refer to burner
manual for detailed procedure of replacing flame rod.
MOTOR RUNS CONTINUOUSLY, BURNER LIGHTS ON
MOMENTARILY THEN LOCKS OUT OR EXCESSIVE
ON/OFF CYCLE
Under this condition, the burner will start the purge cycle again,
then pilot ignition and main flame cycle. If main flame cannot be
sustained:
1. Make sure main manual gas valve (right after the Robertshaw
gas valve) is fully open;
2. Check for 24V at the Robertshaw gas valve when the main
gas light is on. If there's no 24V at the valve, check loose wire
connection.
3. Check for gas supply line pressure. The gas line pressure
before the valve should be maintained at minimum
8" w.c. when main flame is "ON". If the gas line pressure
drops below 8" w.c. (2 kPa), the service regulator pressure
setting must be increased to keep 8" w.c. (2 kPa) minimum
gas pressure. After adjusting the gas regulator setting, turn
off the heater, make sure the gas line pressure does not
exceed 14" w.c. (3.5 kPa) if it does exceed 14" w.c. (3.5 kPa)
static pressure, the gas supply line size must be increased
accordingly to avoid gas line pressure exceeding 14" w.c.
(3.5 kPa)
4. Check the gas valve manifold pressure (refer to Table 10),
see ADJUSTMENT PROCEDURE to adjust the manifold
pressure.
5. Check for defective gas valve for failing to open or shut off.
6. Verify that the air supply is adequate. The air inlet screen or
blower wheel may be restricted.
7. Check the installation for proper ventilation, see AIR
REQUIREMENTS.
8. Verify the air switch setting is not too high.
9. Check the venting system for the correct sizing, excessive or
insufficient draft, and proper operation of the barometric draft
control, see VENTING.
NOISY BURNER OPERATION
1. Check for flue gas excess O
10). If combustion is too lean (flue gas O
7.5%), the combustion flame front may not be stable, which
will cause noisy operation. See ADJUSTMENT.
2. Check the venting system for the correct sizing, excess or
insufficient draft, and proper operation of the barometric draft
control, see VENTING.
3. If the burner operation is still noisy, then remove the burner,
examine the burner diffuser, blast-tube tip, anti-flashback
corrugated tube, center mixing, refer to the burner manual for
details.
GAS FAILS TO SHUT OFF
Check for defective gas valve or thermostat. If operation is
incorrect, replace.

REPLACEMENT PARTS

Replacement parts may be ordered through A. O. Smith
dealers, unauthorized servicers or distributors. Refer to
the Yellow Pages for where to call or contact the A.O. Smith
Water Products Company, 5621 W. 115th Street, Alsip,
IL 60803, 1-800-433-2545 or visit our website at
www.aosmithwaterheaters.com When ordering parts be sure
to state the quantity, part number and description of the items
including the complete model and serial number as it appears
on the product. Refer to the parts list for more information.
32
or CO
reading (refer to Table
2
2
reads more than
2

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents