Fire-Lite Alarms Honeywell MMF-302-6 Installation And Maintenance Instructions page 3

Six zone interface module

Advertisement

4.
A shunt is provided to disable a maximum of
two unused modules in Class B operation and
Class A operation. Modules are disabled from
the highest address and work downward. If
two modules are disabled, the lowest four ad-
dresses will be functional, while the highest
two will be disabled. For example, in Class B
operation, if the shunt for Address Disable is
placed on "two" and the base switch is set to 28,
the modules will be assigned to 28, 29, 30 and 31 while disabling the
highest two positions.
NOTE: Place unused shunts on single pin to store on board for future use.
NOTE: Power must not be applied to the unit when changing functionality of
the shunts.
FIGURE 8. INTERFACE TWO-WIRE CONVENTIONAL DETECTORS – CLASS B
1. To use a common power supply between multiple MMF-302-6 modules, connect a long power supply jumper from T5 or T6 to T5 or T6 on the adjacent
MMF-302-6 module.
CONNECT MODULES TO
LISTED COMPATIBLE
FIRE•LITE CONTROL
PANELS ONLY
3.9K EOL
RESISTOR
(INCLUDED)
+
CLASS B IDC (TYPICAL)
TO PANEL CONTROLLED
RESETTABLE POWER SUPPLY
+
FROM PANEL OR
PREVIOUS DEVICE
+
TO NEXT DEVICE
SIGNAL LINE CIRCUIT 32 VDC MAX.
TWISTED PAIR IS RECOMMENDED.
FIGURE 9. INTERFACE TWO-WIRE CONVENTIONAL DETECTORS – CLASS A
1. To select Class A, remove the two shunts from the "A/B select" positions.
2. To use a common power supply between multiple MMF-302-6 modules, connect a long power supply jumper from T5 or T6 to T5 or T6 on the adjacent
MMF-302-6 module.
CONNECT MODULES TO LISTED COMPATIBLE
FIRE•LITE CONTROL PANELS ONLY
+
CLASS A IDC (TYPICAL)
TO PANEL CONTROLLED
RESETTABLE POWER SUPPLY
+
FROM PANEL OR
PREVIOUS DEVICE
+
TO NEXT DEVICE
SIGNAL LINE CIRCUIT 32 VDC MAX.
TWISTED PAIR IS RECOMMENDED.
7 8
6
9
5
10
4
11
3
12
13
2
1
14
0
15
TENS
FIGURE 7
+
(+)
(–)
POWER-LIMITED
AND SUPERVISED
INSTALL DETECTORS PER MANUFACTURER'S INSTALLATION INSTRUCTIONS.
IDC 2
+
IDC 3
(+)
(–)
POWER-LIMITED
AND SUPERVISED
Detectors must be UL listed compatible with the module. Install detectors per
manufacturers installation instructions.
WIRING NOTES
• Power-limited circuits must employ type FPL, FPLR, or FPLP cable as
required by Article 760 of the NEC.
• All wiring must be in accordance with the NEC, NFPA 72 and all other
applicable codes and standards. All external power supplies must be
power limited with battery back-up. All external power supplies and
detectors must be UL listed for fire protection signaling applications.
PROGRAMMING
Connect the module to listed-compatible control panels only. Refer to panel
installation documentation to confirm compatibility.
The modules are programmed as devices in each system according to the pro-
gramming instructions in the appropriate FACP manual.
A/B SELECT
A/B SELECT
DISABLE 1
DISABLE 2
DETECTORS MUST BE UL LISTED COMPATIBLE WITH THE MODULE.
6 7 8 9
5
4
3
2
1
0
A/B SELECT
A/B SELECT
DISABLE 1
DISABLE 2
3
BASE ADDRESS
6 7 8 9
6 7 8 9
5
5
10
4
4
11
3
3
12
2
13
2
1
14
1
0
0
15
BASE ADDRESS
6 7 8 9
5
10
4
11
3
12
13
2
14
1
0
15
STATUS
INDICATORS
C0779-04
STATUS
INDICATORS
C0780-03
I56-1900-023
7/1/2022

Advertisement

loading