Installation – FIADMPR102*
Uncrate the damper and locate all parts shown in
Each damper ships with items 1, 2 and 3 attached. Remove
screws completely from items 1 and 2. Remove item 3 by
loosening the three screws but do not remove them. See
figure below.
Figure 1.
Damper components
2
3
Do not
remove screws
WARNING
Hazardous Voltage w/Capacitors!
Failure to follow instructions below could result in
death or serious injury.
Power down the outdoor unit before making contact
with the inverter circuit board. Follow proper lockout/
tagout procedures to ensure the power cannot be
inadvertently energized.Wait for at least 15 minutes to
allow the unit to fully discharge high DC voltage.
Confirm the unit is fully discharged using a CAT III or IV
voltmeter rated per NFPA 70E.
1. Remove unit end panel, retain the screws removed
from the top of panel and the screws removed from
bottom of panel for use later
2. To install the damper, lift into position by fitting the
upper left hand corner around the channel in the
cabinet post. Then pivot the damper into the opening
in the cabinet. Refer to
3. Once the damper is in place, lift the damper and panel
assembly to align the upper two screw holes. Secure
the top by inserting two screws, top left 1 then top right
2. Refer to
Figure 2, p.
4. Pull out on the bottom of the damper and secure
bottom left 3. Refer to
6
Figure
1
Figure 2, p.
6.
6.
Figure 3, p.
6.
1.
Figure 2.
Damper panel
Align (3) tabs on bracket
with (3) slots in panel.
Pivot into place and
secure with three screws
engaged into damper
side panel.
5. Remove the filter access panel. Position the adapter
backing plate inside the filter section. The adapter
backing plate will slip over the three screws that were
loosened in
Figure 1, p.
hole in the adapter backing plate, with the screw
clearance hole in economizer side panel and secure
lower right side of damper with screw four. Refer to
Figure 2, p.
6.
6. Install the bottom blockoff and secure with three
screws. Refer to
Figure 3.
Bottom blockoff
3
Align (3) slots in panel
with (3) tabs on damper
side panel. Pivot panel
into place.
6. Align the screw engagement
Figure 3, p.
6.
Adapter
2
Backing Plate Panel
4
1
Bottom Blockoff
ACC-SVN231A-EN