1 Basic Product Information
1.1 Input Output Control module IOCM43 (hereinafter – IOCM43) is designed:
– to control four alarm loops (hereinafter – ALs) with non-addressable fire detectors;
– to control actuating devices with the help of the outputs with circuit integrity control;
– to control the actuating device with the help of output switching contacts of "dry contact" relay
type.
1.2 IOCМ43 complies with requirements of EN 54-18.
1.3 IOCМ43 is designed for the operation in fire alarm systems developed on the basis of R3500 device.
1.4 Power supply of the logical part and data exchange with the Device are carried out via the addressable
communication line (hereinafter – the ACL) connected to R3500 device.
1.5 ACL is galvanic isolated from IOCM43 power supply sources.
1.6 IOCM43 allows the connection to ACL regardless of polarity.
1.7 IOCM43 is powered via two inputs from external DC power supply sources with the voltage range of
(10.5 – 14) V and (20 – 28.5) V.
1.8 IOCM43 occupies 8 addresses in the system:
– 4 alarm loops;
– 2 outputs with the circuit integrity control;
– 1 "dry contact" output;
– 1 reserve.
1.9 IOCM43 performs the following functions:
– monitoring of alarm loops status;
– control of outputs and output status;
– IOCM43 status indication (see Table 1);
– monitoring of unauthorized opening of IOCM43 enclosure cover;
– testing of the communication over the ACL using the TEST/tamper button.
1.10 IOCM43 is designed for continuous operation at an ambient temperature of minus 10°C to plus 55°C
and a maximum relative humidity of (93 ± 2) %, without condensation.
Table 1
Indicator
LINK
AL1 – AL4
OUT.1, OUT.2
OUT.3
Note
* For more information on these statuses, see the R3500
IOCM43
Indications
Flashing with 5 sec intervals Exchange over the ACL
No light
Flashing frequently during 1
sec
No light
Constant light
One flash every 2 sec
Two flashes every 2 sec
No light
Light on
No light
Light on
Input Output Control module operation mode
No communication
TEST button is pressed
"Normal" status of respective AL line
"Pre-alarm" (Fire 1), "Fire" (Fire 2) status
tive AL line
"Open circuit" status of respective AL line
"Short circuit" status of respective AL line
Respective output of IOCM43 is switched off
Respective output of IOCM43 is switched on
"Relay" contacts are open
"Relay" contacts are closed
device
Operation Manual
*
of respec-
24.08.2021

Advertisement

loading
Need help?

Need help?

Do you have a question about the IOCM43 and is the answer not in the manual?

Questions and answers

Summary of Contents for RUBEZH IOCM43

  • Page 1 1.5 ACL is galvanic isolated from IOCM43 power supply sources. 1.6 IOCM43 allows the connection to ACL regardless of polarity. 1.7 IOCM43 is powered via two inputs from external DC power supply sources with the voltage range of (10.5 – 14) V and (20 – 28.5) V.
  • Page 2 2 Basic Technical Data 2.1 The operating range of supply voltage of IOCM43 from the ACL is (24 – 36) V. IOCM43 current consumption from the ACL in the indicated voltage range is 0.2 mA, max. 2.2 IOCM43 interference protection is adjustable in the range from 0 to 1.9 s.
  • Page 3 Figure 1 3.6 Types of loops for heat and smoke fire detectors control. IOCM43 operation modes with different loop types. 3.6.1 Type 1 – the mode of smoke detectors and manual call points fire alarm loop with circuit integrity control and safe reset. The standard connection diagram and AL status diagram are specified in Figure 2.
  • Page 4 3.6.3 Technological type – is used for connection of technological equipment with “dry contact” or “open-collector” output type with circuit integrity control. The standard connection diagram and AL status diagram are specified for two detectors in Figure 4, for one detector – in Figure 5. IOCM43 24.08.2021...
  • Page 5 3.7.1 To enable operation of electronic key outputs OUT.1, OUT.2 for monitoring the integrity of commu- nication line with the load, diodes or load connection device (hereinafter – LCD) shall be connected directly to the load according to the diagram (Figure 6). Figure 6 IOCM43 24.08.2021...
  • Page 6 3.7.3 Relay output OUT3 of “dry contact” type is controlled by commands from the fire alarm control panel, but it is not provided with the monitoring of the integrity of the communication line. 3.8 IOCM43 marking is located on the label at the inner side of the base of enclosure, and con- tains: a) European standard number –...
  • Page 7 4.5 IOCM43 reference load configuration is carried out in enabled state for each output in turn. The setup shall be performed at the place of IOCM43 installation with the help of menu and controls of R3500 device. To do this, open the device menu, go to "Control and Status" =>"Devices" =>"Total", where in the opened list of all units select the required one and press "Start"...
  • Page 8 – The “Normal” message at the Device screen in the “Device Management” window when selecting IOCM43. 5.2 Select “Addressing” item in the Device menu. Briefly press the TEST/tamper button of IOCM43 (see Figure 1) and check for: – Fast flashing of the LINK indicator for (2 – 3) s;...
  • Page 9 6.1 When maintaining the fire alarm system, at least once every 6 months, check the operation of IOCM43 according to requirements of Section 5. 6.2 Maintenance of devices connected to IOCM43 is to be carried out according to their respective Data Sheets.
  • Page 10 Annex A IOCM43 24.08.2021...
  • Page 11 ООО «КБ Пожарной Автоматики» МЕТКА АДРЕСНАЯ IOCM43 Руководство по эксплуатации ПАСН.423149.111 РЭ 1 Основные сведения об изделии 1.1 Метка адресная IOCМ43 (далее – IOCМ43) предназначена: – для контроля четырех шлейфов сигнализации (далее – ШС) с неадресными пожарными извещате- лями; – для управления исполнительными устройствами с помощью выходов с контролем целостности це- пи;...
  • Page 12 *Подробнее об этих состояниях см. в «Руководстве по эксплуатации на прибор серии R3500» 2 Основные технические данные 2.1 Рабочий диапазон питающих напряжений IOCM43 от АЛС – (24 – 36) В. Ток потребления IOCM43 от АЛC в указанном диапазоне напряжений – не более 0,2 мА.
  • Page 13 рассчитывается по следующим формулам: { ДД �� × (�� ���� �� < 1,23 кОм ( Пожар ) , 0,15 кОм < �� + (�� ���� �� где R – сопротивление одного извещателя в режиме «Пожар». ДД ИТ ИТ рассчитывается по формуле ДР IOCM43 24.08.2021...
  • Page 14 + �� ���� ДТ рассчитывается по следующим формулам: { ДТ × 2 < 25 кОм ( Пожар ) . 11,7 кОм < �� + �� ���� ДТ Сброс состояний «Пред. тревога» или «Пожар» производится только с прибора по АЛС. IOCM43 24.08.2021...
  • Page 15 0 кОм 0,15 кОм 3,3 кОм 25 кОм ∞ 0.15 k 3.3 k 25 k NO – нормально разомкнутые контакты; NС – нормально замкнутые контакты; ОС – открытый коллектор. Рисунок 5- Технологический шлейф с одним датчиком типа «сухой контакт» или «открытый коллектор» IOCM43 24.08.2021...
  • Page 16 3.8 Маркировка IOCМ43 размещена на этикетке на внутренней стороне основания корпуса и содер- жит: а) номер европейского стандарта – EN 54-18; b) степень защиты, обеспечиваемую оболочкой – IР20; c) торговую марку производителя – RUBEZH; d) обозначение изделия – IOCМ43; e) серийный номер; f) версию ПО;...
  • Page 17 – «Текущая нагрузка» – отображает текущую нагрузку, – «Эталонная нагрузка» – отображает ранее сохраненную нагрузку. Если ввести значение текущей нагрузки в строку эталонной, перемещая меню вниз, и выбрать стро- ку «Записать», то на экране высвечивается сообщение «Сохранено» – текущая нагрузка становится эта- лонной. IOCM43 24.08.2021...
  • Page 18 5.1 При правильном выполнении подключений IOCМ43 к системе, настройке и включенном прибо- ре контролировать: – мигание индикатора СВЯЗЬ с периодом (4 – 5) с (таблица 1); – сообщение «Норма» на экране прибора в окне «Управление устройствами» при выборе IOCМ43. IOCM43 24.08.2021...
  • Page 19 5.7 Для проверки формирования и передачи сообщений в прибор о неисправности выходов управле- ния исполнительными устройствами "1" и "2", находясь в окне «Управление устройствами» выбрать тестируемую IOCM43. ВНИМАНИЕ! В результате тестирования возможен запуск подключенных к IOCM43 устройств. Необходимо предупредить противопожарные службы, которым поступают сигналы «Тревога» и «Неисправность», о проведении тестирования.
  • Page 20 6.1 При обслуживании системы пожарной сигнализации регулярно, не реже одного раза в 6 месяцев, проверять работу IOCМ43 по разделу 5. 6.2 Техническое обслуживание устройств, подключенных к IOCМ43, необходимо производить в со- ответствии с паспортами на них. Приложение А IOCM43 24.08.2021...