Advertisement

VP-1405A Advanced Power
V-PM1000 Series, Veesta Power Module Product Series
48V Power Supply & Charger Instructions & User's Manual
3.1.4

Communication Port

1.
Rear Panel port
2.
Port Specifications
3.
Communication Protocol :
4.
Factory Defaults
3.1.5

Alarm outputs

1.
Relay Outputs
2.
Contact Switching Current :
3.
Contact Rating Voltage
4.
Contact / Coil Isolation
Voltage
5.
Contact Short Circuit
Protection
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization.
:
RS-485 Network 2 wires for networking to master
Baud-rate: 2400, 9600, 19200, 38400 bps
Parity: None, Odd, Even
Start/Stop: 1 bit, 2 bits
:
RJ-45 Connection Port
Isolated 2500V communication port
ModBus RTU Protocol
Slave Address: 1~247
Function Support: 03/04/06/16
Factory Defaults: 9600 bps
:
Baud rate: 9600 bps
Parity: None
Start/Stop: 1 bit
Slave Address ID: 200
:
4x Configurable Alarm Output Relays
Default Alarms:
- Alarm Out 1: AC Input Power OK Status
- Alarm Out 2: Any Failure Alarm
- Alarm Out 3: Battery Fail/Under voltage Alarm
- Alarm Out 4: Battery Disconnect Alarm
1.0 A
:
250 VAC
:
3 kV
:
Activate on maximum 1.1 A
Auto-resettable Fuse
Chapter 3 - Specifications