Summary of Contents for Greentrol Automation GreenFlow 2000 Series
Page 1
GF-A2100, GF-A2200 ™ Models Technical Manual Automation, Inc. Air Flow Measurement with PID Control Output and Alarm - Analog Output GreenFlow 2000 Series Greentrol Automation, Inc. Installation, Operation and Maintenance Technical Manual GF-A2100 GF-A2200 Dual Analog Output Air Flow Measurement with...
All brand names, trademarks and registered trademarks are the property of their respective owners. Information contained within this document is subject to change without notice. All rights reserved. GreenTrol Automation, Inc. • 156 Holly View Lane Loris, SC 29569 • Toll Free: 877-4GN-TROL (877.446.8765) • Internet: GreenTrol.com...
Page 4
Table 4. Troubleshooting .................28 GreenTrol Automation, Inc. •...
* Sensor accuracy is the calibrated accuracy of the individual sensor. The installed accuracy of the overall airflow station is application-dependent on the resulting sen- sor density; typically better than 15% of reading. GreenTrol Automation, Inc. • 156 Holly View Lane Loris, SC 29569 • Toll Free: 877-4GN-TROL (877.446.8765) • Internet: GreenTrol.com...
Proceed to install the GF-A2100/GF-A2200 sensor probe(s) as outlined in the appropriate procedures that follow for Universal Mounting Brackets or for Insertion Mounting Brackets. GreenTrol Automation, Inc. • 156 Holly View Lane Loris, SC 29569 • Toll Free: 877-4GN-TROL (877.446.8765) • Internet: GreenTrol.com...
STANDARD UNIVERSAL BRACKET SHOWN. FACTORY DESIGNED BRACKET SOLUTIONS ARE AVAILABLE FOR ANY MOUNTING APPLICATION. Figure 3. Universal Mount Probe and Bracket Mechanical Detail GreenTrol Automation, Inc. • 156 Holly View Lane Loris, SC 29569 • Toll Free: 877-4GN-TROL (877.446.8765) • Internet: GreenTrol.com...
¼ X ‘X’ UNOBSTRUCTED PROBE MOUNTING WIDTH Figure 4. Universal Mount Probe Detail for Unit Ventilator and OA Damper Hood Applications GreenTrol Automation, Inc. • 156 Holly View Lane Loris, SC 29569 • Toll Free: 877-4GN-TROL (877.446.8765) • Internet: GreenTrol.com...
SCORE LINE AT NOTCH ON BLOCK. SECURE PROBE SET SCREW. Figure 6. GF-A2100 Single Probe Insertion Mount Detail for Economizer Hood and Duct Applications GreenTrol Automation, Inc. • 156 Holly View Lane Loris, SC 29569 • Toll Free: 877-4GN-TROL (877.446.8765) • Internet: GreenTrol.com...
(76.2 + {¼ X ‘D’} + {½ WALL INSULATION}) mm MEASURED FROM NON-CABLED END Figure 7. GF-A2200 Two Probe Insertion Mount Detail for Economizer Hood and Duct Applications GreenTrol Automation, Inc. • 156 Holly View Lane Loris, SC 29569 • Toll Free: 877-4GN-TROL (877.446.8765) • Internet: GreenTrol.com...
Connect OUT2 Analog/PID Output signal wire at terminal 3, and the signal ground at terminal 2 as shown in Figures 9 and 10 while observing the previous wiring precautions. GreenTrol Automation, Inc. • 156 Holly View Lane Loris, SC 29569 • Toll Free: 877-4GN-TROL (877.446.8765) • Internet: GreenTrol.com...
Refer to the Set up menu details and descriptions later in this manual for a complete description of analog output and PID control output options. GreenTrol Automation, Inc. • 156 Holly View Lane Loris, SC 29569 • Toll Free: 877-4GN-TROL (877.446.8765) • Internet: GreenTrol.com...
5. OUT1 AND OUT2 TYPE CAN EACH BE SELECTED AS EITHER AN ANALOG OUTPUT (TYPE=ALARM; FLOW; TEMP; DIFF FLOW) OR AS A PID CONTROL OUTPUT (TYPE=CTRL) - SEE SETUP MENU DETAIL. 6. DASHED LINES INDICATE ALTERNATE SHIELDED TWISTED PAIR WIRING CONNECTIONS FOR PID CONTROL DEVICES. Figure 10. GF-A2100/GF-A2200 Wiring Diagram Detail GreenTrol Automation, Inc. • 156 Holly View Lane Loris, SC 29569 • Toll Free: 877-4GN-TROL (877.446.8765) • Internet: GreenTrol.com...
However, if desired, the factory default full scale output range setting can be reconfigured in the field (see: CHANGING FACTORY DEFAULT SETTINGS). GreenTrol Automation, Inc. • 156 Holly View Lane Loris, SC 29569 • Toll Free: 877-4GN-TROL (877.446.8765) • Internet: GreenTrol.com...
10 seconds) each time power is applied. Verify that the readings at the host control system return an output that matches the output of the GF-A2100/GF-A2200. GreenTrol Automation, Inc. • 156 Holly View Lane Loris, SC 29569 • Toll Free: 877-4GN-TROL (877.446.8765) • Internet: GreenTrol.com...
(Use only with two-probe Model GF-2200-A). Area 2 menu only active when system is configured as dual. Figure 11. Transmitter Start Up Menu GreenTrol Automation, Inc. • 156 Holly View Lane Loris, SC 29569 • Toll Free: 877-4GN-TROL (877.446.8765) • Internet: GreenTrol.com...
LCD will display an asterisk (* * ) as the right most character, and depressing the “UP” or “DOWN” key will per- mit you to cycle and hold the display at each individual reading. GreenTrol Automation, Inc. • 156 Holly View Lane Loris, SC 29569 • Toll Free: 877-4GN-TROL (877.446.8765) • Internet: GreenTrol.com...
*P GAIN= Proportional gain term *I GAIN= Integral gain term *D GAIN= Derivative gain term *MAX INT= Maximum value for Integral state GreenTrol Automation, Inc. • 156 Holly View Lane Loris, SC 29569 • Toll Free: 877-4GN-TROL (877.446.8765) • Internet: GreenTrol.com...
VIEWING SENSOR DATA Data from the sensors can be displayed locally on the LCD from the Diagnostic sub-menu as detailed in Figure 15. GreenTrol Automation, Inc. • 156 Holly View Lane Loris, SC 29569 • Toll Free: 877-4GN-TROL (877.446.8765) • Internet: GreenTrol.com...
(+/-) indicates direction of ad ustment from initial value - TO PART 2 Figure 15. GF-A2100/GF-A2200 Setup Menu Option (“IP SYS”) GreenTrol Automation, Inc. • 156 Holly View Lane Loris, SC 29569 • Toll Free: 877-4GN-TROL (877.446.8765) • Internet: GreenTrol.com...
Page 24
Set the output to indicate the difference between flow 1 and flow 2. SYS CFG = DUAL TO PART Figure 15. (part 2 of 3) GF-A2100/GF-A2200 Setup Menu Option (“IP SYS”) GreenTrol Automation, Inc. • 156 Holly View Lane Loris, SC 29569 • Toll Free: 877-4GN-TROL (877.446.8765) • Internet: GreenTrol.com...
Page 25
TEMP = SENSOR TEMPERATURE SENSOR TEMP ↑ 1= TEMP 2= TEMP Figure 15. (part 3 of 3) GF-A2100/GF-A2200 Setup Menu Option (“IP SYS”) GreenTrol Automation, Inc. • 156 Holly View Lane Loris, SC 29569 • Toll Free: 877-4GN-TROL (877.446.8765) • Internet: GreenTrol.com...
GF-A2100/GF-A2200 if the difference between the transmitter and the field reference measurement is less than 10%. The following paragraphs detail use of the Field Calibration Wizard. GreenTrol Automation, Inc. • 156 Holly View Lane Loris, SC 29569 • Toll Free: 877-4GN-TROL (877.446.8765) • Internet: GreenTrol.com...
(Set to 0 – 15000 CFM using the samples taken. SETUP (See SETUP Menu) Figure 16. Field Calibration Wizard Menu (all System of Units) GreenTrol Automation, Inc. • 156 Holly View Lane Loris, SC 29569 • Toll Free: 877-4GN-TROL (877.446.8765) • Internet: GreenTrol.com...
Greentrol products are warranted for 12 months from shipment. Product will be repaired/replaced free of charge as described in the Terms and Conditions of Sale. GreenTrol Automation, Inc. • 156 Holly View Lane Loris, SC 29569 • Toll Free: 877-4GN-TROL (877.446.8765) • Internet: GreenTrol.com...