The output signal for these types of sensors is a frequency proportional to the rate of flow The BP2900 monitor uses the frequency information to calculate flow rate and total flow Through the use of the programming buttons, you can select rate units, total...
Scope of This Manual SCOPE OF THIS MANUAL This manual is intended to help you get the BP2900 flow monitor up and running quickly IMPORTANT Read this manual carefully before attempting any installation or operation. Keep the manual accessible for future reference.
Connecting the BP2900 Monitor to a Frequency Output Device The BP2900 monitor has two jumpers for setting the type of signal and the minimum amplitude of the signal that it accepts First, establish the type of output provided by the flow sensor The outputs almost always fall into one of two types •...
Page 8
For amplified input signals, set the input jumper to Pulse and the signal jumper to Low See Figure 4 on page 9 NOTEE: Amplified magnetic pickups require an external power source The BP2900 monitor does not supply power to an amplified pickup April 2021...
POWER CONNECTIONS Standard The power supply used in the BP2900 monitor is an internal lithium 3.6V DC D cell that powers the monitor for about six years when no outputs are used The monitor can also get power from a 4…20 mA current loop See...
Operating the Monitor OPERATING THE MONITOR Buttons BP2900 Figure 6: Keypad detail Switches to Program mode, press and hold for three seconds to enter MENU Extended Programming mode, and is used in reset process Scrolls forward through the parameter choices, increments numeric variables...
Programming Using Frequency Output Turbine Flow Meters Each Pembina Controls turbine flow meter is shipped with either a K-factor value or frequency data If frequency data is provided, the data must be converted to a K-factor...
OTEE: The meter size selection refers to the bore of the meter and not the connections size For a listing of the Pembina Controls turbine bore sizes, see the default K- factor table in “Default K-Factor Values” on page 38...
Page 25
Programming Grand Total The Flow-GT setting forces the meter to alternate between the instantaneous flow and the grand total with roll-over counts See Figure The grand total is the accumulation of all the fluid that has gone through the meter since the last time the grand total was cleared This totalizer is in addition to the current total totalizer on the display and is always enabled In addition, the grand total screen displays the number of times the grand total has reached...
Page 26
Programming Enter Meter’s K-Factor* OTEE: The K-factor supplied with your meter, or calculated from calibration data, is needed to complete this step At the KFactor prompt, press ENTER The most significant digit in the K-factor flashes If the current K-factor is correct, press ENTER to advance to the next parameter To change the K-factor, press UP to increment the digit until it matches the meter’s first K-factor digit Press RIGHT to advance to the next digit Repeat this process until all K-factor digits have been entered Press ENTER to save the K-factor and advance to the RateInt parameter...
Page 27
Programming Enter Specific Gravity Value* Mass readings in the BP2900 monitor are not temperature or pressure compensated so it is best to enter the specific gravity of the fluid as close to the system running temperature as possible As liquids are essentially incompressible, pressure compensation is not necessary...
Page 28
Programming Low Flow Cutoff The flow cutoff shows low flow rates (that can be present when pumps are off and valves are closed) as zero flow on the flow monitor A typical value would be about five percent of the flow sensor’s maximum flow Enter the low flow cutoff as an actual flow value For example, if the maximum flow rate for the flow sensor was 100 gpm, set the low flow cutoff value to 50 At the Cutoff prompt, press ENTER The first digit of the current low flow cutoff flashes If...
Page 29
The amplitude of the pulse is dependent on the voltage level of the supply connected to the pulse output and is limited to a maximum 28V DC The BP2900 monitor provides two types of totalizer pulses The basic open drain FET output,...
Page 30
Yes Press ENTER to advance to the 4mA Out parameter The DAC used in the BP2900 monitor is an twelve bit device The valid entries are 0…4095 F A S T M A X M I N AV G...
Page 31
Press ENTER to advance to the Freq#1 prompt NOTEE: If the number of linear points is set to 1 the BP2900 monitor assumes you are entering the maximum frequency and coefficient Further, the meter assumes that the implied first point is at a frequency of 0 Hz and a coefficient of 0 Frequency At the Freq#1 prompt, press ENTER The first digit of the first linear point’s frequency input...
Page 32
Press ENTER to save and advance to the Modbus parameter OTEE: The frequency values must be entered in ascending order If a lower frequency value is entered after a higher value, the BP2900 monitor flashes Limit followed by the minimum frequency value acceptable to the display Example:...
Page 33
If Modbus is being used, all devices connected to the bus must have the same baud rate setting Baud is expressed as ‘bits per second’ and defines the data transmission speed of the network The BP2900 monitor can be changed to use any of the following baud rates: 9600, 19200, 38400, 57600 and 115200 See “Modbus Interface”...
Page 34
Programming 2.2…10K Pull-up 100 mA RS485 B (–) Resistor Maximum RS485 A (+) RS485 Gnd Open Collector Setpoint 1 Control Output Setpoint 2 1 and 2 Freq. In – Pulse Internal 4-20mA – Iso Total Pluse – Total Reset High OC Total Pluse Signal Gnd Figure 15: Set point output (NEMA 4X)
Page 35
Programming Minimum Maximum Flow Flow Output ON Output OFF Hysteresis Figure 16: Set point actions OTEE: Neither the set point nor the hysteresis values are checked for compatibility with the meter size Check the values to prevent the outputs from working unexpectedly Trip SP 1 The trip parameter can be set for either High or Lo When set to High, the open collector...
Page 36
Programming Clear Grand Total At the Clr G-T prompt, press ENTER The monitor displays No on the screen To clear the grand total, press UP or RIGHT to change from No to Yes Press ENTER to save and advance to the Passwd parameter The totalizer can also be reset using a hardware reset, as shown in Figure 18 or by pressing...
Programming Operating Pressure At the Op Pres prompt, press ENTER The first digit of the current pressure setting flashes If the current selection is correct, press ENTER to advance to the next parameter To change the operating pressure, press UP to increment the digit until it matches the first digit of the correct pressure value Press RIGHT to move to the next digit When all the digits have been entered, press ENTER to save and advance to the Op Temp parameter Operating Temperature...
Troubleshooting Guide TROUBLESHOOTING GUIDE Trouble Remedy Check battery voltage Should be 36V DC If the input is 34V DC or lower, Battery replace the battery Check 4…20 mA input Voltage must be within the minimum and maximum No LCD supply voltage and capable of supplying enough current to run the display Display Loop The input voltage is checked across, or in parallel with, the 4…20 mA...
Battery Replacement BATTERY REPLACEMENT Battery powered monitors use a single 36V DC, D size lithium battery When replacement is necessary, use a clean, fresh battery for continued trouble-free operation Replacement Batteries Manufacturer Part Number B300028 Xeno S11-0205-10-03 Tadiran TL-5930/F Table 2: Replacement batteries 1 Unscrew the two captive screws on the front panel to gain access to the battery 2 Press the tab on the battery connector to release it from the circuit board 3 Remove the old battery and replace it with new one...
K-Factors Explained K-FACTORS EXPLAINED The K-factor (with regard to flow) is the number of pulses that must be accumulated to equal a particular volume of fluid You can think of each pulse as representing a small fraction of the totalizing unit An example is a K-factor of 1000 (pulses per gallon) This means that if you were counting pulses, when the count total reached 1000, you would have accumulated one gallon of liquid Using the same reasoning, each individual pulse represents an accumulation of...
Page 41
K-Factors Explained Example 2 Known values are: Full Scale Flow Rate 85 gpm Full Scale Output Frequency = 650 Hz 650 Hz × 60 sec = 39,000 pulses per min 39,000 pulses per min K-factor 458.82 pulses per gallon 85 gpm The calculation is a little more complex if the velocity is used because you first must convert the velocity into a volumetric flow rate to be able to compute a K-factor To convert a velocity into a volumetric flow, the velocity measurement and an accurate...
24 awg for connecting devices on a RS485 network The BP2900 monitor is rated as a 1/8 unit load device (input impedance equal to 96 kΩ) The RS485 specification states it is capable of supporting 32 standard unit loads (1 standard unit load equals 12 kΩ) In order to determine the maximum number of devices on a...
The BP2900 monitor sends each byte of a 16-bit register in big-endian format For example, the hex value ‘1234’ is sent as ‘12’ ‘34’ The BP2900 monitor provides for big- endian and little-endian word ordering when a master requests data To accomplish this,...
Page 45
40712…40713 – Table 6: Modbus register map for ‘big-endian’ word order master devices For reference: If the BP2900 Totalizer = 12345678 hex Register 40606 would contain 1234 hex (Word High) Register 40607 would contain 5678 hex (Word Low) Modbus Coil Description Modbus Coil...
Page 46
Modbus Interface Opcode 01 – Read Coil Status This opcode returns the state of the alarm coils The following Coils are defined: Coil # Description Alarm Set point 1 Alarm Set point 2 11 and up Spare Table 8: Read coil status CommandE: <addr><01><00><08><00><02><crc-16>...
Rate Time Seconds, minutes, hours, days Totalizer 000, 00, X1, x10, x100, x1000 Exponents Pulses/US Gallon, Pulse/cubic meter, pulses/liter, pulses/cubic K-factor Units foot PART NUMBER CONSTRUCTION Pembina Controls BP2900 Display Model BP29 Pembina Controls BP2900 Display Model Advanced Mounting Meter...
Mounting Options and Dimensions MOUNTING OPTIONS AND DIMENSIONS Meter Mount BP2900 G dia 925 in 700 in 575 in 400 in 345 in 150 in 0875 in (2350 mm) (1778 mm) (1460 mm) (1016 mm) (876 mm) (381 mm) (222 mm)
Mounting Options and Dimensions Swivel Mount BP2900 G dia 1225 in 700 in 575 in 400 in 345 in 150 in 0875 in (3112 mm) (1778 mm) (1460 mm) (1016 mm) (876 mm) (381 mm) (222 mm) April 2021 Page 51...
Page 52
Digital Flow Monitor, BP2900 The Pembina BP2900 is proprietary to Pembina Controls Inc. and a private labeled Blancett product. Blancett is a registered trademark of Badger Meter, Inc. Other trademarks appearing in this document are the property of their respective entities. Due to continuous research, product improvements and enhancements, Badger Meter reserves the right to change product or system specifications without notice, except to the extent an outstanding contractual obligation exists.