Page 1
FIRE PROTECTION HTE 400 Rectangular fi re damper UNI EN 1366-2 Certifi cation UNI EN 13501-3 Classifi cation ASSEMBLY INSTALLATION AND MAINTENANCE MANUAL The procedure listed into this manual should be carried out by qualifi ed personnel and we recommend to use relevant in-...
Page 2
HT400 Rectangular fi re damper - UNI EN 1366-2 Certifi ed - UNI EN 13501-3 Classifi ed HTE 400 Depending on the type of wall, the installation and sealing procedures described in this manual, and in accordance with the tested confi guration, must be respected at all time.
HT400 Rectangular fi re damper - UNI EN 1366-2 Certifi ed - UNI EN 13501-3 Classifi ed Summary Types and Confi gurations page HTE 400 + BELIMO - Confi guration B2 / B6 / C6 / C8 / F1 / F3 page HTE 400 + SCHISCHEK - Confi guration X1 / X3 / X5 page...
Page 4
HT400 Rectangular fi re damper - UNI EN 1366-2 Certifi ed - UNI EN 13501-3 Classifi ed Confi gurations and types HTE 400 + BELIMO - Confi guration B2 / B6 / C6 / C8 / F1 / F3 Wall limit W [±...
Page 5
HT400 Rectangular fi re damper - UNI EN 1366-2 Certifi ed - UNI EN 13501-3 Classifi ed HTE 400 + BELIMO - Confi guration B2 / B6 / C6 / C8 / F1 / F33 Electrical installation B2 - BF 24T B6 - BF 230T Servo motor 90°, AC / DC 24 V, 18/12 Nm, with BAE...
Page 6
HT400 Rectangular fi re damper - UNI EN 1366-2 Certifi ed - UNI EN 13501-3 Classifi ed HTE 400 + SCHISCHEK - Confi guration X1 / X3 / X5 Wall limit W [± 2 int.] 400 [± 5 ext.] MS = Minimum space for servicing servo motor equivalent to 200 mm BO = Blade overhang For dampers with height >...
Page 7
HT400 Rectangular fi re damper - UNI EN 1366-2 Certifi ed - UNI EN 13501-3 Classifi ed HTE 400 + MECHANICAL RELEASE WITH MANUAL RESET Confi guration M1 / M2 / M3 (M3 confi guration shown in the drawing) Wall limit W [±...
Page 8
HT400 Rectangular fi re damper - UNI EN 1366-2 Certifi ed - UNI EN 13501-3 Classifi ed HTE 400 + MAGNET - Confi guration E1 / E3 / E5 / E7 (confi guration shown in the drawing E1 / E3) Wall limit W [±...
Page 9
HT400 Rectangular fi re damper - UNI EN 1366-2 Certifi ed - UNI EN 13501-3 Classifi ed HTE 400 + MAGNET - Confi guration E1 / E3 / E5 / E7 Micro - Electromagnet SIGNAL MICROSWITCH FUSE LINK MICROSWITCH 41.5 16.5...
Page 10
HT400 Rectangular fi re damper - UNI EN 1366-2 Certifi ed - UNI EN 13501-3 Classifi ed HTE 400 + CO DRIVEN RELEASE- Confi guration G0 Wall limit W [± 2 int.] 400 [± 5 ext.] MS = Minimum space for servicing servo motor/mechanism 200 mm BO = Blade overhang For dampers with height >...
Page 11
HT400 Rectangular fi re damper - UNI EN 1366-2 Certifi ed - UNI EN 13501-3 Classifi ed HTE 400 + CO DRIVEN RELEASE- Confi guration G0 release - Signal microswitch RELEASE Mod. LNMTOTT33NICH Ø10 MATERIAL 1. Bushing Nickel-plated brass CW 614N 2.
Page 12
HT400 Rectangular fi re damper - UNI EN 1366-2 Certifi ed - UNI EN 13501-3 Classifi ed Damper weight / Actuator weight DAMPER WEIGHT TABLE H [mm] Weight [Kg] 14,8 16,3 19,2 22,1 25,0 27,9 30,9 33,8 36,7 39,6 42,5 45,4 48,4 51,3...
HT400 Rectangular fi re damper - UNI EN 1366-2 Certifi ed - UNI EN 13501-3 Classifi ed Individual damper installation General information • Only valid for dimensions from 150 x 150 2.2) 2.3) 2.4) Brick and concrete Hard horizontal Plasteboard walls to 1500 x 800 mm;...
HT400 Rectangular fi re damper - UNI EN 1366-2 Certifi ed - UNI EN 13501-3 Classifi ed Installation on autoclaved aerated concrete walls The HTE400 fi re damper can only protect against fi re and smoke if it is installed correctly in approved walls. IF THE WALL HAS LESS RESISTANCE THAN THE FIRE DAMPER, THE DAMPER RESISTANCE WILL BE REDUCED TO THAT OF THE BRICKWORK.
Page 15
HT400 Rectangular fi re damper - UNI EN 1366-2 Certifi ed - UNI EN 13501-3 Classifi ed Installation on autoclaved aerated concrete walls PHASE 3 Position the fi re damper in the centre of the opening. NB: With thicker walls comply with the wall limits indicated on the damper and install it as shown in the diagram. Wall Limit Information Limite di muratura...
Page 16
HT400 Rectangular fi re damper - UNI EN 1366-2 Certifi ed - UNI EN 13501-3 Classifi ed Installation on hard horizontal surfaces made of high-density reinforced concrete The HTE400 fi re damper can only protect against fi re and smoke if it is installed correctly in an approved horizontal support.
Page 17
HT400 Rectangular fi re damper - UNI EN 1366-2 Certifi ed - UNI EN 13501-3 Classifi ed Installation on hard horizontal surfaces made of high-density reinforced concrete PHASE 3 Use class M10 EN 998-2 mortar to fi ll in around the horizontal support and ensure there are no gaps.
HT400 Rectangular fi re damper - UNI EN 1366-2 Certifi ed - UNI EN 13501-3 Classifi ed Installation on vertical plasterboard bases The HTE400 fi re damper can only protect against fi re and smoke if it is installed correctly in an approved vertical plas- terboard support.
Page 19
HT400 Rectangular fi re damper - UNI EN 1366-2 Certifi ed - UNI EN 13501-3 Classifi ed Installation on vertical plasterboard bases PHASE 3 PHASE 4 PHASE 5 Proceed by fi lling the structure with Close the structure by fi tting the two Seal the opening in the structure.
HT400 Rectangular fi re damper - UNI EN 1366-2 Certifi ed - UNI EN 13501-3 Classifi ed Installation on vertical plasterboard bases PHASE 6 Once the fi re damper is housed in the opening with the closed blades positioned in the centre of the wall secure it using 4 brackets (to be ordered separately).
HT400 Rectangular fi re damper - UNI EN 1366-2 Certifi ed - UNI EN 13501-3 Classifi ed Installation on vertical plasterboard bases PHASE 7 Perimeter closure frame Finish off the perimeter of the damper using 2 plates per side measuring 135 mm in height. Leave a section “m”...
It is possible to install just two fi re dampers side by side, each measuring a maximum of 1000 x 800 mm. Connect the HTE 400 fi re dampers using the accessories purchased in the connection kit, as shown in the diagrams below.
Page 23
HT400 Rectangular fi re damper - UNI EN 1366-2 Certifi ed - UNI EN 13501-3 Classifi ed Installation of dampers side-by-side or in multi-sections SE_20200507_HTE400_M...
HT400 Rectangular fi re damper - UNI EN 1366-2 Certifi ed - UNI EN 13501-3 Classifi ed Side-by-side installation on autoclaved aerated concrete walls The HTE400 fi re damper can only protect against fi re and smoke if it is installed correctly in approved walls. IF THE WALL HAS LESS RESISTANCE THAN THE FIRE DAMPER, THE DAMPER RESISTANCE WILL BE REDUCED TO THAT OF THE BRICKWORK.
Page 25
HT400 Rectangular fi re damper - UNI EN 1366-2 Certifi ed - UNI EN 13501-3 Classifi ed Side-by-side installation on autoclaved aerated concrete walls PHASE 3 Position the fi re damper at the centre of the opening. NB: With thicker walls comply with the wall limits indicated on the damper and install it as shown in the diagram. Wall Limit Information Limite di muratura...
HT400 Rectangular fi re damper - UNI EN 1366-2 Certifi ed - UNI EN 13501-3 Classifi ed Side-by-side installation on vertical plasterboard bases The HTE400 fi re damper can only protect against fi re and smoke if it is installed correctly in an approved vertical plas- terboard support.
HT400 Rectangular fi re damper - UNI EN 1366-2 Certifi ed - UNI EN 13501-3 Classifi ed Side-by-side installation on vertical plasterboard bases PHASE 3 PHASE 4 PHASE 5 Proceed by fi lling the structure with Close the structure by fi tting the two Seal the opening in the structure.
Page 28
HT400 Rectangular fi re damper - UNI EN 1366-2 Certifi ed - UNI EN 13501-3 Classifi ed Side-by-side installation on vertical plasterboard bases PHASE 6 Once the fi re damper is housed in the opening with the closed blades positioned in the centre of the wall secure it using 4 brackets (to be ordered separately).
Page 29
HT400 Rectangular fi re damper - UNI EN 1366-2 Certifi ed - UNI EN 13501-3 Classifi ed Side-by-side installation on vertical plasterboard bases PHASE 7 Perimeter closure frame Finish off the perimeter of the damper using 2 plates per side measuring 135 mm in height. Leave a section “m”...
Page 30
HT400 Rectangular fi re damper - UNI EN 1366-2 Certifi ed - UNI EN 13501-3 Classifi ed Special case: installation in ducting with dimensions > 2000 x 800 mm If the size of the ducting is > 2000 x 800 mm the net space must be split into N separate sections in which a damper will be installed.
HT400 Rectangular fi re damper - UNI EN 1366-2 Certifi ed - UNI EN 13501-3 Classifi ed Procedures for replacing actuators accessories Mechanical release with manual reset/magnet Thermal fuse replacement 1. Check the condition of the If the seal is damaged the damper 2.
Page 32
HT400 Rectangular fi re damper - UNI EN 1366-2 Certifi ed - UNI EN 13501-3 Classifi ed Damper with BELIMO electric actuator mod. BFL / BFN / BAT thermal fuse 4.2.1 Procedure for replacing dampers with height < 250 mm 1.
Page 33
HT400 Rectangular fi re damper - UNI EN 1366-2 Certifi ed - UNI EN 13501-3 Classifi ed 4.2.2 Procedure for replacing dampers with height ≥ 250 mm 1. Check the condition of 2. Use two spanners to unscrew the four 3.
Page 34
HT400 Rectangular fi re damper - UNI EN 1366-2 Certifi ed - UNI EN 13501-3 Classifi ed Dampers with Belimo electric actuator mod. BF/BAE thermal fuse 4.3.1 Procedure for replacing dampers with height < 250 mm 1. Check the condition of 2.
Page 35
HT400 Rectangular fi re damper - UNI EN 1366-2 Certifi ed - UNI EN 13501-3 Classifi ed 4.3.2 Procedure for replacing dampers with height ≥ 250 mm 1. Check the condition of 2. Use a spanner to unscrew the actua- 3.
HT400 Rectangular fi re damper - UNI EN 1366-2 Certifi ed - UNI EN 13501-3 Classifi ed Dampers with Schischek electric actuator ExProTT - InProTT thermal fuse 4.4.1 Procedure for replacing dampers with height < 250 mm 1. Check the condition of 2.
Page 37
HT400 Rectangular fi re damper - UNI EN 1366-2 Certifi ed - UNI EN 13501-3 Classifi ed 4.4.2 Procedure for replacing dampers with height ≥ 250 mm 1. Check the condition of 2. Unscrew the actuator’s four M4 clamp- 3. Slip the actuator off the control pin, tak- the damper ing screws with a fl at screwdriver.
HT400 Rectangular fi re damper - UNI EN 1366-2 Certifi ed - UNI EN 13501-3 Classifi ed Dampers with mechanical release and manual reset 4.5.1 Procedure for replacing the opening signal microswitch To prevent accidents it is advisable to take care around the lever’s area of operation, as outlined in the diagram.
Page 39
HT400 Rectangular fi re damper - UNI EN 1366-2 Certifi ed - UNI EN 13501-3 Classifi ed 4.5.2 Procedure for replacing the closing signal microswitch To prevent accidents it is advisable to take care around the lever’s area of operation, as outlined in the diagram.
HT400 Rectangular fi re damper - UNI EN 1366-2 Certifi ed - UNI EN 13501-3 Classifi ed Dampers with normally non-energised magnets 4.6.1 Procedure for replacing the opening/closing signal microswitch To prevent accidents it is advisable to take care around the lever’s area of operation, as outlined in the diagram.
Page 41
HT400 Rectangular fi re damper - UNI EN 1366-2 Certifi ed - UNI EN 13501-3 Classifi ed 4.6.2 Procedure for replacing the microswitch powered by the magnet To prevent accidents it is advisable to take care around the lever’s area of operation, as outlined in the diagram.
Page 42
HT400 Rectangular fi re damper - UNI EN 1366-2 Certifi ed - UNI EN 13501-3 Classifi ed 4.6.3 Procedure for replacing the magnet To prevent accidents it is advisable to take care around the lever’s area of operation, as outlined in the diagram. 1.
HT400 Rectangular fi re damper - UNI EN 1366-2 Certifi ed - UNI EN 13501-3 Classifi ed Dampers with CO - Driven release 4.7.1 Procedure for replacing the opening signal microswitch To prevent accidents it is advisable to take care around the lever’s area of operation, as outlined in the diagram.
Page 44
HT400 Rectangular fi re damper - UNI EN 1366-2 Certifi ed - UNI EN 13501-3 Classifi ed 4.7.2 Procedure for replacing the closing signal microswitch To prevent accidents it is advisable to take care around the lever’s area of operation, as outlined in the diagram.
Page 45
HT400 Rectangular fi re damper - UNI EN 1366-2 Certifi ed - UNI EN 13501-3 Classifi ed 4.7.3 Procedure for replacing the piston To prevent accidents it is advisable to take care around the lever’s area of operation, as outlined in the diagram. 1.
Page 46
HT400 Rectangular fi re damper - UNI EN 1366-2 Certifi ed - UNI EN 13501-3 Classifi ed SE_20200507_HTE 400_M...
Page 47
HT400 Rectangular fi re damper - UNI EN 1366-2 Certifi ed - UNI EN 13501-3 Classifi ed SE_20200507_HTE400_M...
Page 48
SagiCofi m S.p.A. via Firenze 1 20063 Cernusco sul Naviglio Milan Italy tel +39 02 92 90 21 fax +39 02 92 90 23 00 info@sagicofi m.com www.sagicofi m.com SagiCofi m S.p.A. reserves the right to make amendments or changes to the contents of this document at any time without any obligation to provide notice thereof.
Need help?
Do you have a question about the HTE 400 and is the answer not in the manual?
Questions and answers