Terofire Products Introduction The information provided in this manual covers the Saffire range of fire alarm control panels. The Saffire range is designed to meet the requirements of BS5839 Parts 1 & 4 1988 and includes panels of 1 and 2 zones.
Page 3
Saffire Instruction Manual If a fault is indicated, refer to the fault finding section before proceeding. Disconnect the batteries and switch off the mains supply. Remove the 3k3 end of line resistor from sense zone 1. Terminate sense zone 1 circuit wiring in the panel observing correct polarity and fit the end of line resistor at the extreme end of the circuit.
Terofire Products Panel Operation Entering the access code. Before being able to access the Reset, Silence and Evacuate functions, the panel access code must first be entered. To activate the keypad, press the front panel buttons in the following sequence: 1-3-1-2 The panel should bleep after each button press.
Saffire Instruction Manual Fault Finding Reset, Silence & Evacuate buttons not working. Enter access code to enable keypad. Press the buttons in the following sequence: 1-3-1-2. The panel should bleep after each button press. Fault lamp & zone fault lamp flashing, internal buzzer sounding. Faults monitored are: •...
Terofire Products Panel Specification i n i ± Please ensure all calculations take into account the startup current of the devices used. This is especially important if you intend using xenon beacons.
Page 8
Terofire Products Sense Zone Wiring Diagrams Find the detector bases you will be using in the table on page 7 and check to see which end of line device is required - either a 3k3 resistor or an active end of line unit. The 3k3 resistor should be used if a zone is comprised entirely of call points.
Page 9
Saffire Instruction Manual Alarm Zone Wiring Diagrams The alarm zones are wired as in the diagram below. A 10k end of line resistor must be fitted at the end of the circuit. Motorised fire bells may be used, but solenoid bells MUST NOT be connected to the panel. Some electronic sounders have a choice of tones available.
Page 10
Terofire Products Additional Wiring Information Signalling fire to another panel. By connecting two panels as shown below, when panel B closes its auxiliary contacts, panel A will go into fire. 510R Resistor Sense Zone + 3k3 or C-NO Contacts Panel A...
Page 11
Saffire Instruction Manual Saffire System Log Book All events should be properly recorded in this log book. An ‘event’ should include fire alarms (whether real or false), faults, tests, temporary disconnections and the dates of installing or servicing engineer’s visits with a brief note of work carried out and outstanding. Name and address ................