Hein Lanz HL320 Operating Instructions Manual

Hein Lanz HL320 Operating Instructions Manual

Process indicators for standard analog signals with 2 presets / relays and 2 control inputs

Advertisement

Quick Links

Operating Instructions
Process indicators for standard analog signals with 2 presets / relays and 2 control inputs
Product features:
Two identical models, but with a different power supply range
Analog input 0 ... +/-10 V (or 2 – 10 V) and 0 – 20 mA (or 4 – 20 mA)
Two relay outputs for limit monitoring (dry changeover contacts)
Two digital multi-function inputs with programmable control function
Useful supplementary functions like Digital Filter, Linearization, Totalizer etc.
6 digit 14-segment display (14 mm / 0.55'' size) for readout and menu dialogues
Available devices:
Hein Lanz GmbH
Elsaesserstrasse 15L, D-79110
Freiburg im Breisgau, Germany
: Power supply 10 – 30 VDC
: Power supply 90 – 240 VAC and auxiliary output 24 VDC
Tel.: +49 (0) 761 3841 3864
Fax.: +49 (0) 761 3841 3865
320 /
322
1
E-mail.: info@heinlanz.com
http://www.heinlanz.com

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the HL320 and is the answer not in the manual?

Questions and answers

Summary of Contents for Hein Lanz HL320

  • Page 1 6 digit 14-segment display (14 mm / 0.55’’ size) for readout and menu dialogues Available devices: : Power supply 10 – 30 VDC : Power supply 90 – 240 VAC and auxiliary output 24 VDC Hein Lanz GmbH Elsaesserstrasse 15L, D-79110 Tel.: +49 (0) 761 3841 3864 E-mail.: info@heinlanz.com Freiburg im Breisgau, Germany Fax.: +49 (0) 761 3841 3865...
  • Page 2: Table Of Contents

    Limit Value (Alarm) Monitoring ....................20 Monitoring of the Measuring Circuit ................... Technical Specifications .................... Dimensional Drawings ....................10. Help Texts ........................Hein Lanz GmbH Elsaesserstrasse 15L, D-79110 Tel.: +49 (0) 761 3841 3864 E-mail.: info@heinlanz.com Freiburg im Breisgau, Germany Fax.: +49 (0) 761 3841 3865...
  • Page 3: Safety Instructions And Responsibility

    Please note that device may only be installed in proper form and used in a technically perfect condition in accordance to the “Technical Specifications”. The device is not suitable for operation in explosion-proof areas or areas which are excluded by the EN 61010-1 standard. Hein Lanz GmbH Elsaesserstrasse 15L, D-79110 Tel.: +49 (0) 761 3841 3864 E-mail.: info@heinlanz.com...
  • Page 4: Installation

    (if necessary). Unauthorized opening and repairing can have negative effects or failures to the protection-measures of the unit. Hein Lanz GmbH Elsaesserstrasse 15L, D-79110 Tel.: +49 (0) 761 3841 3864 E-mail.: info@heinlanz.com...
  • Page 5: Short Form Description

    • Programmable via the front keys • Multifunction key and two multifunction inputs, function programmable • Hein Lanz GmbH Elsaesserstrasse 15L, D-79110 Tel.: +49 (0) 761 3841 3864 E-mail.: info@heinlanz.com Freiburg im Breisgau, Germany Fax.: +49 (0) 761 3841 3865...
  • Page 6: Display And Operating Elements

    To display Device Type and Software Version: [ [ > 5 sec ] To restore factory default settings: [ [ > 3 sec ] Hein Lanz GmbH Elsaesserstrasse 15L, D-79110 Tel.: +49 (0) 761 3841 3864 E-mail.: info@heinlanz.com Freiburg im Breisgau, Germany Fax.: +49 (0) 761 3841 3865...
  • Page 7: Block Diagram And Terminal Assignments

    4 4 . Block Diagram and Terminal Assignments Hein Lanz GmbH Elsaesserstrasse 15L, D-79110 Tel.: +49 (0) 761 3841 3864 E-mail.: info@heinlanz.com Freiburg im Breisgau, Germany Fax.: +49 (0) 761 3841 3865 http://www.heinlanz.com...
  • Page 8: Operating Concept (Mode Of Operation)

    5 5 . Operating Concept (Mode of Operation) see 7.4 Hein Lanz GmbH Elsaesserstrasse 15L, D-79110 Tel.: +49 (0) 761 3841 3864 E-mail.: info@heinlanz.com Freiburg im Breisgau, Germany Fax.: +49 (0) 761 3841 3865 http://www.heinlanz.com...
  • Page 9: Programming

    When quitting the programming menu via SAVE, the minimum and maximum values and the totalizer value are all cleared 6.1 How to Enter the Menu / Select a Function Group / Quit the Menu: Hein Lanz GmbH Elsaesserstrasse 15L, D-79110 Tel.: +49 (0) 761 3841 3864 E-mail.: info@heinlanz.com...
  • Page 10: How To Select Functions / Set Parameters / Accept Settings

    6 6 .2 How to Select Functions / Set Parameters / Accept Settings nction Groups Func tion Parameter Hein Lanz GmbH Elsaesserstrasse 15L, D-79110 Tel.: +49 (0) 761 3841 3864 E-mail.: info@heinlanz.com Freiburg im Breisgau, Germany Fax.: +49 (0) 761 3841 3865...
  • Page 11: Function Groups

    Setting range depends on measuring range [V / mA] Select low display value for I NP.LO. Setting range -199999 … +999999 and decimal point Hein Lanz GmbH Elsaesserstrasse 15L, D-79110 Tel.: +49 (0) 761 3841 3864 E-mail.: info@heinlanz.com Freiburg im Breisgau, Germany Fax.: +49 (0) 761 3841 3865...
  • Page 12: User Linearization

    Select input low value Setting range depends on measuring range [V / mA] Select display low value for INP.LO. Setting range -199999 … +999999 and decimal point. Hein Lanz GmbH Elsaesserstrasse 15L, D-79110 Tel.: +49 (0) 761 3841 3864 E-mail.: info@heinlanz.com Freiburg im Breisgau, Germany Fax.: +49 (0) 761 3841 3865...
  • Page 13 3.000 … 21.000 [mA] The functions LO.LIM and HI.LIM limit the editable range. The value for HI.LIM must always be greater than the value for LO.LIM Hein Lanz GmbH Elsaesserstrasse 15L, D-79110 Tel.: +49 (0) 761 3841 3864 E-mail.: info@heinlanz.com Freiburg im Breisgau, Germany Fax.: +49 (0) 761 3841 3865...
  • Page 14 Example 1: 0 - 10 V = 0 … 600, E E xample 2: 4 - 20 mA = 300 - 900, E E xample3: 1.0 - 9.0 V = 750 - 400 7.3.2 Example for non-linear scaling Hein Lanz GmbH Elsaesserstrasse 15L, D-79110 Tel.: +49 (0) 761 3841 3864...
  • Page 15: Multifunction Key (Mp-Key) And Multifunction Inputs (Mp-Inp)

    Lock-out Keypad In the function group MP.INP, programme the function MP.INP1 or MP.INP2 to LOC.KEY. In the operating mode, activate multifunction input 1 or multifunction input 2 Hein Lanz GmbH Elsaesserstrasse 15L, D-79110 Tel.: +49 (0) 761 3841 3864 E-mail.: info@heinlanz.com Freiburg im Breisgau, Germany Fax.: +49 (0) 761 3841 3865...
  • Page 16 ON (this setting is possible only if all other settings are set to OFF) Select function: Reset Totalizer by MP key (when the totalizer value is in display) Hein Lanz GmbH Elsaesserstrasse 15L, D-79110 Tel.: +49 (0) 761 3841 3864 E-mail.: info@heinlanz.com...
  • Page 17 Lock-out programming and default setting Lock-out limit value setting, programming, default setting and MP-Key Tare Reset tare value Reset totalizer Hein Lanz GmbH Elsaesserstrasse 15L, D-79110 Tel.: +49 (0) 761 3841 3864 E-mail.: info@heinlanz.com Freiburg im Breisgau, Germany Fax.: +49 (0) 761 3841 3865...
  • Page 18: Totalizer Function

    The throughput rate is added into the totalizer memory every second. A dummy decimal point (optical indication only) can be programmed into the totalizer as required. Hein Lanz GmbH Elsaesserstrasse 15L, D-79110 Tel.: +49 (0) 761 3841 3864 E-mail.: info@heinlanz.com...
  • Page 19 Hein Lanz GmbH Elsaesserstrasse 15L, D-79110 Tel.: +49 (0) 761 3841 3864 E-mail.: info@heinlanz.com Freiburg im Breisgau, Germany Fax.: +49 (0) 761 3841 3865 http://www.heinlanz.com...
  • Page 20: Limit Value (Alarm) Monitoring

    Input range 0.0 ... 99.9 [sec] Menu Alarm Output 2 Select operating mode Automatic operation Memory latch operation Hein Lanz GmbH Elsaesserstrasse 15L, D-79110 Tel.: +49 (0) 761 3841 3864 E-mail.: info@heinlanz.com Freiburg im Breisgau, Germany Fax.: +49 (0) 761 3841 3865...
  • Page 21 Power OFF condition. At the next Power ON the limit values are not processed until after the expiration of the start delay (PW.DELY) Hein Lanz GmbH Elsaesserstrasse 15L, D-79110 Tel.: +49 (0) 761 3841 3864 E-mail.: info@heinlanz.com Freiburg im Breisgau, Germany Fax.: +49 (0) 761 3841 3865...
  • Page 22 7 7 .6.2 C ontrol with incrementing measuring signal 7 7 .6.3 C C ontrol with d d ec c rementing measuring signal Hein Lanz GmbH Elsaesserstrasse 15L, D-79110 Tel.: +49 (0) 761 3841 3864 E-mail.: info@heinlanz.com Freiburg im Breisgau, Germany Fax.: +49 (0) 761 3841 3865...
  • Page 23 Hein Lanz GmbH Elsaesserstrasse 15L, D-79110 Tel.: +49 (0) 761 3841 3864 E-mail.: info@heinlanz.com Freiburg im Breisgau, Germany Fax.: +49 (0) 761 3841 3865 http://www.heinlanz.com...
  • Page 24: Monitoring Of The Measuring Circuit

    ■ ■ (< 2 mA) Indication blinking blinking blinking blinking blinking (■ = is detected) Hein Lanz GmbH Elsaesserstrasse 15L, D-79110 Tel.: +49 (0) 761 3841 3864 E-mail.: info@heinlanz.com Freiburg im Breisgau, Germany Fax.: +49 (0) 761 3841 3865 http://www.heinlanz.com...
  • Page 25: Technical Specifications

    No. of switching cycles at 5 A / 250 V AC 5x10 No. of switching cycles at 5 A / 30 V DC 5x10 Hein Lanz GmbH Elsaesserstrasse 15L, D-79110 Tel.: +49 (0) 761 3841 3864 E-mail.: info@heinlanz.com Freiburg im Breisgau, Germany Fax.: +49 (0) 761 3841 3865...
  • Page 26 Core cross section max. 2,5 mm² / AWG 14 Signal and control inputs: Plug-in screw terminal 9-pos.RM 3,50, Core cross section max. 1,5 mm² / AWG 16 Hein Lanz GmbH Elsaesserstrasse 15L, D-79110 Tel.: +49 (0) 761 3841 3864 E-mail.: info@heinlanz.com Freiburg im Breisgau, Germany Fax.: +49 (0) 761 3841 3865...
  • Page 27: Dimensional Drawings

    + + 0,6 m m m (3.62 + + 0.03 ’ ’ ’ x 1.77 +0.23 ’’) Hein Lanz GmbH Elsaesserstrasse 15L, D-79110 Tel.: +49 (0) 761 3841 3864 E-mail.: info@heinlanz.com Freiburg im Breisgau, Germany Fax.: +49 (0) 761 3841 3865...
  • Page 28 RES.MAX. FUNCTION RESET MAX VALUE ON RES.REL. FUNCTION RESET OUTPUT-LATCH OFF RES.REL. FUNCTION RESET OUTPUT-LATCH ON Hein Lanz GmbH Elsaesserstrasse 15L, D-79110 Tel.: +49 (0) 761 3841 3864 E-mail.: info@heinlanz.com Freiburg im Breisgau, Germany Fax.: +49 (0) 761 3841 3865...
  • Page 29 OFF DELAY ALARM x [SEC] END.PRG. REPEAT PROGRAMMING END.PRG. EXIT PROGRAMMING AND STORE DATA -1.9.9.9.9.9 DISPLAYRANGE UNDERFLOW Hein Lanz GmbH Elsaesserstrasse 15L, D-79110 Tel.: +49 (0) 761 3841 3864 E-mail.: info@heinlanz.com Freiburg im Breisgau, Germany Fax.: +49 (0) 761 3841 3865 http://www.heinlanz.com...
  • Page 30 OVERFLOW UPPER INPUT RANGE LIMIT UNDERF. UNDERFLOW LOWER INPUT RANGE LIMIT S S ENSOR SENSOR ERROR Hein Lanz GmbH Elsaesserstrasse 15L, D-79110 Tel.: +49 (0) 761 3841 3864 E-mail.: info@heinlanz.com Freiburg im Breisgau, Germany Fax.: +49 (0) 761 3841 3865...