OPERATING AND CONFIGURING INSTRUCTIONS
DESCRIPTION FOR EACH FEATURE
Activation & disabling the module
Before being delivered to the customer, the module is disabled.
The ''OFF'' message is displayed on the screen. When the
module is disabled, only the alarms and temperature displays
are deactivated. It is always possible to control the lighting
manually or automatically, with the door (See ''lighting
Control''). Note that all the initial parameters and those
modified by the customer are stored in memory when the
module is disabled.
Refer to ''keypad Operation'' section on how to enable and
disable the module.
Temperature monitoring and display
The unit displays the temperature in degrees Celsius. Should
one or more alarms be present, the display will show the
temperature and the alarm message(s) alternatively.
Lighting control
The lighting is controlled two different ways;
1.
By pressing the button on the keypad, which will switch
alternatively ON and OFF.
2.
By detecting the opening of the door, which will turn the
lights ON and the closing door will initiate a 5-minute
countdown. The light will then go OFF after this delay.
OPTION
1. Panic Alarm Buzzer
2. Battery (9 Volt) Holder
3. Display
4. High Temp alarm Button
5. Light Switch Button
6. Set Button
7. Low Temp Alarm Button
8. Up Button (and Mute)
9. Down Button
10. Mute Button (only mute the loud Buzzer)
Temperature Alarms
These alarms are activated 45 minutes (adjustable, see
«parameter descriptions» after reaching the
temperature alarm settings. An audible alarm (about 55
dB) from the keypad will then occur. The display will
show the message HA (High Temp Alarm) Or LA *Low
Temp Alarm), alternatively with the actual temperature.
The 115 Volt alarm signal will turn ON.
The High and Low temperature alarm setting and the
activation delay can be modified in the parameters menu.
Door Open Alarm
If the door remains open for more than 15 minutes
(adjustable, see
« parameter descriptions»), this alarm is
triggered and an audible alarm from the keypad will
occur. The display will show the message dA (Door Open
Alarm), alternatively with the actual temperature. The
115 Volt alarm signal will turn ON.
1

Advertisement

loading

Summary of Contents for Norbec Intelligence I3

  • Page 1 OPERATING AND CONFIGURING INSTRUCTIONS 1. Panic Alarm Buzzer 2. Battery (9 Volt) Holder OPTION 3. Display 4. High Temp alarm Button 5. Light Switch Button 6. Set Button 7. Low Temp Alarm Button 8. Up Button (and Mute) 9. Down Button 10.
  • Page 2 DESCRIPTION FOR EACH FEATURE (Cont'd.) (SUITE) Battery back-up Panic Alarm The 9 Volt battery holder is located just above the controller. In This alarm is triggered by an interior backlit button, besides the normal condition, an alkaline battery should maintain the door opening.
  • Page 3 KEYPAD OPERATION Press 1 second to activate the module. Press 5 seconds to disable the mode. The message OFF is displayed on the screen when the module is disabled. Switch ON and OFF the light fixture. Press to see the HIGH Temp ALARM setting (ALU parameter). Press for 3 seconds to enter a new value for the HIGH Temp ALARM (ALU displayed), then press the Up-Down Buttons for proper setting and then press the Set button to confirm and exit.
  • Page 4 The factory settings are as follows: PARAMETER DESCRIPTION PRESET VALUE (By default) RANGE High temperature alarm setting C : 6°C F : -12°C « ALL » value to 150°C Low temperature alarm setting C : 0°C F : -25°C -50°C to « ALU » value Temperature alarm delay 0 —...