300 mA current leakage protection (type B or B+). Before connecting unit to the electrical power supply, it is necessary to check whether earthing has been installed properly. UAB KOMFOVENT we reserve the right to make changes without prior notice C5.1_22-08...
1.3 a Picture. Controller with connection terminals Total power of all external elements with 24 V supply may not exceed 15 W. External control Indication 1.3 b Picture. External control elements connection UAB KOMFOVENT we reserve the right to make changes without prior notice C5.1_22-08...
Control panel connection and other cable thicknesses are specified in the wiring diagram! Remove protective screen tape, before mounting front cover on the control panel! Yellow (A) ( ) White Green (B) (+) Red UAB KOMFOVENT we reserve the right to make changes without prior notice C5.1_22-08...
Extract air volume Energy recovery operation mode Supply air humidity Air heater operation „Override“ mode Extract air humidity Air cooler operation Alarm signal Extract (room) air quality Sold separately. UAB KOMFOVENT we reserve the right to make changes without prior notice C5.1_22-08...
When starting CF type AHU for the first time, it will be needed to perform heat exchanger calibra- tion, which is used for frost prevention function (See 2.5.1.3). Start CF exchanger calibration? Temperature Temperature STARTING UAB KOMFOVENT we reserve the right to make changes without prior notice C5.1_22-08...
All temperature sensor readings, functioning of CF exchanger calibration separate air handling unit elements and other de- 1 / 3 Calibrated tailed information is available in this menu. Only in CF units. UAB KOMFOVENT we reserve the right to make changes without prior notice C5.1_22-08...
“Air quality func- tion”. A room sensor with the analogue output (0...10 V DC) should be designed for this function. Factory setting. UAB KOMFOVENT we reserve the right to make changes without prior notice C5.1_22-08...
Reset settings In ventilation intensity control, this function has top priority over “Outdoor compensated ventilation” and “VAV” functions. UAB KOMFOVENT we reserve the right to make changes without prior notice C5.1_22-08...
Humidification and dehumidification of air. For humidification of air the control signal of 0...10 V is used through the output TG3 of the controller, and the dehumidification of air is performed using the coolers and heaters available in the unit. UAB KOMFOVENT we reserve the right to make changes without prior notice C5.1_22-08...
Add new holiday Delete holiday 2.5.4. Settings This menu is for air handling unit and the user parameter setting. Menu Settings Overview Scheduling Air handling unit Functions Settings Personalization UAB KOMFOVENT we reserve the right to make changes without prior notice C5.1_22-08...
/h, and the B6 input value – 7 V, the unit will supply constant air volume of 560 m /h, i. e., 70 % of the set value. The same applies to the exhaust air only by B7 input. UAB KOMFOVENT we reserve the right to make changes without prior notice C5.1_22-08...
Page 15
Panel sensor calibration Panel sensor calibration Panel sensor calibration Temperature correct... Humidity correction Temperature correction 0,0 °C 5,0 °C 10,0%RH Humidity correction 0,0%RH 0,0°C -5,0 °C -10,0%RH UAB KOMFOVENT we reserve the right to make changes without prior notice C5.1_22-08...
If the user has forgotten the modified password, it can be set to the default. To do this, user should to restore the factory settings of the air handling unit. UAB KOMFOVENT we reserve the right to make changes without prior notice C5.1_22-08...
“Heating” (Pic. 1.3 b.). The option of reversal of direct evaporation cooling units must be provided in ad- vance. Factory setting. UAB KOMFOVENT we reserve the right to make changes without prior notice C5.1_22-08...
Extract air tempera- The discharged air temperature Check connections of the sensor or 3A, 4A ture sensor failure sensor is not connected or broken. replace the sensor. UAB KOMFOVENT we reserve the right to make changes without prior notice C5.1_22-08...
Page 19
The evaporator is iced over due to excessively high humidity content Check the operation of the evapo- Evaporator icing in the exhaust air and low outdoor rator defrost system. temperatures. UAB KOMFOVENT we reserve the right to make changes without prior notice C5.1_22-08...
Page 20
The rotor drive is overloaded. drive and its cooling. Check the rotor motor and replace 111A Rotor motor failure The rotor motor is broken. it if necessary. UAB KOMFOVENT we reserve the right to make changes without prior notice C5.1_22-08...
Page 21
However if the failure has not been eliminated, unit either starts operating and after some time it stops again, or it does not operate and failure message is indicated. UAB KOMFOVENT we reserve the right to make changes without prior notice C5.1_22-08...
Page 24
UAB KOMFOVENT PARTNERS SERVICE AND SUPPORT J. PICHLER Gesellschaft m. b. H. www.pichlerluft.at Phone: +370 5 200 8000 service@komfovent.com Ventilair group www.ventilairgroup.com ACB Airconditioning www.acbairco.be Komfovent AB REKUVENT s.r.o. www.rekuvent.cz Ögärdesvägen 12B 433 30 Partille, Sverige WESCO AG www.wesco.ch Phone: +46 31 487 752 SUDCLIMATAIR SA www.sudclimatair.ch...