3. Go one step back in the menu and select Return to.
4. Choose one of the following options:
• Auto
• Off.
5. Go one step back in the menu and select Forced start time.
6. Set the time period in which the pump must run in manual
operating mode.
Related information
6.16.2.1 Starting and stopping the pump manually with Grundfos
GO Remote
6.16.2.2 Starting and stopping the pump manually with the
operating panel

6.17 Motor protection

Make sure that all settings are entered according to the
pump and system requirements to avoid malfunction.
Related information
6.14 Setting the maximum number of restarts with Grundfos GO
Remote
8.13 Code 69 (Winding temperature too high)
6.17.1 Overheat protection
The control unit offers thermal protection for the connected motors.
Two types of thermal-protection sensor can be connected to the
control unit: a PTC sensor (analog) and a thermal switch (digital).
Under normal running conditions, the sensor will act as a short
circuit, but when its temperature limit is reached, it will open and tell
the control unit that the temperature is too high, and the pump is
stopped. When the temperature has dropped to the sensor-trigger
level, the pump will return to normal running conditions. It will not be
possible to start the pump manually as long as the temperature is
too high.
Related information
6.14 Setting the maximum number of restarts with Grundfos GO
Remote
6.17.2 Overload protection
The pump is protected by a motor-protection relay. The nominal
current draw must be set manually on the motor-protection relay.
See the specific documentation for the relay on how to set the
trigger level. If the current exceeds the trigger level, the relay will
switch off the pump and the controller will give an alarm. The alarm
has to be manually reset directly on the motor protection relay.
Related information
6.14 Setting the maximum number of restarts with Grundfos GO
Remote
6.17.3 Moisture protection
When a moisture sensor is installed in series with the temperature
sensor, the control unit needs to know how to determine whether
there is a high temperature or moisture in the pump. If the
temperature is too high, normally the temperature sensor will go
back to its normal stage when the temperature has dropped to its
trigger level. If there is moisture in the pump, then the moisture
sensor will keep the series connection open until the pump is
opened and serviced.
To determine which sensor has been active, a cool down
time must be entered. This is the time that will normally pass until
the temperature has dropped enough for the temperature sensor to
return to its normal stage. If the cool down time is exceeded, the
control unit will assume that there is moisture in the pump, and it
will send a moisture alarm.

6.18 Alarm reset

6.18.1 Resetting alarms and warnings manually with Grundfos
GO Remote
1. Go to Alarms and warnings.
2. Press Reset alarm.
18
All current alarms and warnings have been reset. However, if
the fault causing the alarm or warning has not been removed,
the alarm or warning will appear again.
3. If you want to delete all alarms and warnings from the history
log, press Show log > Reset alarm and warning logs.
6.18.2 Setting the automatic alarm reset with Grundfos GO
Remote
1. Go to Settings > Automatic alarm reset.
2. Select one of the following:
No automatic reset
All except pump critical
All alarms
6.18.3 Resetting alarms and warnings on the operating panel
You can manually reset alarms and warnings on the operating
panel. However, if the fault causing the alarm or warning has not
been removed, the alarm or warning will appear again.
1. Press Reset on the operating panel to reset the alarm or
warning.

6.19 Setting the buzzer with Grundfos GO Remote

The internal buzzer is used to give an acoustic sound if there is a
warning or an alarm.
1. Go to Settings > Buzzer settings.
2. Select when the buzzer is to be activated:
• All alarms
• All alarms and warnings.

6.20 Setting units for Grundfos GO Remote

Changing units as described here will only change the units shown
in Grundfos GO Remote. It will not affect the units shown on the
operating panel of products connected to Grundfos GO Remote.
The control unit does not reset
any alarm or warning. You
must do it manually.
The control unit resets alarms
and warnings unless the rela-
ted fault can damage the
pump.
The control unit resets alarms
and warnings, regardless of
the fault.