Ddc Control Specifications - Dometic DDC Operation Manual

Digital diagnostic control
Table of Contents

Advertisement

DDC Control • Specifications
Cooling Set Point Range ....................................................................40°F to 58°F (4.4°C to 14.4°C)
Heating Set Point Range ................................................................95°F to 120°F (35.0°C to 48.9°C)
Ambient Temperature Operating Range Displayed ...........................0°F to 150 F (-17.8°C to 65.6°C)
Sensor Accuracy ..............................................................................± 2°F at 77°F (±1.1°C at 25.0°C)
Low Voltage Limit 115 volt units .............................................................................................. 85 VAC
Low Voltage Limit 220 volt units ............................................................................................ 170 VAC
Line Voltage ................................................................................................................115 or 230 VAC
Frequency ........................................................................................................................ 50 or 60 Hz
Valve Output .......................................................................................................1/2 Amp @ 115 VAC
Valve Output ...................................................................................................... 1/4 Amp @ 230 VAC
Pump Output ........................................................................................................ 1/4 HP @ 115 VAC
Pump Output ........................................................................................................1/2 HP @ 230 VAC
Compressor Output ................................................................................................. 1 HP @ 115 VAC
Compressor Output .................................................................................................2 HP @ 230 VAC
Minimum Ambient Operating Temperature ....................................................................0°F (-17.8°C)
Maximum Ambient Operating Temperature ................................................................ 180°F (82.2°C)
Maximum Rh Conditions ................................................................................. 99% Non Condensing
Power Consumption ..............................................................................................Less Than 5 Watts
Dimensions
PCB .................................................................. 5.25" X 5.875" X 2.0"(133mm X 149mm X 51 mm)
Cable Lengths
Water Sensor ......................................................................................................2' (0.61m) Standard
System Inputs
Return Water Sensor ........................................................................................................................ 1
Optional High Freon Pressure........................................................................................................... 1
Optional Low Freon Pressure ........................................................................................................... 1
Supply Water (Freeze) Sensor .......................................................................................................... 1
High Limit Sensor ............................................................................................................................. 1