Relay Control; Relay Contact Ratings; Relay Settings; Manual Override - Geist GBB100 Series Instruction Manual

Environmental monitoring unit with output relay
Table of Contents

Advertisement

Relay Control

Relay Contact Ratings

The output relay contacts are intended to carry low voltage signals only. Do not exceed the
following ratings on the output relay contacts:
DC: 60 V, 30 W
AC: 30 Vrms, 1 A

Relay Settings

The GBB100 Series units provide one output relay that can be operated remotely or set to
automatically open or close based on alarm conditions.
automatically energize and de-energize as its associated alarms trip and clear.
latching mode will similarly energize on an alarm trip, but will only de-energize when
acknowledged
by
associating an alarm condition with one of the output relays.

Manual Override

The output relay can be operated remotely through the Manual Override section of the Control
page. The user can force the relay to energize or de-energize by selecting the desired action in
a drop down menu and clicking the execute button. The current relay status is displayed in the
Manual Override section of the Control page. The word "forced" is displayed next to any relay
that has been manually forced to a given state. Any forced relay will not change state based on
alarm status. Relays can be released from a forced energized or forced de-energized state by
selecting the Release Override option in the drop down menu.

Acknowledgments

Any relay in latching mode will change from de-energized to energized if it receives an alarm
trip; however, the relay will not change from energized to de-energized when the alarm status
returns to normal until the user acknowledges the pending change.
latching mode will change from de-energized to energized if it receives a manual override Force
Energized command; however, the relay will not change from energized to de-energized when
the Release Override command is issued until the user acknowledges the pending change. The
user must check the Acknowledge and De-energize box on the Control page for a latched relay
to de-energize.