Page 1
RRE2-A/101 Analogue inputs unit With Ethernet interface Operation manual Version 1.01 rre2-a101_g_en_101...
Page 2
RRE2-A/101 AMiT, spol. s r.o. does not provide any warranty concerning the contents of this publication and reserves the right to change the documentation without obligation to inform anyone or any authority about it. This document can be copied and redistributed under following conditions: 1.
RRE2-A/101 History of revisions Document name: rre2-a101_g_en_101.pdf Revision Date Author of change Changes 30. 3. 2015 Šach J. New document 16. 12. 2016 Šach J. Added required chapters Packing, Storing, Product marking Related documentation Application Note AP0037 – Principles of using Ethernet network file: ap0037_en_xx.pdf...
RRE2-A/101 1. Introduction RRE2-A/101 is a remote inputs unit with Ethernet interface. Device is supplied from factory only with loader. Before first use must be loaded an user application into device. ▪ 4 × mutually galvanically isolated digital input Basic features ▪...
RRE2-A/101 2. Technical parameters Analogue Number of inputs inputs Voltage range 0 V DC to 10 V DC Frequency range 0 Hz to 10 kHz Galvanic isolation Galvanic isolation strength 1000 V AC /1 minute *) Max input current 5 mA at 10 V DC Reverse polarity protection Max.
Page 7
RRE2-A/101 Software Device is supplied with loader, which enables software downloading via Ethernet line. equipment Components with reduced lifetime Claims of Equipment is intended to operate up to 1 400 m above the sea level. Equipment is designed to meet the Temperature Class TX.
RRE2-A/101 2.2. Recommended drawing symbol Following drawing symbol is recommended for the RRE2-A/101 unit. Only part of it will be visible in following examples. RRE2-A/101 AGND1 AGND2 AGND3 AGND4 AIN1 AIN2 AIN3 AIN4 Fig. 2 - Recommended drawing symbol for RRE2-A/101...
RRE2-A/101 3. Unit marking Unit RRE2-A/101 has a type label on its top side Location of the label is shown on following picture. RRE2-I/101 TYPE xxxxxxxx xx-xx-xx-xx-xx-xx APP x.xx / LDR x.xx 802.3af, Class 0 WEIGHT 0.76 kg TEST OK-MU...
RRE2-A/101 3.1. Producer type label RRE2-A/101 TYPE xxxxxxxx xx-xx-xx-xx-xx-xx APP x.xx / LDR x.xx 802.3af, Class 0 WEIGHT 0.75 kg TEST OK-MU HiPot HiPot-OK DATE 16.12.2016 Fig. 4 - Example of design of the type label Description Data Note Logo AMiT...
RRE2-A/101 4. Conformity assessment The equipment meets the claims of Czech government decree NV616/2006; the conformity assessment has been performed in accordance with harmonized standard EN 50121-3-2:2006 Tested in accordance Type of test Classificati with standard EN 55011:2007 Industrial, scientific and medical Complies *) equipment –...
Page 13
RRE2-A/101 Electromagnetic compatibility (EMC) – EN 61000-4-29:2000 Complies Part 4-29: Electromagnetic compatibility (EMC) – Part 4-29: Testing and measurement techniques – Voltage dips, short interruptions and voltage variations on d.c. input power port immunity tests Railway applications – Rolling stock...
RRE2-A/101 5. Elements on the front panel Fig. 5 - Elements on the front panel RRE2-A/101 Elements on Element Element name the front panel Unit power supply Analogue inputs LED for unit's status indication The RESTORE button 5, 7 Ethernet line state LED indication...
RRE2-A/101 6. Power supply Unit RRE2-A/101 can be powered only by DC power supply 24 V. Fig. 6 - Power supply connector location Connector X3 Connector Signal Description Unit chassis Power supply, ground Power supply 24 V DC 15/27 rre2-a101_g_en_101...
RRE2-A/101 7. Inputs Unit RRE2-A/101 has four, mutually galvanically isolated analogue inputs. Signal connected to unit's inputs must comply with parameters stated in chapter 2. Technical parameters. Connector X3 Connector Signal Description Not connected AGND1 Analogue Ground input 1 Not connected...
RRE2-A/101 8. Ethernet Connectors X1 and X2 used for connection of Ethernet interface are located on front side of the unit. LEDs indicating line status are located above Ethernet connectors. Fig. 8 - Location of Ethernet connectors and indication LEDs...
RRE2-A/101 9. System LEDs LED indicator marked with “OK” and “PW”, is used for unit’s status indication is located on the front panel. Fig. 10 - Location of system LEDs Status Colour Status Description indication Green Power supply voltage is not connected...
RRE2-A/101 10. Configuration All configuration of RRE2-A/101 unit can be performed via Ethernet interface. Some changes in setting will take effect after restarting the unit. 10.1. Factory setting Unit is fitted with “RSTR” button to restore unit into factory setting. The button should be pressed while switching ON unit’s power supply.
RRE2-A/101 11. Mounting 11.1. Mounting instructions Unit RRE2-A/101 is to be mounted to panel in switchboard 11.2. Mounting apertures Device can be mounted in any position. Two M5 screws are used for mounting. Fig. 12 - Unit backward assembly RRE2-A/101...
PE terminal of power supply connector must be connected with local installation earthing terminal. All connections to PE terminal must be done with lowest impedance possible. Technical parameters of unit RRE2-A/101 are guaranteed only when these wiring rules are applied. 21/27...
RRE2-A/101 12. Factory settings Factory Parameter Default value setting IP address 192.168.1.1 Network mask 255.255.255.0 Default gateway 0.0.0.0 12.1. Software equipment Before first use – a user application must be loaded into device. RRE_configurator tool is used for application loading. User application and configuration tool can be downloaded from product project website.
RRE2-A/101 14. Packing Protective Unit is packed in protective bubble wrap. package Unit is stored in paper box. Label Sticker on the box contains following information: Item Description TYPE RRE2-A/101 NETTO 0.75 kg BRUTTO 0.9 kg 1 pc Serial number –...
RRE2-A/101 15. Storing To prevent damage of the device, follow these rules. Product in a Product in original packaging must be stored under the conditions specified in chapter Chyba! Nenalezen zdroj odkazů.. Chyba! Nenalezen zdroj odkazů.. package Product must not come into contact with water, oil or any other liquids, that can damage the packaging.
RRE2-A/101 16. Maintenance Device requires no periodic control, nor maintenance. Cleaning Depending on equipment usage, the dust is to be removed occasionally from equipment. The equipment can be cleaned by dry soft brush or vacuum cleaner, only when turned-off. rre2-a101_g_en_101...
RRE2-A/101 17. Waste disposal Electronics The disposal of electronic equipment is subject to the regulations on handling disposal electrical waste. The equipment must not be disposed of in common public waste. It must be delivered to places specified for that purpose and recycled.