K3G500-PB38-19
4.3.3 Cable routing
Water must be prevented from reaching the cable gland along the cable.
NOTE
Damage caused by moisture penetration.
Moisture can penetrate into the terminal box if water is
constantly present at the cable glands.
→ To prevent the constant accumulation of water at the cable
glands, the cable should be routed in a U-shaped loop
wherever possible.
→ If this is not possible, a drip edge can be produced by
fitting a cable tie directly in front of the cable gland for example.

4.4 Factory settings

Factory settings made for the device by ebm-papst.
Mode parameter set 1
PWM control
Mode parameter set 2
PWM control
Fan/device address
01
Max. PWM / %
100
Min. PWM / %
5
Save set value to
Yes
EEPROM
Set value requirement
Analog (linear)
Direction of action
Positive (heating)
parameter set 1
Direction of action
Positive (heating)
parameter set 2
Item no. 55264-5-9970 · ENU · Change 260717 · Approved 2022-06-23 · Page 9 / 15
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com