DAMAGES, LOSS OF PROFITS OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT LIABILITY. In no event shall responsibility of ABB JOKAB SAFETY for any act exceed the individual price of the product on which liability asserted.
System Structure ..........................12 Assumptions ..............................12 Safety Function and Safe State ........................12 10 Functional Safety Data ........................13 Functional Safety Data BT50(T) ........................13 11 Useful life time ........................... 14 Installation and commissioning ......................... 14 Proof Test procedure ............................14 12 Technical data ...........................
SE-434 39 Kungsbacka Sweden Scope The purpose of these instructions is to describe how to use the safety relay BT50(T) in control circuits that are related to functional safety. Prerequisites It is assumed that the reader of this document has knowledge of the following: ·...
This manual contains information on using the safety relay in control circuits that are related to functional safety. The BT50(T) is designed to connect safety devices, such as emergency stops, directly in the voltage supply circuit to the relay. This relay can be used to expand the safety outputs of Pluto.
The NC output 41 – 42 should only be used for monitoring purposes e. g. indication lamp for emergency stop pressed. The BT50T is the same as BT50 except that it also has delay time selectable outputs and additional information output relay. This is explained in the following connection diagrams.
Controlled monitoring of external BT50(T) as emergency stop and Hatch with automatic reset. contactor, relay, valve or Jokab control relay with Start and Stop Safety’s expansion relays. function. * BT50 has additional power terminals A1 and A2. 2TLC172316M0201, rev E www.abb.com/ jokabsafety 2015-09-30...
Connection examples More connection examples can be found at www.abb.com/ jokabsafety or in the Safety Handbook. 2TLC172316M0201, rev E www.abb.com/ jokabsafety 2015-09-30...
Installation Attach the BT50(T) on a 35mm DIN rail and use the information in section 4 ‘Connections’ in this manual to connect power supply and safety devices for your need. Terminals The connection block is detachable without cables having to be disconnected.
Operation LED indication LED is on when Supply voltage is OK. LED is on when the safety outputs are activated. Led is on when auto-reset condition is fulfilled. 2TLC172316M0201, rev E www.abb.com/ jokabsafety 2015-09-30...
LED indicator “Out”. The “Out” LED lights when the safety outputs are On. The safety outputs of the BT50(T) open when the power supply is disconnected at A1, A2 or both A1 and A2(Read the Safety Level information at chapter 3).
Safety Function and Safe State Safety Function When the input of the BT50 is de-energized, the output is de-energized. When the input of the BT50T is de- energized, the output is de-energized according to the time settings. Safe state The safe state is when all three NO safety outputs are de-energized.
10 Functional Safety Data Functional Safety Data BT50(T) Parameters acc. to IEC 61508 Values Device type Mode of operation Low Demand Mode or High Demand Mode Safety function Output relays in OFF state when input is de-energized λ 7562.2 FIT λ...
The failure rates have been calculated according to worst case stress region for inductive load, DC. The output relays in BT50(T) have a mechanical life time of 10.000.000 cycles. Installation and commissioning During installation all aspects regarding the SIL level of the loop must be considered.
Model overview Type Article number Description BT50 2TLA010033R0000 BT50 BT50T 2TLA010033R1000 BT50T Dimensions All measurements in millimetres. Connector blocks are detachable (without cables having to be disconnected) 2TLC172316M0201, rev E www.abb.com/ jokabsafety 2015-09-30...