Note for connecting armoured cable:
 It is necessary to check back with the Adolf Schuch GmbH before installing other
!
explosion-proof cable glands or explosion-proof locking screws than the ones supplied!
Connecting an emergency battery
In its delivery state, there is no electrical connection between the emergency battery and the
emergency light unit.
 The electrical connection between the battery and the unit can only be established or
!
broken in a non-explosive atmosphere!
 If no power supply is present, even if the light fitting is connected to the emergency
battery, it will not enter emergency lighting mode!
The electrical connection between the emergency battery and emergency light unit should be
established as follows:
Version without battery box:
Attach the connector of the red battery cable leading to the emergency light unit to the positive pole
of the emergency battery.
Version with battery box:
Open the battery box by loosening the locking screws and flip open the lid.
Remove the protective cap from the connector of the battery cable.
Attach the connector of the battery cable to the socket in the battery box. Check the catch
mechanism of the plug connection.
Close the lid of the battery box and tighten the locking screws.
4.3 How to close the light fitting
Join diffuser with included reflector and housing together.
Hook the clamp lockings into the diffuser and fix it.
After closing the light fitting take care that the whole gasket is effective.
5. Commissioning
If a power supply is present, the battery connected to the emergency light unit will be charged. The
signal LED will indicate this state by means of a steady green light.
 After the initial setup, the emergency battery must be charged for 12 hours. From a
!
physical point of view, the full capacity of the battery is only available after 3 or 4 charge-
discharge cycles.
If a battery contact failure is indicated despite an existing connection to a power supply and to the