Taco 00e Series Instruction Sheet page 2

Infinitely variable speed, ecm high-efficiency circulator
Hide thumbs Also See for 00e Series:

Advertisement

Figure 2:
PREFERRED PIPING
FOR CIRCULATORS
ON BOILER SUPPLY
ZONE
ZONE
3
2
ALTERNATE PIPING
FOR CIRCULATORS
ON BOILER RETURN
ZONE 3
V3
V3
2
ZONE
1
ZONE 2
ZONE 1
V3
ZONE 1
ZONE 2
V3
V3
LAST
AIR PURGING
SEQUENCE
BY ZONE
KEY:
VI, V2, V3 = SHUT-OFF ISOLATION VALVE
P = TACO CIRCULATOR WITH IFC
FF = FAST FILL BOILER FEED VALVE
PV4 = PURGE VALVE
RECOMMENDED PURGING STEPS:
1. CLOSE V1, PV4, V2
2. OPEN V3
3. OPEN FF VALVE
4. OPEN V2, PV4, TO PURGE LAST ZONE
FIRST (ZONE 3)
5. CLOSE FF VALVE
6. CLOSE V2, PV4
7. REPEAT STEPS 1 TO 6 FOR EACH
ADDITIONAL ZONE, PURGE ZONE 1 LAST
8. OPEN V1 WHEN ALL ZONES ARE
PURGED
9. ADJUST SYSTEM TO DESIRED OPERATING
FILL PRESSURE IF REQUIRED
LAST
AIR PURGING
SEQUENCE
BY ZONE
ZONE 3
V3
FIRST
3
FIRST