Produce and Consume a Tag
26
2. On the Connection tab in the Produced Tag Connections dialog box,
click Advanced. The Advanced Options dialog box opens.
3. In the Minimum RPI box, enter the smallest requested packet interval
(fastest rate) at which consumers may consume data from the tag.
4. In the Maximum RPI box, enter the largest packet interval (slowest
rate) at which consumers may consume data from the tag. Rockwell
Automation recommends using the default value of 536870.9 ms.
5. Select the Provide Default RPI to Consumer for Out-of-Range
Requests check box to enable the producing tag to provide an RPI to a
consuming tag whenever a consuming tag has an RPI outside the range
of the producer's Minimum and Maximum RPI, and then in the
Default RPI box, enter the value that the producer provides to the
consumer.
Important:
Select Allow Consumed Tags to Use RPI Provided by Producer on the
Advanced tab in the Controller Properties dialog box to allow negotiations
to use the RPI provided by the producer.
6. Click OK to close the Advanced Options dialog box.
7. Click OK to close the Produced Tag Connections dialog box.
Rockwell Automation Publication 1756-PM011J-EN-P - February 2018