Cisco 3700 Series Hardware Installation Manual page 62

Cisco systems routers hardware installation guide
Hide thumbs Also See for 3700 Series:
Table of Contents

Advertisement

Power Connections
In
Figure
Figure 3-19
+
+
In
Figure
if Va equals Vb (within 0.25 V).
When connecting source A and source B with common positive terminals, if source A and source B
Caution
voltages are unequal by more than 0.25 V, the higher-voltage source can discharge into the lower-voltage
source through the A- and B- input terminals. Excessive discharging currents through these terminals
can cause one or both of the dual input DC power supply's internal A- or B- fuses to open, resulting in
lack of redundancy or system failure. When source A and source B are within 0.25 V, discharge current
is minimal.
When source A and source B are wired with common negative terminals, as in
Note
does not occur and there is no restriction requiring that source A and source B voltages be equal.
Cisco 3700 Series Routers Hardware Installation Guide
3-16
3-19, source A and source B share common negative terminal connections.
Connecting Source A and Source B with Common Negative Terminals
A-
Va
A+
B+
Vb
B-
3-20, source A and source B share common positive terminal connections. This is allowed only
Chapter 3
Installing the Router
Figure
3-19, discharging
OL-2180-08

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents