Download Print this page

Potter PAD100-ZM Installation Manual

Zone module

Advertisement

Quick Links

Installation Manual: PAD100-ZM Zone Module
NOTICE TO THE INSTALLER
This manual provides an overview and the installation instructions for the PAD100-ZM module. This module is only compatible with
addressable fire systems that utilize the PAD Addressable Protocol.
All terminals are power limited and should be wired in accordance with the requirements of NFPA 70 (NEC) and NFPA 72 (National
Fire Alarm Code). Failure to follow the wiring diagrams in the following pages will cause the system to not operate as intended. For
further information, refer to the control panel installation instructions.
The module shall only be installed with listed control panels. Refer to the control panel installation manual for proper system
operation.
1. Description
The PAD100-ZM uses one (1) SLC loop address when monitoring two (2) Class B or one (1) Class A circuit. The module is used to
supervise a zone of conventional 2-wire smoke detectors on an Initiating Device Circuit (IDC). The module requires and supervises
a 24VDC auxiliary power connection. The 24VDC power source must be either a Potter IPA series addressable panel, or a Potter
PSN series power supply. The IDC may be wired as two individual Class B circuits or one Class A circuit which is selectable by an
on board DIP switch. The module mounts on either an UL Listed 2-1/2" deep 2-gang box or 1-1/2" deep 4" square box.
The PAD100-ZM includes one red LED to indicate the module's status. In normal condition, the LED flashes when the device is
being polled by the control panel. When an input is activated, the LED will flash at a fast rate. If the LED blink has been disabled
via the programming software, in a normal condition the LED of the device will be off. All other conditions remain the same.
2. Setting the Address
All PAD protocol detectors and modules require an address prior to connection to the panel's SLC loop. Each PAD device's
address (i.e., detector and/or module) is set by changing the dip switches located on the device. PAD device addresses are
comprised of a seven (7) position dip switch used to program each device with an address ranging from 1–127.
Figure 1. PAD Device Dip Switch Addresses Table (Addresses 1–127)
1
2
4
8 16 32 64
1
27
2
28
3
29
4
30
5
31
6
32
7
33
8
34
9
35
10
36
11
37
12
38
13
39
14
40
15
41
16
42
17
43
18
44
19
45
20
46
21
47
22
48
23
49
24
50
25
51
26
52
1
2
4
8 16 32 64
Note: Each "gray" box indicates that the dip switch is "On," and each "white" box indicates "Off."
The examples shown below illustrate a PAD device's dip switch settings: the 1st example shows a device not addressed where all
dip switch settings are in the default "Off" position, the 2nd illustrates an addressed PAD device via the dip switch settings.
Figure 2. Examples of PAD Device Showing Default Dip Switch Setting (Unaddressed) & Addressed PAD Device
1 2 4
8
16
32 64
Potter Electric Signal Company, LLC
1
2
4
8 16 32 64
1
2
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
1
2
1
2
4
8 16 32 64
All dip switches are
On
shown in the "Off"
position.
Off
St. Louis, MO
Document 5406308-A 02/16
firealarmresources.com
4
8 16 32 64
1
2
4
8 16 32 64
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100
101
102
4
8 16 32 64
1
2
4
8 16 32 64
1 2 4
8
16
32 64
On
Off
Phone: (800) 325-3936
1
2
4
8 16 32 64
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
122
123
124
125
126
127
1
2
4
8 16 32 64
Example shows this PAD device's
address = 42. Dip switches #2, 8 &
32 are in the "On" position.
www.pottersignal.com
PAGE 1 OF 4

Advertisement

loading
Need help?

Need help?

Do you have a question about the PAD100-ZM and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Potter PAD100-ZM

  • Page 1 1. Description The PAD100-ZM uses one (1) SLC loop address when monitoring two (2) Class B or one (1) Class A circuit. The module is used to supervise a zone of conventional 2-wire smoke detectors on an Initiating Device Circuit (IDC). The module requires and supervises a 24VDC auxiliary power connection.
  • Page 2 INSTALLATION MANUAL: PAD100-ZM ZONE MODULE When the PAD100-ZM is used to monitor two individual Class B circuits a single device address is assigned; each input is then identified as a sub-point of the module address. For example, if the address number is assigned as "8", the "B1" input will be "8.1", and the "B2"...
  • Page 3 INSTALLATION MANUAL: PAD100-ZM ZONE MODULE Figure 4. Example of Wiring a PAD100-ZM as Class A MOVE THE “CL-A” DIP SWITCH TO “UP” POSITION FOR CLASS A WIRING NOTE: END-OF-LINE RESISTOR IS NOT REQUIRED FROM FACP OR PREVIOUS MODULE TO NEXT MODULE...
  • Page 4 Retrofit Base Adaptor 70-501000-003, Identifier MAFE1 (for series 70-201000 Bases, Models -001,-002,-003 and -005). Duct Housing with Detector Base DN-51, Identifier DH22FE5 (for CPD-7051 and PSD-7155 detectors only). POTTER (Max. No. Of Detectors Per Zone is 25) PS-24 HD-3 (HOCHIKI)