4.3.4 Fan Relay Delay Setting – "Frd"
To select the Fan Relay Delay setting, in normal mode, push the Next button to get to "Con" or the Configuration
menu. Then push the Enter button to enter the Con menu. The eighth selection is the "Frd" or Fan Relay Delay. Push
Next seven times to get to "Frd" then Enter. If the delay is "0" (disabled) push Next to change it to 1, 3, 5, or 10
minutes (flashing) then push Enter to confirm the change (solid) and push Enter again to return to "Frd" in the Con
menu. Push Next until "End" is displayed then push Enter to get back to normal operation.
4.3.5 Fan Relay Latching Setting – "FrL"
To select the Fan Relay Latching Option, in normal mode, push the Next button to get to "Con" or the Configuration
menu. Then push the Enter button to enter the Con menu. The tenth selection is the "FrL" or Fan Relay Latching
Option. Push Next nine times to get to "FrL" then Enter. If latching is "OFF" push Next to turn it to "ON" (flashing)
then push Enter to confirm the change (solid) and push Enter again to return to "FrL" in the Con menu. Push Next
until "End" is displayed then push Enter to get back to normal operation.