1 Description
The TR-STSR (recessed) and TR-STSS (surface mount) single Tele-
phone Stations are used with the TR-FFT Series Fire Fighter's Tele-
phone.
The TR-STSR/TR-STSS are compatible with the Triga Fire Fighters
Telephone TR-FFT Series. The Single Telephone Station Series has a
handset with a push-to-talk switch that is used for communication with
the main FFT controller or the other remote handsets.
Figure 1 shows the single mount
telephone station.
Figure 1 Telephone Chassis
1.1 Compatibility
The TR-STSR/TR-STSS is compatible with the Triga Series Fire Fighter
Telephone. For additional information, refer to the following Installation
Manuals.
Document
TR-FFT Manual
2 Mounting Options
There are two options to mount the TR-STSR (recessed) and TR-STSS
(surface mount). Figure 3 shows the components of the Breakglass Kit.
hammer
Figure 3 Breakglass Kit
Figure 2 shows the backbox with
the mounting holes.
Backbox
Figure 2
Document Part Number
LS10309-001TR-E
Tempered Glass
TR-STSR/TR-STSS Single Telephone Station
Product Installation Document
PN LS10308-001TR-E:A 04/27/21 ECN: 151608
Figure 4 shows the TR-STSR
recessed-mount door with the
keylock.
Recessed door
Figure 4 TR-STSR Recessed-
Mount Door with Keylock
3 System Wiring
The following list the wiring specifications.
Riser Wiring Resistance (maximum)
Wiring Distance at 14AWG (maximum) 10,000 ft. (3048 m)
WARNING: THE SYSTEM WIRING FOR TELEPHONES
!
WITH COILED CORD HANDSETS MUST NOT BE
CONNECTED TO THE OUTSIDE WIRING. ALSO, DO
NOT RUN THE SAME CONDUIT OR CABLE TRAY AS
THE POWER OR CABLE TV LINES.
3.1 Telephone Wiring Connection
After the enclosure is mounted and the system wiring is completed,
assemble the telephones with the coiled cord handsets. To assemble the
telephones with the coiled cord handsets, refer to the following steps.
1.
Attach the system wiring to the terminal block on the telephone
chassis assembly.
2.
Insert the 6-32 nut in the backbox. Do not tighten the 6-32 nuts.
3.
Position and connect the telephone chassis assembly in the
backbox.
4.
To install the trim ring on the backbox, use the 6-32 wing nuts. Do
not tighten the 6-32 nuts.
5.
Position and install the door assembly. To secure the door assembly,
tighten the wing nuts.
Figure 5 shows the TR-STSS
surface-mount door with the
keylock.
Surface-mount door
Figure 5 TR-STSS Surface-
Mount Door with Keylock
50 ohms

Advertisement

loading
Need help?

Need help?

Do you have a question about the TR-STSR and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for TRIGA TR-STSR

  • Page 1 2 Mounting Options After the enclosure is mounted and the system wiring is completed, There are two options to mount the TR-STSR (recessed) and TR-STSS assemble the telephones with the coiled cord handsets. To assemble the (surface mount). Figure 3 shows the components of the Breakglass Kit.
  • Page 2 Figure 6 shows the wiring assembly of the TR-STSR/TR-STSS tele- phone connection. TR-FFT Audio TR-FFT Audio Audio - TR-FPJ Audio Audio + TR-FPJ Audio TR-STSS Audio TR-STS Audio Connect to the TR-FFT-SLC Terminal TB4 connectors or the other mini- monitors.

This manual is also suitable for:

Tr-stss