BRACKENHEATH BR1191 Instructions page 2

Remote 3 hour emergency pack

Advertisement

Self-Testing
The emergency pack is preprogramed for periodic monthly and annual self-testing. Once installed, the emergency pack will automatically
run the respective monthly and annual self-test programs.
Self-Test Mode
Emergency Routine
During the periodic monthly self-test, the LED load will operate in emergency mode at a reduced light output for
Monthly
the duration of 2 minutes. After 2 minutes, the LED load will return to normal operation at full brightness.
During the periodic annual self-test, the LED load will operate in emergency mode at a reduced light output for
the duration of 3 hours. After 3 hours, the LED Load will return to normal operation at full brightness.
Note: If the LED indicator colour turns YELLOW during the annual emergency test, it is possible that:
Annual
To troubleshoot, check connections between the emergency pack and the LED load.
Manual Testing
During the installation and commissioning of the remote emergency pack, the integrated test button can be used to simulate the periodic
monthly and manual self-testing programs. The emergency pack enters different test modes depending on the duration the test button is
pressed for. Manual testing does not impact or change the auto-testing modes.
Manual Test Mode
Testing Procedure
Press and hold the test button for 4-5 seconds and release the test button when the LED indicator colour turns
RED . The emergency pack will now simulate the monthly self-test and the LED Load will operate at reduced
Monthly
brightness for 2 minutes. To abort the simulation test, press and release the test button and the LED load will
return to normal operation.
Press and hold the test button for 7-10 seconds and release the test button when the LED indicator colour turns
GREEN. The emergency pack will now simulate the annual self-test and the LED load will operate at reduced
brightness for 3 hours. To abort the simulation test, press and release the test button and the LED load will
Annual
return to normal operation.
Note: Manual testing can also be carried out by switching off the unswitched supply with a key-switch.
Routine Test Record
Monthly Test
Date
Functional test
Functional test
Functional test
Functional test
Functional test
Functional test
Functional test
Functional test
Functional test
Functional test
Functional test
Functional test
Three hour test
Specification
Input Voltage:
Output power:
Emergency Duration:
Battery Charging Time:
Emergency Output
Voltage:
Battery Type:
INS0103 V1.2 11/20 NPD 0653
Either the battery is not fully charged, or its capacity has depreciated.
The LED load is not connected
Year 1
Sign:
220-240V 50Hz
3W
3 Hours
24 Hours
12-60V DC
6V 2.5Ah Ni-Cd
Year 2
Date
Sign:
Test Switch:
LED Indicators:
Housing Material:
Dimensions (LxWxH):
UK: Panattoni Park Luton Road Chalton Bedsfordshire LU4 9TT UK
EU: Unit 16 Ashbourne Ind. Est. Ashbourne Co. Meath A84 W972 Ireland
Year 3
Date
Sign:
Yes
Green – Battery fully charged
Red – Battery charging
Yellow – Battery fault
Steel
200x100x33mm
Deta Electrical Company Limited
deta.co.uk Technical Helpline: +44(0)1582 544 548