4.2.2

Input Message 3 Using Microphone

1. Enter programming mode at main control panel.
2. Select option 9 VIP-VCM Maint.
3. Select option 2 Local Recording.
4. Select which module you wish to have the playback from.
5. Select the circuit on the selected module you wish the playback to be from.
6. When ready press the button on the microphone in and say your message.
Note: If a message is already stored in user message 3 memory location, then the message heard from the
microphone will only be heard and not recorded when the microphone is activated. See Table 4-2.
7. To save the message, release the button on the microphone.
8. If you wish to hear your message played back, press Switch 1 on the VIP-VCM.
If you are not satisfied with the recorded message, erase it (see Section 4.2.3) and then
repeat steps 1 through 8.
4.2.3

Erasing User Message 3

To erase the message stored in message 3 memory location follow these steps:
1. Enter programming mode at main control panel.
2. Select option 9 VIP-VCM Maint.
3. Select option 2 Local Recording.
4. Select which module you wish to have the playback from.
5. Select the circuit on the selected module you wish the playback to be from.
6. Momentarily press switch 4 on the VIP-VCM. The active LED for switch 4 will come on
while the message is being erased. When the message is erased both LEDs for switch 1
and 4 will turn off.
4.2.4

Using 7780 Software

The 7780 software is a software support utility that is used to download recorded messages (in
.ske format stored on your PC hard drive) to the various message locations of the VIP-Series
controls. Messages can be uploaded from the VIP-Series control, stored, and used again in
similar installations. The 7780 software can also be used to move messages to different
message locations. For example, move message 1 to message 3 memory location.
To read/write SKE formatted messages to and from the main panel, follow these steps:
1. Make sure that panel is in normal standby mode.