Page 2
Where the consequences of failure may be severe, back-up controls are essen- tial. Although the safety of the installation is the responsibility of the user, Chromalox will be glad to make equipment recommendations. Principle of Operation — Control action of these thermostats is provided through the principle of liquid volume change.
Page 3
To avoid this, carefully follow these procedures. A. Be sure that thermostat shaft is fully counter-clockwise (see Figure 12). With thermostat knob held in the indicated OFF position, carefully replace enclosure cover while feeling for proper engagement of shaft coupling.
Page 4
3. Without disturbing the shaft setting, loosen the thermostat knob set-screw and re-align dial setting accordingly. Retighten knob set-screw. 4. Recheck for thermostat operation as per steps 2 and 3 and make further calibration adjustment if indicated. 5. Recheck of thermostat operation following final adjustment completes the calibration procedure.