Safety requirements and installation instructions

2 Safety requirements and installation instructions
2.1

Installation instructions

The device is associated equipment with an EPL [Ga], [Da] (category 1) of the ignition protection
type "intrinsic safety" and can be installed as a device with the EPL Gc (category 3) in the potentially
explosive area of Zone 2. The intrinsically safe electrical circuits can be routed up to Zone 0 /
Zone 20. It meets the requirements from the following standards.
EN 60079-0, EN 60079-11, EN 60079-15
For detailed information, please refer to the declarations of conformity.
The installation, operation, and maintenance must be carried out by personnel with electrotechnical
qualifications. Follow the described installation instructions.
Adhere to the applicable conditions and safety regulations (including national safety regulations)
and the general rules of engineering during set-up and operation.
Observe the safety information, conditions, and limits of use specified in the product documentation.
Comply with them.
Opening or modifying the device is not admissible. Do not repair the device yourself; instead, you
should replace it with an equivalent device. Repairs must only be performed by the manufacturer.
The manufacturer is not liable for damage resulting from violations of this.
The protection type IP20 (IEC/EN 60529) of the device is intended for a clean and dry environment.
Do not expose the device to any mechanical and/or thermal stresses that exceed the described lim-
its.
Only use the device up to a pollution degree of 2 according to IEC 60664-1.
The connected, non-intrinsically safe electrical circuits must have a maximum overvoltage
category II according to IEC 60664-1.
The device must be taken out of operation if it is damaged, has been improperly stressed or stored,
or malfunctions.
The device complies with the EMC regulations for industrial areas (EMC class A). It may cause EMC
problems if used in residential areas.
The products must be installed according to all relevant standards for electrical systems in poten-
tially explosive areas.
Only use copper cables as connecting cables.
2.2

Intrinsic safety

The device is approved for intrinsically safe (Ex i) electrical circuits up to Zone 0 (gas) and Zone 20
(dust) of the Ex area. The safety technology values for intrinsically safe equipment and the connect-
ing lines must be observed for the hook-up process (EN 60079-14) and the values specified in this
installation note and/or the EU examination certificate must be observed.
During measurements on the intrinsically safe side, make sure to observe the valid conditions rele-
vant to the interconnection of intrinsically safe equipment. Only use the approved measuring devic-
es in intrinsically safe electrical circuits.
If the device has been used in non-intrinsically safe electrical circuits, using it again in intrinsically
safe electrical circuits is prohibited! Clearly mark the device as not intrinsically safe.