Unit Readings
Compressor
Voltage
Amperage
Condenser Fan motor
Amperage
Temperature
Ambient
Outdoor Coil Discharge Air
Compressor Discharge Line
Indoor Return Air
Indoor Coil Discharge Air
Pressures
Suction (Vapor)
Liquid
STEP 2 Confirm DC voltage output on compressor
solenoid plug
1. Shut power off to outdoor unit.
2. Supply 24 volts AC control voltage to the wire ends of
the full wave rectifier plug. Listen for a click" as the so-
lenoid is energized. See figure 6.
rectifier plug leads
solenoid fusite
compressor
fusite
terminals
compressor
FIGURE 6
3. Unplug the full wave rectifier plug from the fusite con-
nection on the compressor.
4. Turn the low voltage power back onto the unit. Supply
24VAC to the wires of the full wave rectifier plug. Set
volt meter to DC volts and measure the DC voltage at
the female connector end of the full wave rectifier plug.
The DC voltage reading should be 1.5 to 3 volts lower
than the input voltage to the plug wire leads. (EX: Input
voltage is 24VAC output voltage is 22VDC). See figure
7.
apply 24vac
terminals
meter
TABLE 1
Compressor Operation
Y1 −
1st-Stage
compressor
fusite
terminals
compressor
If the above checks verify that the solenoid plug is pro-
viding power to cycle into high capacity operation, con-
tinue to step 3 to determine if problem is with solenoid
coil in compressor
STEP 3 Confirm internal unloader solenoid has prop-
er resistance
1. Shut all power off to unit (main and low voltage)
2. Unplug the molded plug from the compressor solenoid
2−pin fusite.
3. Using a volt meter set on the 200 ohm scale
Replace the Compressor under these conditions:
Bad Solenoid
a. Measure the resistance at the 2−pin fusite.The resist-
ance should be 32 to 60 ohms depending on compressor
temperature. If no resistance replace compressor.
b. Measure the resistance from each fusite pin toground.
There should not be continuity to ground. If solenoid coil
is grounded, replace compressor.
Good Solenoid
a. Seals not shifting, replace compressor
b. Slider ring not shifting, replace compressor.
Page 6
Expected Results
2nd-Stage
Same
Higher
Same or Higher
Same
Higher in Cooling
Lower in Heating
Higher
Same
Lower in Cooling
Higher in Heating
Lower
Higher
rectifier plug leads
solenoid
fusite
terminals
meter
FIGURE 7
Y2 −
apply 24vac