Flomotion Systems BE6200 Installation And Operation Manual

Flomotion Systems BE6200 Installation And Operation Manual

Ultrasonic transit-time flow meter

Advertisement

Quick Links

BE6200
Ultrasonic Flow Meter

Advertisement

Table of Contents
loading

Summary of Contents for Flomotion Systems BE6200

  • Page 1 BE6200 Ultrasonic Flow Meter...
  • Page 2 BE6200 Ultrasonic Flow Meter O&M Manual Page 2 Flomotion Systems, Inc ~ FlomotionSystems.com...
  • Page 3 BE6200 Ultrasonic Flow Meter O&M Manual Installation and Operation Manual BE6200 Ultrasonic Transit-Time Flow Meter JUNE 2012 Flomotion Systems, Inc. 165 Creekside Drive, Suite 112 Buffalo, NY 14228-2103 Toll Free (800) 909-3569 Tel: (716) 691-3941 Fax: (716) 691-1253 info@FlomotionSystems.com www.FlomotionSystems.com Flomotion Systems, Inc ~ FlomotionSystems.com...
  • Page 4: Table Of Contents

    BE6200 Ultrasonic Flow Meter O&M Manual Table of Contents I. Introduction ........................ 7 1. Preface ....................................7 2. Characteristics ................................7 3. Operation Principles ..............................8 4. Typical Applications ..............................9 5. Packing List ..................................9 6. Technical Specifications ............................10 (1) DB6200 Version Updates……………………………...……………………………………………….……………...10...
  • Page 5 BE6200 Ultrasonic Flow Meter O&M Manual 6. Selecting a Location for Transducer Mounting ..................18 Preparing the Pipe Surface ............................ 18 7. Optional Data Logger Setup (1) Logger Program Setup / Logger Status…………………………………………………………………………..19 (2) Logger Cable Connection / SD Connection ....................19 III.
  • Page 6 BE6200 Ultrasonic Flow Meter O&M Manual Appendix 4. Pipe Dimensions and Weights ............. 60 Ductile Iron Pipe ................................62 Cast Iron Pipe ................................... 62 Page 6 Flomotion Systems, Inc ~ FlomotionSystems.com...
  • Page 7: Introduction

    Welcome to BE6200 series ultrasonic flow meter. Please read this instruction manual thoroughly before installation and operation. BE6200 ultrasonic flow meter is a time-difference type ultrasonic flow meter, whose transducers are mounted by being clamped to the external surface of a pipe. It measures clean, well-distributed flows of liquids in which the content of suspended particles is minimal.
  • Page 8: Operation Principles

    In industrial sites, the liquids may contain a certain level of impurities and flow conditions are often not very uniform, thereby negatively affecting the performance of the ultrasonic flow meters. But our BE6200 ultrasonic flow meter adopts the most advanced direct time measuring method that considers the influence of temperature and crude inside pipe situation in order to increase the accuracy and the reliability of the result.
  • Page 9: Typical Applications

    BE6200 Ultrasonic Flow Meter O&M Manual 4. Typical Applications  Water supply, drainage, water purification facility  Oil field and petrochemical plants  Power plants(thermal and hydro power plants)  Steel factory and mining industries  Food and beverage plants ...
  • Page 10: Technical Specifications

    ±1.0% of reading above ±1 ft/s Performance Repeatability ±0.2% at 1 to 53 ft/s (0.3 ~16m/s) Linearity 0.5% (1) BE6200 Version Updated to Version 18 Differences Listed: PREVEOUS VERSION 7 VERSION 18 Output : RS232 and 4-20mA Output: RS 485 and 4-20mA...
  • Page 11: Power Connection

    BE6200 Ultrasonic Flow Meter O&M Manual 7. Power Connection Attention: Meter can be badly damaged if a different power from what was specified is supplied. Careful attention is advised. The meter can use standard 120VAC or 24VDC power supply. By default, the meter is provided with the standard 120VAC power type.
  • Page 12: Wire Connections

    BE6200 Ultrasonic Flow Meter O&M Manual 9. Wire Connections (1) Wall Mount Page 12 Flomotion Systems, Inc ~ FlomotionSystems.com...
  • Page 13: Installation And Operation

    BE6200 Ultrasonic Flow Meter O&M Manual II. Installation and Operation The clamp-on type ultrasonic flow meter allows for the simplest and the easiest installation of all types of flowmeters, though careful attention in selecting the measurement point, inputting pipe parameters, fixing the transducers onto pipe, etc.
  • Page 14: Rapid Setup Procedure

    BE6200 Ultrasonic Flow Meter O&M Manual 3. Rapid Setup Procedure (1) Preprograming Each BE6200 is preprogramed with the following values to help reduce setup time. MENU SELECTED VALUE 77 BEEPER SETUP 25. Disable Beeper 30 MEASURE UNITS IN 1. ENGLISH...
  • Page 15: Rapid Programing Setup

    BE6200 Ultrasonic Flow Meter O&M Manual The user can enter into specific windows using the key followed by a 2-digit code. So, for example, in order to go to M13 window, this is the window for inputting the inner diameter of the pipe, press...
  • Page 16: Transducer Mounting Methods

    BE6200 Ultrasonic Flow Meter O&M Manual 5. Transducer Mounting Methods Clamp-on Sensors There are two mounting methods, ‘V’ and ‘Z’. Usually V method is used as standard because it provides longer signal path and therefore more accurate measurement of flow velocity. It is recommended for pipes sizes between 0.5~16”...
  • Page 17: Signal Strength & Quality (M90)

    BE6200 Ultrasonic Flow Meter O&M Manual (1) Signal Strength & Quality The signal strength is indicated by a number between 0.00 ~ 99.9. 0.00 means no signal received and 99.9 means the signal strength is at the maximum. It should be larger than 60.0 for normal operation. The signal quality Q is indicated by a number between 0.00 ~ 99.9.
  • Page 18: Selecting A Location For Transducer Mounting

    BE6200 Ultrasonic Flow Meter O&M Manual 6. Selecting a Location for Transducer Mounting 1. Locate the transducers downstream from the center of the longest available straight run. A location ten pipe diameters or greater downstream from the nearest bend will provide the best flow profile conditions.
  • Page 19: Optional Data Logger Setup

    1 second and the maximum is 24 hours. Set the Log Times to 1-9998 to limit the amount of logs or set it to 9999 (equal to infinity), this will set the BE6200 to continual recording data.
  • Page 20: Display Windows

    BE6200 Ultrasonic Flow Meter O&M Manual III. Display Windows 1. Summary All display windows of BE6200 and their descriptions will be discussed in this chapter. The user can enter display windows following the instruction given in Chapter II, i.e. to realize the communication between the user and the machine.
  • Page 21: Descriptions

    BE6200 Ultrasonic Flow Meter O&M Manual 2. Descriptions (1) Flow/Totalizer Display Menu  FLOW RATE / NET TOTALIZER (M00) Description: This window is only for display. The selection of the unit is made in M31 and M32 windows. If the NET totalizer is unselected, the value shown in the window is replaced by the totalizer last time.
  • Page 22 BE6200 Ultrasonic Flow Meter O&M Manual  DATE AND TIME / FLOW RATE (M04) Description: This window is only for display. This window is for displaying current date, time and flow rate. The time and date can be entered in M60.
  • Page 23 BE6200 Ultrasonic Flow Meter O&M Manual  SYSTEM ERROR CODES (M08) Description: This window is only for display. It shows the status of operation and corresponding status or error) code. There are several error codes, whose implications and solutions are discussed in “ERROR SEARCHING”.
  • Page 24: Initial Setup

    BE6200 Ultrasonic Flow Meter O&M Manual (2) Initial Setup Menu  PIPE OUTER PERIMETER (M10) Description: Input the outer perimeter of the pipe. If the outer diameter is available, please ignore this value and input the outer diameter of the pipe in M11.
  • Page 25 BE6200 Ultrasonic Flow Meter O&M Manual  PIPE MATERIAL (M14) Description: You can select one of the following materials from the list provided; If ‘9. Other’, you must input the corresponding sound velocity of the material in M15. TO DISPLAY WINDOW...
  • Page 26 BE6200 Ultrasonic Flow Meter O&M Manual  LINER THICKNESS (M18) Description: Only when a liner is selected in M16, this menu will be activated. TO DISPLAY WINDOW LINER THICKNESS SELECTION Keypad Selection: Keypad Selection: use keypad numbers to enter size then...
  • Page 27 BE6200 Ultrasonic Flow Meter O&M Manual  FLUID VISCOSITY (M22) Description: Enter the viscosity of the fluid you chose in M20. This is activated only when ‘8. Other’ is selected in M20. TO DISPLAY WINDOW FLUID VISCOSITY SELECTION Keypad Selection:...
  • Page 28 BE6200 Ultrasonic Flow Meter O&M Manual  TRANSDUCER SPACING (M25) Description: This window is only for display of the transducer mounting distance that was calculated based on the parameters input in the foregoing menus. The distance is between the front edges of the transducers.
  • Page 29 BE6200 Ultrasonic Flow Meter O&M Manual  HOLD ON POOR SIGNAL (M28) Description: Select “Yes” to hold the last good flow signal displayed if the flow meter experiences a poor signal condition. This function will allow continued data calculation without interruption.
  • Page 30: Flow Unit Setup

    BE6200 Ultrasonic Flow Meter O&M Manual (3) Flow Unit Setup  MEASUREMENT UNIT (M30) Description: The default is English. The following options are provided; TO DISPLAY WINDOW MEASUREMENT UNIT SELECTION Keypad Selection: Keypad Selection: to make selection then Display Example: 0.
  • Page 31 BE6200 Ultrasonic Flow Meter O&M Manual  TOTALIZER MULTIPLIER (M33) Description: The totalizer multiplier acts as the function to increase the totalizer indicating range. Meanwhile, the totalizer multiplier can be applied to the positive totalizer, negative totalizer and net totalizer at the same time. The following options are available;...
  • Page 32 BE6200 Ultrasonic Flow Meter O&M Manual  TOTALIZER RESET? (M37) Description: Totalizer reset; all parameters are reset. Press ; move arrow to select “YES” or “NO”. After “YES” is selected, the following operations are available; If it is necessary to recover all the factory default, press keys after the above-mentioned characters are displayed on the screen.
  • Page 33: Option Setup Menu

    BE6200 Ultrasonic Flow Meter O&M Manual (4) Option Setup Menu  DAMPING (M40) Description: The damping factor ranges from 0~999 seconds. 0 indicates no damping; 999 indicate the maximum damping. Damping function is used to display the data smoothly. To large of a coefficient will cause the measurement to appear delayed on the display.
  • Page 34 BE6200 Ultrasonic Flow Meter O&M Manual  RESET ZERO (M43) Description: elect “YES”; reset “Zero Point” which was set by the user. TO DISPLAY WINDOW RESET ZERO SELECTION Keypad Selection: Keypad Selection: to make selection then Display Example: Reset Zero ...
  • Page 35 BE6200 Ultrasonic Flow Meter O&M Manual  SYSTEM LOCK (M47) Description: Once the system is locked, any modification is prohibited in the system. However, the parameter is readable, so as to protect proper operation of the instrument. “Unlock” by the password only. The password is composed of 1 to 4 numbers.
  • Page 36: Output/Input Setup Menu

    BE6200 Ultrasonic Flow Meter O&M Manual (5) Output/Input Setup Menu  DATA LOGGER OPTION (M50) Description: Turns On/OFF internal data logger. If ON is selected, 22 logging options appear. DATA LOGGER TO DISPLAY WINDOW LOGGING DATA OPTIONS SELECTION Keypad Selection:...
  • Page 37 BE6200 Ultrasonic Flow Meter O&M Manual  ANALOG INPUT AI5 (M53) Description: This window is only for display. Displays the electric current of AI5 and its corresponding parameters such as temperature, pressure or level. TO DISPLAY WINDOW Keypad Selection: Display Example: Analog Input AI5 [53 AI5= 0.0177, -1.4900...
  • Page 38 BE6200 Ultrasonic Flow Meter O&M Manual  CL 20 mA Output Value (M57) Description: Use this window to set the flow value to 20mA. The flow unit is the same that was set at M31. TO DISPLAY WINDOW OUTPUT VALUE SELECTION...
  • Page 39 Description: This window is only for display. Displays the electronic serial number (ESN) of the instrument. This ESN is the only one assigned to each BE6200 series flow meter ready to leave the factory. The factory uses it for files setup and for management by the user.
  • Page 40 BE6200 Ultrasonic Flow Meter O&M Manual  SELECT COMM PROTOCOL (M63) Description: Select Communication Protocol DISPLAY WINDOW SELECT COMM PROTOCOL COMPATIBLE PROTOCOL Keypad Selection: Keypad Selection: Keypad Selection: to make selection then to make selection then 0. CRL-G 1. SCL-61D(D<50mm ) Select Comm Protocol Display 2.
  • Page 41 BE6200 Ultrasonic Flow Meter O&M Manual  AI5 VALUE RANGE (M66) Description: To input scale range of temperature, pressure or level for the analog input of 4-20mA. For example, the value 10 in the above box represents 4mA and 100 20mA.
  • Page 42 BE6200 Ultrasonic Flow Meter O&M Manual  LCD BACK LIGHT CONTROLLER (M70) Description: LCD can be controlled using this window. Time can be set in seconds with a range of 0-60000 seconds TO DISPLAY WINDOW BACKLIGHT TIME SELECTION Keypad Selection:...
  • Page 43 BE6200 Ultrasonic Flow Meter O&M Manual  #1 ALARM HIGH VALUE (M74) Input the high value of alarm. When the value exceeds this value, it will cause the Description: alarm to be output using hardware OCT or relay as set in M78 and M79.
  • Page 44 BE6200 Ultrasonic Flow Meter O&M Manual  BEEPER SETUP (M77) Description: The following sources can be selected to set off the buzzer. TO DISPLAY WINDOW BEEPER SELECTION Keypad Selection: Keypad Selection: to make selection then Display Example: 0. No Signal 13.
  • Page 45 BE6200 Ultrasonic Flow Meter O&M Manual  RELAY OUTPUT SETEP (M79) Description: Set the system to put Relay output when one of the following sources occurs TO DISPLAY WINDOW RELAY OUTPUT SETUP SELECTION Keypad Selection: Keypad Selection: to make selection then...
  • Page 46: Energy Meter Setup Menu

    BE6200 Ultrasonic Flow Meter O&M Manual (6) Energy Meter Setup Menu  BATCH TRIGGER SELECT (M80) Description: Set the system to put Relay output when one of the following sources occurs TO DISPLAY WINDOW BATCH TRIGGER SELECTION Keypad Selection: Keypad Selection:...
  • Page 47 BE6200 Ultrasonic Flow Meter O&M Manual  AUTOMATIC FLOW AMEND(M83) Description: With the function of automatic flow correction, the flow lost in an offline session can be estimated and automatically adjusted. The estimate is based on the average value, which is obtained from flow rate before going offline and flow measured after going online the next time, multiplied times the time period that the meter was offline.
  • Page 48 BE6200 Ultrasonic Flow Meter O&M Manual  ENERGY TOTLER ON/OFF (M87) Description: Turn on/off the energy totalizing function. TO DISPLAY WINDOW ON/OFF ENERGY TOTLER SELECTION Keypad Selection: Keypad Selection: to make selection then G EL Display Example: Energy Totler ON/OFF ...
  • Page 49: Diagnostics Setup Menu

    BE6200 Ultrasonic Flow Meter O&M Manual (7) Diagnostics Setup Menu  STRENGTH + QUALITY (M90) Description: This window is only for display. Display the measured signal strength and signal quality Q value upstream and downstream. Signal strength is indicated from 00.0~99.9. A reading of 00.0 indicates no signal detected, while 99.9 indicates maximum signal strength.
  • Page 50 Description: This window is only for display. Display the measured ultrasonic average time (unit: μS) and delta time of the upstream and downstream (unit: nS) time. The velocity calculation in BE6200 ultrasonic flowmeter is based on the two readings; especially the delta time will best indicate if the instrument is running steadily.
  • Page 51: Other Options Setup Menu

    BE6200 Ultrasonic Flow Meter O&M Manual (8) Other Options Setup Menu  POWER ON/OFF TIME (M+0) Description: To view the power on/off time and flow rate for the last 64 update times to obtain the offline time period and the corresponding flow rate. Enter the window, press ENT to display the last update before the last 64 times of on/off time and flow rate values.
  • Page 52 BE6200 Ultrasonic Flow Meter O&M Manual  ON/OFF TIMES (M+4) Description: This window is only for display. Displays how many time the unit has been powered up. TO DISPLAY WINDOW Keypad Selection: Display Example: ON/OFF Times [+4 00000067  CALCULATOR (M+5) Description: This window is a calculator which has the ability of functional operation.
  • Page 53 BE6200 Ultrasonic Flow Meter O&M Manual  TOTAL FLOW THIS YEAR (M+8) Description: Net totalizer for this year TO DISPLAY WINDOW Keypad Selection: Display Example: Total Flow This Year 2000 Gal Flomotion Systems, Inc ~ FlomotionSystems.com Page 53...
  • Page 54: Trouble Shooting

    BE6200 Ultrasonic Flow Meter O&M Manual III. Trouble Shooting With highly reliable design, the BE6200 ultrasonic flowmeter has a low failure rate. However, problems may occur as a result of unskillful handling, setting errors or working in an extremely undesirable working condition.
  • Page 55: Error Code Causes And Solutions

    BE6200 Ultrasonic Flow Meter O&M Manual Error Code Causes and Solutions CODE M08 DISPLAY CAUSE SOLUTION System Normal System operates normally Contact the manufacturer SCPU Fatal Error Hardware failure Contact the manufacturer * No signal received * Make sure the sensor is close to the pipe.
  • Page 56: 20 Ma Output Calibration

    BE6200 Ultrasonic Flow Meter O&M Manual 4-20 mA Output Calibration How to calibrate the analog output In general, there is no need to calibrate the analogue output since it has been calibrated in factory. However, when conducting current loop calibration, if you find the current value shown in M58 differs from the actual current shown in the ammeter, you do need to recalibrate the analogue output.
  • Page 57: Appendix 1. Sound Velocity And Viscosity Of Liquids

    BE6200 Ultrasonic Flow Meter O&M Manual Appendix 1. Sound Velocity and Viscosity of Liquids SOUND SOUND VISCOSITY VISCOSITY LIQUID VELOCITY LIQUID VELOCITY (mm2/s) (mm2/s) (m/s) (m/s) Water 20ºC 1482 Glycerin 1923 1180 Water 50ºC 1543 0.55 1250 0.80 Water 75ºC...
  • Page 58: Appendix 2. Sound Velocity For Various Common Materials

    BE6200 Ultrasonic Flow Meter O&M Manual Appendix 2. Sound Velocity for Various Common Materials Pipe Material PIPE MATERIAL SOUND VELOCITY (m/s) Steel 3206 2286 Aluminum 3048 Brass 2270 Cast Iron 2460 Bronze 2270 Fiber, Glass-Epoxy 3430 Glass 3276 Polyethylene 1950...
  • Page 59: Appendix 3. Sound Velocity In Water (1 Atm) At Different Temperatures

    BE6200 Ultrasonic Flow Meter O&M Manual Appendix 3. Sound Velocity in Water (1 ATM) at Different Temperatures Unit: t(oC), v(m/s) 1402.3 2525 1496.6 1542.5 1555.1 1407.3 1499.2 1543.5 1555.0 1412.2 1501.8 1544.6 1544.9 1416.9 1504.3 1545.5 1554.8 1421.6 1506.7 1546.4 1554.6...
  • Page 60 BE6200 Ultrasonic Flow Meter O&M Manual Appendix 4. Pipe Dimensions and Weights Nominal Nominal Schedule Wall Schedule Wall Pipe size Pipe size Inch Designations inch inch Inch Designations inch inch (inch) (inch) 0.083 4.334 0.049 0.307 0.120 4.260 0.0405 0.068 0.269...
  • Page 61 BE6200 Ultrasonic Flow Meter O&M Manual Nominal Nominal Schedule Wall Schedule Wall Pipe size Pipe size Inch Designations inch inch Inch Designations inch inch (inch) (inch) 0.218 21.564 0.156 12.438 0.250 21.500 0.180 12.390 0.375 21.250 0.250 12.250 0.500 21.000 0.330...
  • Page 62 BE6200 Ultrasonic Flow Meter O&M Manual DUCTILE IRON PIPE Standard Classes (Inside Diameters) Cement Lining Outside Size Diameter Class Class Class Class Class Class Class ** Std. **Bbl. inch Inch Thickness Thickness 3.96 3.46 3.40 3.34 3.28 3.22 3.16 4.80 4.28...