Baud Rage
Max Masters
Max Info Frame
Enable Bias
Enable Termination
BACnet Network Number
Router Setup:
Send Establish Connection
to Network
Establish Connection
Termination Time
BBMD (BACnet Broadcast Management Device) & FDR (Foreign Device Registration) Setup
Note: If the IP Router being used can transmit broadcast messages, the Distribution Mask can be set to the same mask as on
the IP Router. This will cause any broadcast messages to be handled by the IP router.
Foreign Devices are BACnet devices that are on a different IP Subnet to the TP-NM-R/2000 and have been registered with
it to send/receive BACnet broadcasts.
t: +44 (0)161 406 6480 ● e: sales@titanproducts.com ● w: www.titanproducts.com
UK DESIGNED, DEVELOPED AND MANUFACTURED
Ref: SKU 224
Select the Baud Rate from the drop down menu. The baud rate should be the same for
each device on the network.
The maximum permitted MS/TP master device address. If unknown, or future devices are
expected, then this should be left at the default 127.
The number of messages that can be sent once a token has been received. A value of
between 10 and 20 is recommended.
It is recommended to bias the network at either a single point or at each end of a
segment.
It is recommended to terminate both ends of the network using 120 ohm resistors.
This is the BACnet Network number for MS/TP Port.
This instructs a BACnet half router to establish communications when the PTP link is
currently inactive.
The time in seconds that the PTP connection should remain active in the absence of
messages being sent. Use a value of 0 to indicate a permanent connection.
The BACnet Broadcast Management Device (BBMD) page is used
to control the Broadcast Distribution Table (BDT) for the primary
and secondary IP Ports. It also displays any Foreign Devices that are
registered on each Port.
Note: The maximum number of BDT entries is set to 50 for each port.
The Maximum number of Foreign Devices is also set to 50 for each
Port.
BDT entries can be added, removed and the whole table submitted
using the webpage buttons. The table can also be updated via
BACnet. To add a BDT, enter the IP address of the BBMD devices
and its associated Distribution Mask
(default = 255.255.255.255). Once all BBMD devices have been
added for each port select submit.