  • Page 1 NETMASTER TP-NM-R/1000 BACnet MS/TP to IP Router...
  • Page 2: Specification

    The Titan Products TP-NM-R/1000 NetMaster Router is a high performance, intelligent and secure communications product designed to route BACnet MS/TP network points to BACnet IP. Designed and manufactured by Titan Products in the UK, the router’s feature set includes smart commissioning HTML5 web pages that automatically re-size for PC, mobile and tablet screens.
  • Page 3 Dimensions 90mm Connections Power Supply BACnet RS485 MSTP 24V AC/DC 3 Wire 0v 24V COM +ive -ive Ethernet IP RJ45 Reset t: +44 (0)161 406 6480 ● e: sales@titanproducts.com ● w: www.titanproducts.com UK DESIGNED, DEVELOPED AND MANUFACTURED Ref: SKU 205...
  • Page 4 To comply with the EIA-485 standard, the maximum number of nodes per segment shall be 32 and any additional nodes will require the use of repeaters. If only Titan controllers are on the MS/TP network, the number of controllers may be increased but this will depend on the network traffic, the baud rate being used and the length/route of the cable.
  • Page 5 • Default Gateway (192.168.1.254) • Username ‘admin’ and password ‘admin’ • The user screens allow the user to view: The NetMaster TP-NM-R/1000 Home Screen and current firmware settings • The NetMaster TP-NM-R/1000 set up • Admin pages • BBMD, FDR setup & Broadcast Distribution Tables •...
  • Page 6 Setup Device Setup: Device ID A unique network wide device number in the range 0 to 4194302. Ensure this is unique to all other devices on the network. Device Name This is the name of the device E.g. Router 1. APDU Timeout This is the time to wait in m/s before re-transmitting an unacknowledged message APDU Retries...
  • Page 7 Baud Rage Select the Baud Rate from the drop down menu. The baud rate should be the same for each device on the network. Max Masters The maximum permitted MS/TP master device address. If unknown, or future devices are expected, then this should be left at the default 127. Max Info Frame The number of messages that can be sent once a token has been received.
  • Page 8 Diagnostics The TP-NM-R/1000 includes a Diagnostics webpage which provides real time information of the routers performance and active applications. This is designed to help with any troubleshooting while on site. For more information contact Titan Products. Updating the TP-NM-R/1000 To update the TP-NM-R/1000 router to the latest software please follow the below instructions: Check the ‘Update Enabled’...
  • Page 9 Backup and Restore Backing up software files: Select the Update tab to view connected controllers and Backup options. To back up the firmware, configuration or RDU screen files within a controller, select the file type you would like to Backup under the Backup dropdown.
  • Page 10 Updating the controllers with new software or restoring from a backup: From with the Update tap, select the controllers you would like to update or restore and press the Update Controllers button. Browse and select the file from the connected PC or Laptop you would like to use to update the controllers. The update will then begin.
  • Page 11 BACnet Protocol Implementation Conformance Statement Date: 8th September 2015 Vendor Name: Titan Products Ltd Product Name: NetMaster Router 1000 Product Model Number: TP-NM-R/1000 BACnet Protocol Revision: BACnet Interoperability Building Blocks Supported (Annex K): DS-RP-A/B Data Sharing – ReadProperty – A/B DS-RPM-A/B Data Sharing –...
  • Page 12 Standard Object Types Supported Data Object Type Property Optional Writable Range Restriction Device Object_Identifier Object_Name Object_Type System_Status Vendor_Name Vendor_Identifier Model_Name Firmware_Revision Application_Software_Version Location ● ● max 100 characters Description ● ● max 100 characters Protocol_Version Protocol_Revision Protocol_Services_Supported Protocol_Object_Types_Supported Object_List Max_APDU_Length_Accepted Segmentation_Supported APDU_Timeout ●...
  • Page 13 ISO 10646 (UCS-2) ISO 10646 (UCS-4) JIS X 0208 Titan Products Ltd. Reserve the right to alter or amend this product in any way without notification. t: +44 (0)161 406 6480 ● e: sales@titanproducts.com ● w: www.titanproducts.com UK DESIGNED, DEVELOPED AND MANUFACTURED...
  • Page 14 SETUP By default the Netmaster has the IP address 192.168.1.151 and this is the access point to change any settings. Access the NetMaster To access the NetMaster, you will need to be on the same subnet as it, i.e. 192.168.1.x. This can be done in one of two ways: an Ethernet crossover cable or a network router/switch/hub.
  • Page 15 You should see the following page. From here you will need to click the Local Area Connection: After clicking, you will be presented with a window where you can set the properties of the network adapter. Click the Properties button: t: +44 (0)161 406 6480 ●...
  • Page 16 Another window will appear to allow you to set the IP settings for the adapter. Select ‘Internet Protocol Version 4 (TCP/ IPv4)’ and then click the Properties button: The following properties window will be shown. Select ‘Use the following IP address:’ and set the IP address to ‘192.168.1.1’, the Subnet mask to ‘255.255.255.0’...