Idem SCR-7 User Information page 2

Safety relays

Advertisement

Safety Relays from IDEM
User Information
Depending on the application or the result of the risk assessment according to EN ISO 13849-1, the de-
Applications
vice must be wired as shown in Fig. 1 to Fig. 11.
Emergency Stop
Circuit
Starting Behavior
Feedback Loop
Power supply
and
Safety contacts
Commissioning
Note: The items listed under "Electrical connection" must be observed during commissioning.
Procedure
1. Wiring emergency stop circuit:
Wire the emergency stop circuit according to the required
Performance Level determined (see Fig. 1 to Fig. 5).
2. Wiring start circuit:
Wire the start circuit according to Fig. 6 or Fig. 7 to set the
starting behavior.
Warning:
If "Automatic start" is set, bear in mind that the safety
contacts will switch immediately after the power supply is
connected. If "Monitored manual start" is set, the start
button must be opened after wiring.
3. Wiring feedback loop:
If your application provides for external contactors or ex-
pansion modules, connect them to the device according to
Fig. 8 or Fig. 9.
4. Wiring power supply:
Connect the power supply to terminals A1 and A2 (Fig. 10).
Warning: Wiring only in de-energized state.
Fig. 1:
Two-channel emergency stop
circuit with short circuit and earth
fault monitoring.
(category 4, up to PL e)
Fig. 3:
Single-channel emergency stop
circuit with earth fault monitor-
ing.
(category 1, up to PL c)
Fig. 5:
Two-channel emergency stop
with pnp-outputs/OSSD-outputs
with short circuit monitoring.
(category 4, up to PL e)
Fig. 6:
Monitored manual start.
It is monitored that the start
button was opened before the
emergency stop button closes.
(Prerequisite: operating voltage
must not be interrupted.)
Fig. 8:
Feedback loop for monitored manual
start:
The feedback loop monitors contactors
or the expansion modules .
Fig. 10:
Power supply A1 and A2.
(Power supply according to techn.
Data )
SCR-7
Fig. 2:
Two-channel emergency stop
circuit with earth fault monitoring.
(category 3, up to PL d)
Fig. 4:
Two-channel sliding guard
monitoring with short circuit and
earth fault monitoring.
(category 4, up to PL e)
Warning:
In order to activate earth fault monitoring, the PE must be
connected only to the power supply unit in accordance with
EN60204-1.
Corresponded to the application, the starting circuit have to
be wired according to Fig. 6 or Fig. 7.
Fig. 7:
Automatic start.
Max permitted delay during
closing of the safety switches on
Warning:
S12 and S13:
Safety contacts switch
S12 before S13: 300 ms
immediately when the
S13 before S12: any
power supply is connected.
Fig. 9:
Feedback loop for automatic start:
The feedback loop monitors contac-
tors or the expansion modules .
Fig. 11:
Connecting load to safety contacts.
(Figure shows example.
Voltage „+V" according to techn.
Data)
5. Starting the device:
Switch on the operating voltage.
Warning:
If the "Automatic start" starting behavior is set, the safety
contacts will close immediately.
If the "Monitored manual start" starting behavior is set, close
the start button to close the safety contacts.
LEDs K1 and K2 are lit.
6. Triggering safety function:
Open the emergency stop circuit by actuating the connec-
ted safety switch. The safety contacts open immediately.
7. Reactivation:
Close the emergency stop circuit. If "Automatic start" is
selected, the safety contacts will close immediately.
If the "Monitored manual start" starting behavior is set, close
the start button to close the safety contacts.
H04
Ver. A
E61-329-00