Download Print this page
System Sensor M200EA Series Quick Start Manual
System Sensor M200EA Series Quick Start Manual

System Sensor M200EA Series Quick Start Manual

Advertisement

Available languages

Available languages

Quick Links

Fig./Abb. 1
1:2 DIN
1:1 M200E-SMB
Sollevare
Levantar
Anheben
Fig./Abb. 2
Fig./Abb. 3
a
+
+
e
+
NC
C
f
NO
Fig./Abb. 4
DOP-IOD068
0905
EN54-17: 2005
21
EN54-18: 2005
D200-501-00
22 mm
60°C
-20°C
2
1
Rotate
Plug
Ruotare
Inserire
Girar
Conectar
Drehen
Einhaken
Clip / Agganciare
3
Acoplar / Einrasten
3
1
Lift
Push down
Premere
Precionar
hacia abajo
Runterdrücken
2
Rotate / Ruotare
Girar / Drehen
M201EA
1
2
M201EA
3
4
5
6
7
8
8 9
10
11
12
OUT
(i)
+
(iii)
Fig./Abb. 5
Honeywell Products and Solutions Sàrl
(Trading as System Sensor Europe)
Zone d'activités La Pièce 16
CH-1180 ROLLE, Switzerland
Pittway Tecnologica S.r.l, Via Caboto 19/3, 34147 Trieste, Italy
M201EA
EN
This manual is intended as a quick reference installation guide. Please refer to the
control panel manufacturers installation manual for detailed system information.
The M200 series of modules are a family of microprocessor controlled interface
devices permitting the monitoring and/or control of auxiliary devices. The M201EA
is an output module that allows the control of auxiliary devices such as fire shutters
or sounders.
A single tri-colour LED indicates the status of the module. In normal conditions, the
LED can be set by command from the control panel to blink green when the module is
polled. When the control panel switches the relay to the energised state the LED can
be set to continuous green.
SPECIFICATIONS
Operating Voltage Range:
Maximum Standby Current
LED Current (Red):
LED Current (Yellow):
Isolator features:
Humidity:
Maximum Wire Gauge
INSTALLATION
Note: These modules must only be connected to control panels using compatible
proprietary analogue addressable communication protocols for monitoring and control.
M200 series modules can be mounted in several ways (See Figure 1):
1:1 An M200E-SMB custom low profile surface-mounting box. The SMB Base is
affixed to mounting surface, and then the module and cover are screwed onto
the base using the two screws supplied. Box dimensions: 132 mm (H) x 137 mm
(W) x 40 mm (D)
1:2 The DIN bracket on top allows mounting onto standard 35 mm x 7.5 mm "Top Hat"
DIN rail inside a control panel or other suitable enclosure. Install and remove as
shown in Figure 1:2.
Wiring to all series M200 modules is via plug in type terminals capable of supporting
conductors up to 2.5 mm²
Disconnect loop power before installing modules or sensors.
The module address is selected by means of rotary decade address switches (see
Figure 4). A screwdriver should be used to rotate the wheels to select the desired
address, either from the front or the top of the module. (Note: The number of addresses
available will be dependent on panel capability, check the panel documentation for
information on this.)
Short Circuit Isolators
All M200 series modules are provided with short circuit monitoring and isolators on the
intelligent loop. If required the isolators may be wired out of the loop to facilitate the
use of the modules on high current loaded loops, for example if sounders are used.
To achieve this, the loop out positive should be wired to terminal 5 rather than terminal
2. See the relevant wiring diagram for details.
M201EA WIRING
The M201EA can be wired for either Supervised (Figure 2) or Non-Supervised
(Figure 3) operation respectively.
M201EA Single Output Module with Supervised Output
When the module is used in supervised mode and power is supplied to the module,
a switched negative input on terminal 12 can be used to signal an external fault
condition, such as a power supply fault. Loss of power is also supervised in this mode
such that if the supply voltage falls below 7V a fault indication is achievable. Note that
the use of this fault mode is dependant on panel software. Please contact the panel
(ii)
manufacturer for further details.
PSU monitoring is not available when the module switches the output to Alarm.
Wire as follows (see Figure 2):
a: T1 Loop Output -. b: T2 Loop Output +. c: T3 Loop Input -. d: T4 Loop Input +
e: T5 Loop Output +. If short circuit isolation is not required, loop output+ should be
wired to terminal 5 and not 2. Terminal 5 is internally connected to terminal 4.
f: To enable output circuit supervision, the link supplied must be fitted across
terminals 6 and 7, and the load must be polarised.
INSTALLATION INSTRUCTIONS
FOR THE M201EA OUTPUT MODULE
15 to 32VDC (Min 16.5VDC for LED operation)
160 µA - No Communication
1.5 mA
5.5 mA
see S00-7100
5% to 95% relative humidity (non-condensing)
2.5 mm²
CAUTION
CAUTION
Electrostatic Sensitive Device
Observe precautions when handling and making connections
I56-4401-001

Advertisement

loading
Need help?

Need help?

Do you have a question about the M200EA Series and is the answer not in the manual?

Questions and answers

Summary of Contents for System Sensor M200EA Series

  • Page 1 5 and not 2. Terminal 5 is internally connected to terminal 4. Honeywell Products and Solutions Sàrl DOP-IOD068 0905 (Trading as System Sensor Europe) f: To enable output circuit supervision, the link supplied must be fitted across EN54-17: 2005 Zone d’activités La Pièce 16 terminals 6 and 7, and the load must be polarised.
  • Page 2 h: External power supply max. 32V DC, min. 7V DC. In supervised mode, the module ATTENZIONE monitors the power supply voltage across terminals 10 and 11 to ensure it does Dispositivo sensibile alle scariche elettrostatiche not drop below 7V, and also monitors for a switched negative fault signal from Effettuare i collegamenti e maneggiare con cautela the power supply to terminal 12 (optional).
  • Page 3 INSTRUCCIONES PARA LA INSTALACIÓN Cuando el módulo se utiliza en modo supervisado y con alimentación, se puede utilizar una entrada negativa conmutada en el terminal 12 para indicar una avería DE LOS MÓDULOS DE SALIDA M201EA externa, como un fallo de alimentación. En este modo, también se supervisa la pérdida de alimentación, de manera que si la tensión cae por debajo de 7V, se indica Este manual ha sido preparado para que sirva como guía de referencia rápida en la una avería.
  • Page 4 INSTALLATIONSANLEITUNG f: Zur Aktivierung der Ausgangsüberwachung muss die mitgelieferte Verbindung FÜR DIE MODULE M201EA zwischen Klemme 6 und 7 und eine gepolte Last angeschlossen werden. h: Externes netzteil max. 32VDC, min. 7VDC. Im überwachten Betrieb wird die Betriebsspannung zwischen den Klemmen 10 und 11 überwacht und Diese Kurzbedienungsanleitung ermöglicht einen schnellen Überblick zur Installation geprüft, dass der Wert 7V nicht unterschritten wird.

This manual is also suitable for:

M201ea