HAINKE IFC 12 Operation Manual

Electronic solenoid valve control

Advertisement

Quick Links

Operation manual
Electronic solenoid valve control
IFC 12
Version V1.0 · 04/2022

Advertisement

Table of Contents
loading

Summary of Contents for HAINKE IFC 12

  • Page 1 Operation manual Electronic solenoid valve control IFC 12 Version V1.0 · 04/2022...
  • Page 2 ​ Hainke Filteranlagen GmbH An der Imbäke 7 27798 Hude Germany Tel: +49 4408 8077-0 Fax: +49 4408 8077-100 Email: info@hainke.de Internet: www.hainke.de Electronic solenoid valve control · V1.0 · 04/2022 Operation manual...
  • Page 3: Table Of Contents

    Notes on particular conditions for safe use in hazardous area Zone 22  ... 2 Intended use ......................3 Technical data  ...................... 4 Assembly and installation ..................Electrical connection  ..................Dimension plan IFC 12  ................... Connection plan IFC12  .................. 5 Start-up  ......................... 6 Control and message functions ................Remote control input F  ..................
  • Page 4: Safety

    • EN 55014-1:2012 • EN 60204-1:2012 • EN 60079-0:2014 • EN 60079-31:2014 The named standards and directives can be examined at HAINKE Filteranlagen GmbH . Marking electrical equipment for potentially explosive atmospheres Marking according to Dir- ective 2014/34/EU: II 3D...
  • Page 5: Operation Of The Control In The Mounting Enclosure

    2 | Intended use Areas of use Category 3 Zone 22 non-conductive dust Equipment group II Cat- Equipment designed to be capable of functioning in conformity egory 3D with the operating parameters established by the manufacturer and ensuring a normal level of protection. Electrical equipment for use Equipment in this category is intended for use in areas in which ex- in areas with combustible...
  • Page 6: Technical Data

    Quiescent current in- typically 40 mA typically 80 mA typically 60 mA Type IFC 12 E in the polycarbonate IFC 12 S in metal chassis mounting enclosure Output data 1 − 12 solenoid valve outputs 24 VDC, output fuse 1.6 A very fast acting, manually activatable with a step switch Output power max.
  • Page 7 3 | Technical data Type IFC 12 E in the polycarbonate IFC 12 S in metal chassis mounting enclosure Allowable ambient temperat- Hazardous area Zone 22: Ta: - - 20 °C ... + 55 °C  5 °C ... + 40 °C Outside the hazardous area: -  20 °C ...+ 40 °C Conformity Low Voltage Directive 2014/35/ Low Voltage Directive 2014/35/ EU (EN 60204-1)
  • Page 8: Assembly And Installation

    Target group Unless assigned otherwise, the assembly and installation are carried out by skilled per- sonnel of HAINKE Filteranlagen GmbH . Work on the electrical installation is only carried out by electrically skilled personnel. Work on live parts is not planned.
  • Page 9: Electrical Connection

    4 | Assembly and installation If mounted outdoors, measures must be taken to protect the enclosure from the weather. Example: Canopy If using in potentially explosive atmospheres, the notes required in these instructions must be complied with. Metal chassis The control in the metal chassis is suitable for mounting in the control cabinet. To this end, the metal chassis is snapped onto the top-hat rail 35 mm to EN 50022.
  • Page 10: Dimension Plan

    4 | Assembly and installation Dimension plan IFC 12 Electronic solenoid valve control · V1.0 · 04/2022 Operation manual...
  • Page 11: Connection Plan

    4 | Assembly and installation Connection plan IFC12 Operation manual Electronic solenoid valve control · V1.0 · 04/2022...
  • Page 12: Start-Up

    5 | Start-up Start-up WARNING Risk of injury due to the escape of a potentially explosive atmosphere consisting of dust/air mixtures ü Operation with the cover open is prohibited. 1. Before opening the cover, ensure that no potentially explosive atmosphere exists. 2.
  • Page 13: Control And Message Functions

    6 | Control and message functions 1. Check for correct actuation of the valves. In the event of error-free ac- tuation, the status message contact remains operated for the entire run. Light-emitting diode is lit without interruption. 1. Following completion of the commissioning, screw the cover back on, check the cable entries.
  • Page 14: Secondary Cleaning

    7 | Fault messages • Direct voltages 12 to 30 V, to 0 V The input is protected against reverse polarity. The function for testing the rated operating pressure is activated by DIP switch 2 in the On position, and is deactivated in the Off position. The switch may also be changed over while the control is in operation.
  • Page 15 7 | Fault messages Message Display Cause of error Remedy • If the compressed air is not to be monitored, set DIP switch 2 to the OFF position Operation manual Electronic solenoid valve control · V1.0 · 04/2022...
  • Page 16 Keeping the World Flowing for Future Generations...