Overview: The FN-1024ULX is a power supply that converts a 115VAC / 60Hz input to a 24VDC regulating output (see specifications below). Specifications: Agency Listings: Battery Backup: • UL File # S4707: • Built-in charger for sealed lead acid or gel type batteries.
LED Diagnostics: Red (DC) Green (AC) Power Supply Status Normal operating condition. Loss of AC. Stand-by battery supplying power. No DC output. Loss of AC. Discharged or no stand-by battery. No DC output. CAUTION: De-energize unit prior to servicing. For continued protection Fig.
Terminal Identification: Terminal Legend Function/Description L, N Connect 115VAC 60Hz to these terminals: L to hot, N to neutral. Do not use the [G] terminal. 8 amp supply current in non-alarm condition with 10 amp supply current during alarm for Fire + DC - - - Alarm Applications.
Page 5
J. Battery capacity required I*1.8 (safety factor) Note: FN-1024ULX power supply is designed to work with batteries up to 65AH. Please note, line [I] must not exceeds 36AH. You have to reduce either stand-by current consumption or stand-by time in order to comply with requirement.
Page 6
Enclosure Dimensions (H x W x D): 15.5” x 12” x 4.5” (393.7mm x 304.8mm x 114.3mm) * The door is included 1.5” 4.615” 4.615” 1.5” (38.1mm) (117.22mm) (117.22mm) (38.1mm) 1.75” (44.45mm) 1.375” (34.925mm) 1.125” (28.575mm) 12.23” 4.5” 4.5” (310.64mm) (114.3mm) (114.3mm) 1.25”...
Page 8
Notes: Hochiki America Corp. 7051 Village Drive, Suite 100, Buena Park, CA 90621-2268, 714-522-2246, Fax: 714-690-7890, www.hochiki.com IIFN-1024ULX G02N - 8 -...