Baldor Reliance CDX7150 Installation & Operating Manual page 13

Integral horsepower dc motor
Table of Contents

Advertisement

Blower Ventilation System
Before loading a force-ventilated motor, be sure that the blowers, cooling fans, or central air supply
systems are operating properly to supply cooling air to the motor. Air filters should also be in place. If you
energize the main fields with the motor at standstill, the blowers or external cooling systems must be left
on. This will prevent excessive heat buildup that will decrease the life of the insulation.
When using field economy circuits to reduce the voltage to the main fields during standstill, blowers do
not need to be left on.
Blower motors should be checked for correct rotation. Don't rely on feeling airflow from the drive end of
the motor. Look at the outline drawing or rotation arrow shown on the blower housing. Refer to Figure
2-1.
Air Inlet
Housing
Impeller
Blades
Airflow
Size
Motor Frame
LM2
180
LM3
180
LM3
210-250
LM4
280
LM6
320-400
LM8
504-506
LM9
508-5012
Note: Motor mounted blower units. Mount on commutator end (opposite drive end of motor. We supply
blowers that are powered by totally enclosed motors (standard). Blowers have a cast aluminum fan
housing with washable, wire mesh filters.
2-4 Installation & Operation
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Figure 2-1 View from Air Inlet (Motor is on Opposite Side)
Table 2−4 Electrical Data - Forced Ventilation Blower Units
HP
RPM
1/40
3000
1/8
3450
115/230
1/8
3450
208-230/460
1/3
3450
208-230/460
1
3450
208-230/460
3/4
1750
208-230/460
3
3450
208-230/460
Volts
Phase
230
1
1
3
3
3
3
3
Hz
Amps
60
0.4
50/60
2.6/1.3
50/60
0.66-0.60/0.30
50/60
1.5-1.4/0.7
50/60
3.1-3.0/1.5
50/60
3.4-3.2/1.6
50/60
8.2-7.6/3.8