American Standard S9X1 Installer's Manual page 43

Upflow/horizontal and dedicated downflow gas-fired, direct/non-direct vent, single stage / two stage condensing furnaces with high efficiency motor
Table of Contents

Advertisement

When penetrating roof with PVC vent pipe, a flexible flashing may be
used for a weather tight seal. Lubricate flexible seal on flashing before
PVC pipe is pushed through the seal. (Field Supplied)
Note: No vent cap is the preferred method for vertical vent
termination in extremely cold climates.
Note: In extreme climate conditions, insulate the exposed pipe above
the roof line with Armaflex type insulation.
Venting Through an UNUSED Chimney
Venting Routed Through a Masonry Chimney
Important: Refer to Section 12.6.8 of NFPA 54 / ANSI 223.1 2012
when routing vent piping through a chimney.
Important: The single wall flue pipe joints must be sealed.
The 90° elbow connection to vertical pipe must be sealed
to prevent condensate leakage to base of masonry
chimney.
Venting Through an UNUSED Chimney
Important: Refer to Section 12.6.8 of NFPA 54 / ANSI 223.1 2012
when routing vent piping through a chimney.
Important: The single wall flue pipe joints must be sealed.
The 90° elbow connection to vertical pipe must be sealed
to prevent condensate leakage to base of masonry
chimney.
VENT FITTING MATERIAL – STAINLESS STEEL
Gas and liquid tight single wall metal vent fitting, designed for
resistance to corrosive flue condensate such as Type 29-4C MUST be
used throughout.
These fittings and fitting accessories are to be field supplied.
DIRECTION OF STAINLESS STEEL FITTING
All stainless steel fitting must be installed with male end towards the
Furnace.
All horizontal stainless steel sections must be positioned with the
seam on top.
All long horizontal sections must be supported to prevent sagging.
All pipe joints must be fastened and sealed to prevent escape of
combustion products into the building.
18-CE12D1-1D-EN
F F u u r r n n a a c c e e G G e e n n e e r r a a l l I I n n s s t t a a l l l l a a t t i i o o n n
PVC PLASTIC VENTING
THROUGH UNUSED CHIMNEY
STAINLESS
STEEL
VENT CAP
(OPTIONAL)
SEE CAUTION
FLUE PIPE
COUPLING TO SUPPORT
PIPE FROM ANGLES
OR OTHER SUITABLE
SUPPORT METHOD
FLUE PIPE
TYPE 29-4C STAINLESS STEEL VENTING
THROUGH UNUSED CHIMNEY
STAINLESS
STEEL
VENT CAP
(OPTIONAL)
SEE CAUTION
6 IN. MIN.
SUPPORT THE SINGLE
WALL FLUE PIPE AND
CENTER IT IN THE
CHIMNEY OPENING WITH
ANGLES AS SHOWN OR
ANOTHER EQUIVALENT
MANNER.
COUPLING
AS REQUIRED
NOTE:
HORIZONTAL VENTING
TO VERTICAL VENTING
6 IN. MIN.
SUPPORT THE SINGLE WALL
STAINLESS STEEL GAS
VENTING AND CENTER IT IN
THE CHIMNEY OPENING WITH
ANGLES AS SHOWN OR
ANOTHER EQUIVALENT
MANNER.
NOTE:
HORIZONTAL VENTING
TO VERTICAL VENTING
43