Test Run Flow Chart - LG A2UW18GFA0 Svc Manual

Multi air conditioner
Hide thumbs Also See for A2UW18GFA0:
Table of Contents

Advertisement

2. Test Run Flow chart

START
Test operation for indoor unit
Operate the unit in cooling mode.
Does Test operation start?
Yes
Is cold air discharged for
more than 3 minutes ?
Yes
Is there any temperature
difference between intake and
discharged air?
Yes
Is the operating current
normal ?
Yes
Operation mode change
to Heating mode
Is hot air discharged ?
After Hot Start
Yes
Normal
• Each indoor unit should be tested.
• If the unit has accessory, it should be tested.
Copyright ©2014 LG Electronics. Inc. All right reserved.
Only for training and service purposes
No
Refer to part4, 6 Electric part
No
Refer to part4, 5 Cycle part
No
No
* Check the load (In/Out Temp.)
* Check pipe length and amount of
refrigerant
* Check for abnormal sound in
outdoor unit (comp.,Fan, others )
No
Refer to Troubleshooting
- 35 -
Part 4. Test Run
Guide
LGE Internal Use Only