Installation, Operation and Maintenance Manual
Please read and save these instructions for future reference. Read carefully before attempting to assemble, install,
operate or maintain the product described. Protect yourself and others by observing all safety information. Failure
to comply with these instructions will result in voiding of the product warranty and may result in personal injury
and/or property damage.

Receiving and Handling

Upon receiving dampers, check for both obvious
and hidden damage. If damage is found, record all
necessary information on the bill of lading and file
a claim with the final carrier. Check to be sure that
all parts of the shipment, including accessories, are
accounted for.
Dampers must be kept dry and clean. Indoor storage
and protection from dirt, dust, and the weather is
ideal. Do not store at temperatures in excess of
100°F (37°C).
This manual is the property of the owner and is required for future maintenance. Please leave it with the owner when
the job is complete.

Table of Contents

General Information ................................................ 1
Receiving and Handling ......................................... 1
Pre-Installation Guidelines ...................................... 2
Electrical Guidelines ............................................... 2
Installation .........................................................3-10
Dampers ................................................................. 3
AMD-xx-TD Series without a Factory Supplied
Controller ................................................................ 4
Actuator ...............................................................4-5
Analog Factory Supplied Controller ..................... 4
Optimal Placement for AMD-xx-TD ................10-11
Minimum Installation Requirements ..................... 12
Maintenance ......................................................... 12
Warranty ............................................................... 12
Our Commitment .................................................. 12
Document 478799
AMD-xx-TD Series
AMD-xx-TD Series
1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the AMD TD Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Greenheck AMD TD Series

  • Page 1: Table Of Contents

    Document 478799 AMD-xx-TD Series ® Installation, Operation and Maintenance Manual Please read and save these instructions for future reference. Read carefully before attempting to assemble, install, operate or maintain the product described. Protect yourself and others by observing all safety information. Failure to comply with these instructions will result in voiding of the product warranty and may result in personal injury and/or property damage.
  • Page 2: Pre-Installation Guidelines

    Out of square, racked, twisted Verify power before wiring actuator. Greenheck is not or misaligned installations can cause excessive responsible for any damage to, or failure of the unit leakage and/or torque requirements to exceed caused by incorrect field wiring.
  • Page 3: Installation

    field. However, if field configuration is NOTE: Greenheck dampers are specifically designed necessary please reference the Vari-Green transmitter and engineered for structural integrity based on model Installation, Operation, and Maintenance Manual and conditions.
  • Page 4: Controller

    AMD-xx-TD Series Ordered with a Factory Supplied Controller When you order a factory supplied controller, it comes with a Greenheck exclusive VAF24-BAC-GTD actuator which has the controller integrate inside of it. The actuator/controller is configured by the factory at the time the unit was ordered for either analog or BACnet operation.
  • Page 5: Bacnet Enabled Factory Supplied Controller

    The controller is designed to modulate the AMD-xx- This controller is designed to modulate the AMD-xx- TD series damper such that it maintains a desired TD series damper such that it maintains a desired cfm setpoint. The setpoint is supplied via a 0-10 VDC cfm setpoint.
  • Page 6: Setting The Actuator/Controller's Bacnet Configuration

    Setting the Actuator/Controller’s Access the Actuator BACnet Configuration 1. Open Internet Explorer and enter the following address: http://192.168.0.10:8080/index.html The actuator’s BACnet configuration including the device instance, MAC address, and baud rate can be accessed through its Ethernet port. Connecting to the Actuator 1.
  • Page 7 Table 1 lists and describes all of the BACnet data points associated with the controller inside the actuator of BACnet enabled AMD-TD series dampers. Name Type Access Description Greenheck AMD-TD Displays the application version AirflowSetpoint Displays the real-time setpoint in cfm CurrentAirflow Displays the real-time volumetric airflow rate in cfm...
  • Page 8 Protocol Implementation Conformation Statement - PICS General Information Date: 11. April 2014 Vendor Name: BELIMO Automation AG Vendor ID: Product Name: VAFB24-OP GTD Product Model Number: Applications Software Version: 1.34.0 Firmware Revision: 1.0.3 BACnet Protocol Revision: Product Description: The device is an air damper control actuator with the added benefit of a built-in programmable controller. Free programming environment allows handling of a wide range of HVAC control applications.
  • Page 9 Object Processing Object Type Optional Properties Writeable Properties Analog Input Description Analog Output Description Present_Value Analog Value Description Present_Value Binary Input Description Active_Text Inactive Text Binary Output Description Present_Value Active_Text Inactive_Text Relinquish_Default 1) Priority_Array 1) Binary Value Description Present_Value Active_Text Inactive_Text Relinquish_Default 1) Priority_Array 1)
  • Page 10: Optimal Placement For Amd-Xx-Td

    Optimal Placement for AMD-xx-TD Damper Series Fans 3/4D Centrifugal Fan Discharge Centrifugal Fan Inlet Vane Axial Fan Discharge Vane Axial Fan Inlet Elbows 1/2D 1.5D 1/2D 90°Elbow Without Vanes 90° Vaned Elbow 1/2D Round Sweep Elbow AMD-xx-TD Series...
  • Page 11 Optimal Placement for AMD-xx-TD Damper Series Takeoffs 1.5D Branch Takeoff B1 Branch Takeoff 2 Transitions 1/2D 1/2D Transition 1 Transition 3 Bellmouth Inlets Rectangular Duct: D= Circular Duct: D = Duct Diameter 4 x Width x Height AMD-xx-TD Series...
  • Page 12: Minimum Installation Requirements

    Damper Maintenance Greenheck's dampers are designed to be trouble free and hassle free under normal operation. Dampers are to be installed square and straight so as to prevent binding during operation. The following annual damper maintenance suggestions will help to insure proper damper operation and increase the life expectancy of the damper.