Page 3
Rooftop KRFN Kentatsu Part. 1 General information 1. Product lineup ................. 4 2. Nomenclature ................5 ...
Page 4
Kentatsu Rooftop KRFN 1. Product lineup Nominal ton Model Function Air outlet Power supply KRFN220CFAN3 Cooling only Side discharge 6.25 KRFN260CFAN3 Cooling only Side discharge KRFN300CFAN3 Cooling only Side discharge KRFN350CFAN3 Cooling only Side discharge 12.5 KRFN440CFAN3 Cooling only Side discharge...
Page 5
T - канальный высоконапорный (свыше 100 Па); V - кассетный четырехпоточный; Y - кассетный однопоточный; Z - кассетный 600х600. Наружный: U - универсальный с воздушным охлаждением Вид климатической техники: R – крышный кондиционер. Символ бренда (производителя): К - KENTATSU General Information...
Rooftop KRFN Kentatsu 1. Features Design flexibility. Compact design and flanges of air flow inlet and outlet as standard. It is suitable for installation in rooftop and ground. Durable construction. Pre-painted exterior cabinet panels pass 1000 hours salt spray test for durability.
Page 8
If the unit is in running with abnormal operation, the LED display will show the error code. Wired controller as standard. Besides Kentatsu controller, other brand thermostat can be matched as optional solution. ...
Rooftop KRFN Kentatsu 2. Specifications Nominal ton (Ton) Model KRFN220CFAN3 KRFN260CFAN3 Power supply 380~415V, 3Ph, 50Hz 380~415V, 3Ph, 50Hz Btu/h 75,000 89,000 Cooling capacity Cooling 1 22.0 26.0 Power input Btu/h 61,400 69,600 Cooling capacity Cooling 2 18.0 20.4 Power input Max.
Page 10
Kentatsu Rooftop KRFN Continued: Nominal ton (Ton) Model KRFN220CFAN3 KRFN260CFAN3 Type Axial Axial Quantity Drive type Direct Direct Motor quantity Outdoor fan Motor model YDK450-6C YDK580-6C Motor capacitor 25µF/450V 25µF/450V Motor input 757/403 820/505 Fan speed 840/550 870/640 Type R410A...
Page 11
Rooftop KRFN Kentatsu Nominal ton (Ton) Model KRFN300CFAN3 Power Supply 380~415V, 3Ph, 50Hz Btu/h 102,000 Cooling capacity Cooling 1 30.0 Power input Btu/h 80,700 Cooling capacity Cooling 2 23.7 Power input 10.3 Max. input consumption 14.8 Max. current 29.2 Indoor air flow 3,500 Default: 80;...
Page 12
Kentatsu Rooftop KRFN Continued: Nominal ton (Ton) Model KRFN300CFAN3 Type Axial Quantity Drive type Direct Motor quantity Outdoor fan Motor model YDK580-6C Motor capacitor 25µF/450V Motor input 820/505 Fan speed 870/640 Type R410A Refrigerant Volume 2.25+2.25 Control Throttle valve Wired controller...
Page 13
Rooftop KRFN Kentatsu Nominal ton (Ton) Model KRFN350CFAN3 Power supply 380~415V, 3Ph, 50Hz Btu/h 120,000 Cooling capacity Cooling 1 35.0 Power input 10.7 Btu/h 100,200 Cooling capacity Cooling 2 29.4 Power input 12.6 Max. input consumption 18.0 Max. current 34.1...
Page 14
Kentatsu Rooftop KRFN Continued: Nominal ton (Ton) Model KRFN350CFAN3 Type Axial Quantity Drive type Direct Motor quantity Outdoor fan Motor model YS1100-6P Motor capacitor Motor input Fan speed 1,120/965 Type R410A Refrigerant Volume 2.35+2.35 Control Throttle valve Wired controller KWC-22...
Page 15
Rooftop KRFN Kentatsu Nominal ton (Ton) 12.5 Model KRFN440CFAN3 Power supply 380~415V, 3Ph, 50Hz Btu/h 150,000 Cooling capacity Cooling 1 44.0 Power input 13.3 Btu/h 125,400 Cooling capacity Cooling 2 36.8 Power input 16.1 Max. input consumption 21.0 Max. current 41.2...
Page 16
Kentatsu Rooftop KRFN Continued: Nominal ton (Ton) 12.5 Model KRFN440CFAN3 Type Axial Quantity Drive type Direct Motor quantity Outdoor fan Motor model YDK550-6E Motor capacitor 25µF/450V Motor input 740/640 Fan speed 880/810 Type R410A Refrigerant Volume 2.8+1.7 Control Throttle valve...
Page 17
Rooftop KRFN Kentatsu Nominal ton (Ton) Model KRFN530CFAN3 Power supply 380~415V, 3Ph, 50Hz Btu/h 180,000 Cooling capacity Cooling 1 53.0 Power input 16.7 Btu/h 146,000 Cooling capacity Cooling 2 42.8 Power input 18.7 Max. input consumption 25.0 Max. current 48.0...
Page 18
Kentatsu Rooftop KRFN Continued: Nominal ton (Ton) Model KRFN530CFAN3 Type Axial Quantity Drive type Direct Motor quantity Outdoor fan Motor model YS1100-6 Motor capacitor Motor input Fan speed 1,120/965 Type R410A Refrigerant Volume 4.9+2.25 Control Throttle valve Wired controller KWC-22...
Page 19
Rooftop KRFN Kentatsu Nominal ton (Ton) 17.5 Model KRFN600CFAN3 Power supply 380~415V, 3Ph, 50Hz Btu/h 208,000 Cooling capacity Cooling 1 61.0 Power input 19.1 Btu/h 181,100 Cooling capacity Cooling 2 53.1 Power input 22.6 Max. input consumption 26.5 Max. current 55.0...
Page 20
Kentatsu Rooftop KRFN Continued: Nominal ton (Ton) 17.5 Model KRFN600CFAN3 Type Axial Quantity Drive type Direct Motor quantity Outdoor fan Motor model YDK550-6E Motor capacitor 25µF/450V Motor input 740/640 Fan speed 880/810 Type R410A Refrigerant Volume 3.7+3.7 Control Throttle valve...
Page 21
Rooftop KRFN Kentatsu Nominal ton (Ton) Model KRFN700CFAN3 Power supply 380~415V, 3Ph, 50Hz Btu/h 240,000 Cooling capacity Cooling 1 70.0 Power input 22.6 Btu/h 199,200 Cooling capacity Cooling 2 58.4 Power input 25.1 Max. input consumption 33.0 Max. current 66.9...
Page 22
Kentatsu Rooftop KRFN Continued: Nominal ton (Ton) Model KRFN700CFAN3 Type Axial Quantity Drive type Direct Motor quantity Outdoor fan Motor model YS1100-6-3 Motor capacitor Motor input Fan speed 1,090/944 Type R410A Refrigerant Volume 5.65+5.65 Control Throttle valve Wired controller KWC-22...
Page 23
Rooftop KRFN Kentatsu Nominal ton (Ton) Model KRFN880CFAN3 Power supply 380~415V, 3Ph, 50Hz Btu/h 300,000 Cooling capacity Cooling 1 87.0 Power input 28.0 Btu/h 251,700 Cooling capacity Cooling 2 73.8 Power input 32.0 Max. input consumption 40.5 Max. current 77.4...
Page 24
Kentatsu Rooftop KRFN Continued: Nominal ton (Ton) Model KRFN880CFAN3 Type Axial Quantity Drive type Direct Motor quantity Outdoor fan Motor model YS1500-6-2 Motor capacitor Motor input Fan speed Type R410A Refrigerant Volume Control Capillary Wired controller KWC-22 Centralized controller (Optional) Ambient temperature (Cooling) °C...
Page 25
Rooftop KRFN Kentatsu Nominal ton (Ton) Model KRFN1050CFAN3 Power supply 380~415V, 3Ph, 50Hz Btu/h 360,000 Cooling capacity Cooling 1 105.0 Power input 34.3 Btu/h 336,300 Cooling capacity Cooling 2 98.6 Power input 41.8 Max. input consumption 49.5 Max. current 94.1...
Page 26
Kentatsu Rooftop KRFN Continued: Nominal ton (Ton) Model KRFN1050CFAN3 Type Axial Quantity Drive type Direct Motor quantity Outdoor fan Motor model YS1500-6-2 Motor capacitor Motor input Fan speed Type R410A Refrigerant Volume 7.6+7.6 Control Capillary Wired controller KWC-22 Centralized controller (Optional) Ambient temperature (Cooling) °C...
Rooftop KRFN Kentatsu 7. Fan performance data KRFN220CFAN3 Static Pressure Item High speed Medium speed Low speed 1,001 Fan speed (rpm) Power input (W) 1,665 1,386 1,164 Air flow (CFM) 3,001 2,647 2,356 1,063 Fan speed (rpm) 50Pa Power input (W)
Page 78
Kentatsu Rooftop KRFN KRFN260CFAN3 Static Pressure Item High speed Medium speed Low speed 1,035 Fan speed (rpm) Power input (W) 1,716 1,432 1,197 Air flow (CFM) 3,074 2,697 2,403 1,081 Fan speed (rpm) 50Pa Power input (W) 1,652 1,409 1,160...
Page 79
Rooftop KRFN Kentatsu Blower drive options Motor Blower Fan speed Model Pulley pitch Dia. Pulley pitch Dia. range (rpm) (inch) (inch) Min. Max. 1,400 4.53~5.25 8.35 KRFN300CFAN3 1,400 4.53~5.25 1,016 7.48 KRFN350CFAN3 1,420 4.53~5.25 8.82 KRFN440CFAN3 1,440 4.53~5.25 1,112 7.48...
Page 80
Kentatsu Rooftop KRFN Similarly, use this RPM value to read the No. of turns (N) by referring to the table of ‘Motor Variable Pitch Pulley Data’. The variable pitch pulley for motor shall be adjusted to this ‘N’ in order to get 3483cfm. First, adjust the motor pulley to 0 turns. Then, make 0.25 turns on the pulley.
Rooftop KRFN Kentatsu 9. Operation limits Outdoor temperature Indoor temperature Cooling only mode 10°C~52°C 17°C~31°C Room relative humidity should be less than 80%. If the unit operates in excess, the surface of the unit may attract condensation. Performance...
Page 100
Kentatsu Rooftop KRFN Part. 3 Installations General information ............... 101 Recommendations ..............102 Lifting ..................103 Installation ................104 Condensate drainage ............. 105 Duct work ................106 Electrical wiring ..............107 ...
Rooftop KRFN Kentatsu 1. General information Warning and cautions appear at appropriate locations throughout this manual. Read these carefully, please. Caution: Read this entire manual before beginning installation procedures. Body injury can result from high voltage electrical components, fast moving fans. For protection from these inherent hazards during installation and servicing, the electrical supply must be disconnected.
Kentatsu Rooftop KRFN 2. Recommendations 2.1 Horizontal airflow application These units are designed and certified for outdoor installation. These units may be installed directly on wood flooring or on Class A, Class B and Class C roof covering material.
Rooftop KRFN Kentatsu Any reduction of the unit clearances indicated in these pictures may result in condenser coil starvation or the recirculation of warm condenser air. Actual clearances which appear to be inadequate should be reviewed. 3. Lifting ...
Kentatsu Rooftop KRFN 4. Installation 4.1 For roof top applications using a field fabricated frame and ducts: The frame must be located and secured by bolting or welding to the roof. Flashing is required. The hole in the roof must be prepared in advance of installing the unit.
There must be a weatherproof seal where the duct enters the structure. Complete the installation. 5. Condensate drainage Model X value (mm) Model X value (mm) KRFN220CFAN3 20 ≤ X ≤ 40 KRFN260CFAN3 20 ≤ X ≤ 40 KRFN300CFAN3 20 ≤ X ≤ 40 KRFN350CFAN3 20 ≤ X ≤ 40 KRFN440CFAN3 20 ≤...
Kentatsu Rooftop KRFN 6. Duct work All conditioned air ductwork should be insulated to minimize heating and cooling duct losses. Use a minimum of 2 inches of insulation with a vapor barrier. The outside ductwork must be weatherproofed between the unit and the building.
24V power source is applied to the control circuit. Wiring length between wired controller and unit (One way) Min. wire size (mm 0.75 0.75 Main power supply parameters: Model Main power Main power switch Fuse KRFN220CFAN3 380~415V, 3Ph~, KRFN260CFAN3 50Hz KRFN300CFAN3 Installation...
Page 108
100A KRFN1050CFAN3 Model Wires for power supply Type of wires 3 × UL1015 9AWG 3×6mm² + 2×3mm² KRFN220CFAN3 2 × UL1015 12AWG 3 × UL1015 7AWG 3×10mm² + 2×6mm² KRFN260CFAN3 2 × UL1015 9AWG 3 × UL1015 7AWG 3×10mm² + 2×6mm²...
Page 109
Rooftop KRFN Kentatsu Power supply wiring diagram KRFN220CFAN3, KRFN260CFAN3, KRFN300CFAN3, KRFN350CFAN3, KRFN440CFAN3, KRFN530CFAN3, KRFN600CFAN3, KRFN700CFAN3, KRFN880CFAN3, KRFN1050CFAN3: Wired controller wiring diagram (Standard wired controller) KRFN220CFAN3, KRFN260CFAN3, KRFN300CFAN3, KRFN350CFAN3, KRFN440CFAN3, KRFN530CFAN3, KRFN600CFAN3, KRFN700CFAN3, KRFN880CFAN3, KRFN1050CFAN3: The standard wired controller model of these units is KWC-22. When KWC-22 is connected, the switch SW3 should be set to ON.
Page 110
Kentatsu Rooftop KRFN KRFN220CFAN3, KRFN260CFAN3: The standard wired controller model of these units is KFC-14. Installation...
Rooftop KRFN Kentatsu 8. Start-up Before starting unit: Is the unit properly located and level with the proper clearance? Is the duct work correctly sized, run, taped, insulated, and weatherproofed with proper unit arrangement? Is the wiring properly sized and run according to the unit wiring diagram? Are all the wiring connections tight, including those in the unit? ...
Kentatsu Rooftop KRFN 9. Safety control Functions Minutes delay for the compressor start-up: At the beginning of energizing, 3-minutes delay should be taken to start the compressor. While after the stop of the compressor, 7-minutes delay should be taken to restart the compressor.
Page 113
Rooftop KRFN Kentatsu Error & protection code KRFN300CFAN3, KRFN350CFAN3, KRFN440CFAN3, KRFN530CFAN3, KRFN600CFAN3, KRFN700CFAN3, KRFN880CFAN3, KRFN1050CFAN3 : Type Content Code Remarks Normal Standby ------ Normal Constraint cool Normal Error Compressor phase sequence error or phase lack Condenser pipe temperature sensor (T3) in system A...
Page 114
Anti-freezing protection of evaporator in system B Protection Protection of outdoor ambient temperature Notes: If same protection which includes all system for 2-stage products is triggered 3 times within 1 hour, the unit should be power-off to recovery. KRFN220CFAN3, KRFN260CFAN3: LED1 LED2 LED3 Content (Red)
Page 115
Rooftop KRFN Kentatsu Continued: LED1 LED2 LED3 Content (Red) (Yellow) (Green) Low temperature protection of evaporator FLASH High temperature protection of condenser FLASH Wired controller communication error FLASH FLASH Low pressure protection FLASH FLASH Phase sequence error or phase default:...
Page 116
Kentatsu Rooftop KRFN Evaporator pipe temperature sensor (T2) error: Condenser pipe temperature sensor (T3) error : Ambient temperature sensor (T4) error: Indoor side room temperature sensor (T1) error : Over-current protection of compressor: Installation...
Page 117
Rooftop KRFN Kentatsu High pressure protection: High discharge temperature protection : Wired controller communication error : Installation...
Page 119
Rooftop KRFN Kentatsu Over-current protection of indoor side fan motor : Comprehensive protection of outdoor side fan motor : Installation...
Page 120
Kentatsu Rooftop KRFN High temperature protection of condenser : Low temperature protection of evaporator: Anti-freezing protection of evaporator : Installation...
Page 121
Rooftop KRFN Kentatsu Protection of outdoor ambient temperature : Installation...
Kentatsu Rooftop KRFN 10. Maintenance Caution Do not operate the unit without the evaporator fan access panel in place. Reinstall the access panel after performing any maintenance. Operating the unit without the access panel may result in severe personal injury.
Page 123
Rooftop KRFN Kentatsu Notes: L=A/64 Model A (mm) KRFN300CFAN3 KRFN350CFAN3 KRFN440CFAN3 KRFN530CFAN3 KRFN600CFAN3 KRFN700CFAN3 KRFN880CFAN3 KRFN1050CFAN3 Measure the belt deflection force, the force should be between the values shown in the following lists. The belt which is too tight or too loose may generate noise and be harmful to the unit.
Page 124
Kentatsu Rooftop KRFN Pull out the filter along the supporting slot. Step 2: Clean the air filter. Vacuum cleaner or fresh water may be used to clean the air filter. If the dust accumulated too much, please use soft brush and mild detergent to clean.
Page 125
Rooftop KRFN Kentatsu Motors and drive system components; Economizer gaskets (Reserved); Safety controls; Electrical components and wiring (For possible replacement and connection tightness); Condenser drainage (For cleaning); Unit duct connections (To check that they are physically sound and sealed to the unit casing);...
Need help?
Do you have a question about the KRFN220CFAN3 and is the answer not in the manual?
Questions and answers