MAX. REFRIGERANT PIPING LENGTH and MAX. HEIGHT DIFFERENCE
MUZ-FD25
MUZ-FD35
MUZ-FD50
ADDITIONAL REFRIGERANT CHARGE (R410A: g)
Outdoor unit
Model
precharged
MUZ-FD25
MUZ-FD35
Outdoor unit
Model
precharged
MUZ-FD50
1,550
NOTE: Refrigerant piping exceeding 7 m requires additional refrigerant charge according to the calculation.
Refrigerant piping: m
Max. Length
A
20
30
Indoor
unit
Max. Height
difference
B
Max. Length
5 m
6 m
0
0
1,150
7 m
0
Max. Height difference
B
12
15
A
Outdoor unit
Refrigerant piping length (one way)
7 m
8 m
9 m
10 m
0
90
120
150
Calculation: X g = 30 g/m × (Refrigerant piping length (m) - 5)
Refrigerant piping length (one way)
10 m
15 m
90
240
Calculation: X g = 30 g/m × (Refrigerant piping length (m) – 7)
14
Piping size O.D: mm
Gas
9.52
12.7
11 m
12 m 13 m 14 m 15 m 20 m
180
210
240
270
20 m
25 m
390
540
Liquid
6.35
300
450
30 m
690